SMOKE DETECTOR
WITH INTERCONNECT
The A5364CA is a low-current, CMOS circuit providing all of the
required features for an ionization-type smoke detector. A networking
capability allows as many as 125 units to be interconnected so that if
any unit senses smoke, all units will sound an alarm. In addition,
special features are incorporated to facilitate alignment and test of the
finished smoke detector. This device is designed to comply with
Underwriters Laboratories Specification UL217.
The internal oscillator and timing circuitry keeps standby power to
a minimum by powering down the device for 1.66 seconds and sensing
smoke for only 10 ms. Every 24 on/off cycles, a check is made for low
battery condition. By substituting other types of sensors, or a switch
for the ionization detector, this very-low power device can be used in
numerous other battery-operated safety/security applications.
The A5364CA is supplied in a low-cost, 16-pin dual in-line plastic
package. It is rated for continuous operation over the temperature
range of 0
C to +50C. Similar devices. with an internal timer to allow
for a period of reduced sensitivity ("hush"), are available as the
A5368CA.
Always order by complete part number: A5364CA .
Data Sheet
26110.7A
ABSOLUTE MAXIMUM RATINGS
(Voltages are referenced to V
SS
)
Supply Voltage Range,
V
DD
.......................... -0.5 V to +15 V
Reverse Battery (10.5 V) ................ 20 s
Input Voltage Range,
V
IN
.................. -0.3 V to V
DD
+ 0.3 V
Input Current, I
IN
........................ 10 mA
Operating Temperature Range,
T
A
............................... 0
C to +50
C
Storage Temperature Range,
T
S
......................... -55
C to +125
C
CAUTION: CMOS devices have input static
protection but are susceptible to damage
when exposed to extremely high static
electrical charges.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
LOGIC
OSC. &
TIMING
HORN
DRIVER
GUARD
DETECT. IN
GUARD
SENSITIVITY
SET
OSC. CAP.
HORN
HORN
SUPPLY
NO CONNECT.
I / O
LOW-V SET
NO CONNECT.
LED
+ SUPPLY
TIMING RES.
FEEDBACK
1
V
DD
Dwg. PC-004-1
2
2
1
V
SS
NC
NC
FEATURES
I
Interconnect Up to 125 Detectors
I
Piezoelectric Horn Driver
I
Guard Outputs for Detector Input
I
Pulse Testing for Low Battery
I
Power-ON Reset
I
Internal Reverse Battery Protection
I
Built-In Hysteresis Reduces False Triggering
I
Temporal Horn Pattern
5364
5364
SMOKE DETECTOR
WITH
INTERCONNECT
115 Northeast Cutoff, Box 15036
Worcester, Massachusetts 01615-0036 (508) 853-5000
FUNCTIONAL BLOCK DIAGRAM AND TYPICAL APPLICATION
Copyright 1998, 1999 Allegro MicroSystems, Inc.
9 V
LOW-V
SET
SUPPLY
+ SUPPLY
I / O
TIMING RES.
FEEDBACK
DETECT.
IN
1
2
OSC. CAP.
NO
CONNECTION
4
POWER-ON
RESET
OSCILLATOR
& TIMING
LOGIC
SENSITIVITY
SET
+
+
+
GUARD
GUARD
HORN 1
HORN
2
LED
NO
CONNECTION
+V
+V
V
DD
1
2
3
5
8
11
10
7
12
6
13
9
14
15
16
V
DD
V
SS
Dwg. FC-001-4
+
+V
5364
SMOKE DETECTOR
WITH
INTERCONNECT
www.allegromicro.com
Test
Limits
Characteristic
Pin
Test Conditions
Min.
Typ.
Max.
Units
Supply Voltage Range
6
Operating
6.0
9.0
12
V
Detector Input Current
15
0 to 40% RH, V
IN
= 0 to 9.0 V
--
--
1.0
pA
Input Offset Voltage
14-15
Active Guard
--
--
100
mV
16-15
Active Guard
--
--
100
mV
15-13
Detect Comparator
--
--
50
mV
Hysteresis
13
No Alarm to Alarm
90
130
170
mV
Common Mode Range
14-15
Guard Amplifier
2.0
--
V
DD
- 0.5
V
13-15
Smoke Comparator
0.5
--
V
DD
- 2.0
V
Active Guard Impedance
14
to V
SS
--
10
--
k
16
to V
SS
--
500
--
k
Oscillator Period
12
No Alarm
1.34
1.67
2.00
s
Alarm
32
40
48
ms
Oscillator Pulse Width
4
8.0
10
12
ms
Low Voltage Threshold
6
T
A
= 0 to 50
C
7.2
--
7.8
V
Sensitivity Adj. Voltage
13
V
13
/V
DD
, pin 13 open circuit
48.5
50
51.5
%
Horn Output Voltage
10-11
I
OUT
= 16 mA, V
DD
= 9.0 V
--
0.1
0.5
V
I
OUT
= 16 mA, V
DD
= 7.2 V
--
--
0.9
V
I
OUT
= -16 mA, V
DD
= 9.0 V
8.5
8.8
--
V
I
OUT
= -16 mA, V
DD
= 7.2 V
6.3
--
--
V
Horn Output ON Time
10-11
Alarm (see figure, time "A")
450
500
550
ms
Low Battery
8.0
10
12
ms
Horn Output OFF Time
10-11
Alarm (see figure, time "B")
450
500
550
ms
Alarm (see figure, time "C")
1350
1500
1650
ms
Low Battery
32
40
48
s
LED Output ON Current
5
V
DD
= 7.2 V, V
OUT
= 1.0 V
10
--
--
mA
LED Output ON Time
5
No Local Alarm; Not Latched
8.0
10
12
ms
LED Output OFF Time
5
No Alarm, In Standby
32
40
48
s
ELECTRICAL CHARACTERISTICS at T
A
= +25
C, V
DD
= 9.0 V, V
SS
= 0 V, C
12
= 0.1
F,
R
7
= 8.2 M
(unless otherwise noted).
Continued next page .
. .
NOTE 1:
Negative current is defined as coming out of (sourcing) the specified device pin.
NOTE 2:
Alarm (Smoke) Condition is defined as V
15
< V
13
; No Alarm (No Smoke) Condition as V
15
> V
13
.
5364
SMOKE DETECTOR
WITH
INTERCONNECT
115 Northeast Cutoff, Box 15036
Worcester, Massachusetts 01615-0036 (508) 853-5000
I/O Current
2
No Alarm, V
I/O
= V
DD
- 2.0 V
25
--
60
A
Alarm, V
I/O
= V
DD
- 2.0 V
-7.5
--
--
mA
I/O Alarm Voltage
2
External "Alarm" In
3.0
--
--
V
I/O Delay
2
"Alarm" Out
--
3.0
--
s
Supply Current
6
V
DD
= 9.0 V, No Alarm, No Loads
--
5.0
9.0
A
V
DD
= 12 V, No Alarm, No Loads
--
--
12
A
Test
Limits
Characteristic
Pin
Test Conditions
Min.
Typ.
Max.
Units
ELECTRICAL CHARACTERISTICS (continued)
CIRCUIT DESCRIPTION
The A5364CA is a low-current CMOS circuit
providing all of the required features for an
ionization-type smoke detector.
Oscillator. An internal oscillator operates
with a period of 1.67 seconds during no-
smoke conditions. Every 1.67 seconds,
internal power is applied to the entire circuit
and a check is made for smoke. Every 24
clock cycles (40 seconds), the LED is pulsed
and a check is made for low battery by
comparing V
DD
to an internal reference.
Because very-low currents are used in the
device, the oscillator capacitor at pin 12
should be a low-leakage type (PTFE, polysty-
rene, or polypropylene).
Detector Circuitry. When smoke is
detected, the resistor divider network that sets
the sensitivity (smoke trip point) is altered to
increase the sensitivity set voltage (pin 13) by
typically 130 mV with no external connec-
tions to pins 3 or 13. This provides hysteresis
and reduces false triggering. An active guard
is provided on both pins adjacent to the
detector input (pin 15). The voltage at pins
14 and 16 will be within 100 mV of the input.
This will keep surface leakage currents to a minimum and provide a
method of measuring the input voltage without loading the ionization
chamber. The active guard amplifier is not power strobed and thus
provides constant protection from surface leakage currents. The
detector input has internal diode protection against static damage.
Alarm Circuitry. If smoke is detected, the oscillator period changes
to 40 ms and the horn is enabled. The horn output is typically 0.5 s
ON, 0.5 s OFF, 0.5 s ON, 0.5 s OFF, 0.5 s ON, 1.5 s OFF (temporal
horn pattern). During the OFF time, smoke is checked and will inhibit
further alarm output if smoke is not sensed. During smoke conditions
the low battery alarm is inhibited and the LED is driven at a 1 Hz rate.
Sensitivity Adjust. The detector sensitivity to smoke is set inter-
nally by a voltage divider connected between V
DD
and V
SS
. The
sensitivity can be externally adjusted to the individual characteristics of
the ionization chamber by connecting a resistor between pin 13 and
V
DD
, or between pin 13 and V
SS
.
Low Battery. The low battery threshold is set internally by a voltage
divider connected between V
DD
and V
SS
. The threshold can be in-
creased by connecting a resistor between pin 3 and V
DD
. The threshold
can be decreased by connecting a resistor between pin 3 and V
SS
. The
battery voltage level is checked every 40 seconds during the 10 mA,
10 ms LED pulse. If an LED is not used, it should be replaced with an
equivalent resistor (typically 500
to 1000 ) such that the battery
loading remains at 10 mA.
NOTE 1:
Negative current is defined as coming out of (sourcing) the specified device pin.
NOTE 2:
Alarm (Smoke) Condition is defined as V
15
< V
13
; No Alarm (No Smoke) Condition as V
15
> V
13
.
5364
SMOKE DETECTOR
WITH
INTERCONNECT
www.allegromicro.com
19 CLOCK CYCLES
1.67 s
NO ALARM
NO LOW BATTERY
STANDBY MODE
10 ms
40 ms
24 CLOCK CYCLES
V15 > V13 (NO SMOKE)
V15 < V13 (SMOKE)
V12
OSC. CAP
INTERNAL
CLOCK
LED
SMOKE
COMPARATOR
SMOKE
CHAMBER
HORN
SAMPLE
ALARM
NO LOW BATTERY
30 CLOCK CYCLES
LOW BATTERY
WARNING
HORN
ON TIME
"A"
ALARM AND
LOW BATTERY
NO ALARM
LOW BATTERY
Dwg. WC-003-3
24 CLOCK CYCLES
LED OFF
LED
ON
12 CLOCK
CYCLES
12 CLOCK
CYCLES
36 CLOCK CYCLES
HORN
OFF TIME
"B"
13 CLOCK
CYCLES
24 CLOCK CYCLES
73 CLOCK CYCLES
I/O
SHADED AND UNSHADED AREAS
ARE DIFFERENT TIME SCALES
HORN OFF TIME
"C"
I/O. A connection is provided at pin 2 to
allow multiple smoke detectors to be
commoned. If any single unit detects smoke
(I/O is driven high), all connected units will
sound their associated horns after a nominal 3
second delay. The LED is suppressed when
an alarm is signaled from an interconnected
unit.
Testing. On power up, all internal counters
are reset. Internal test circuitry allows for
low battery check by holding pins 8 and 12
low during power up, then reducing V
DD
and
monitoring HORN
1
(pin 10). All functional
tests can be accelerated by driving pin 12
with a 2 kHz square wave. The 10 ms strobe
period must be maintained for proper opera-
tion of the comparator circuitry.
TYPICAL APPLICATION
TO
OTHER
UNITS
NOTE
1
NOTE
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
LOGIC
OSC. &
TIMING
HORN
DRIVER
V
DD
Dwg. EC-005-4
V
SS
9 V
PUSH
TO
TEST
200 k
200 k
200
8.2 M
1
F
0.1
F
1 M
330 k
0.001
F
330
NC
NC
NOTE 1: Use an external resistor to adjust sensitivity for a particular smoke
chamber.
NOTE 2: A resistor to ground or V
DD
may be added to this pin to modify low
battery voltage threshold.
TIMING DIAGRAM IN TYPICAL APPLICATION
5364
SMOKE DETECTOR
WITH
INTERCONNECT
115 Northeast Cutoff, Box 15036
Worcester, Massachusetts 01615-0036 (508) 853-5000
I/O OPERATION
INTERNAL
CLOCK
HORN
V2 IN
I/O
1.67 s
40 ms
72 CLOCK CYCLES
V2 OUT
I/O
INTERNAL
CLOCK
LOCAL ALARM MODE
NO LOW BATTERY
REMOTE ALARM MODE
NO LOW BATTERY
Dwg. WC-004-2
HORN
12 CLOCK
CYCLES
12 CLOCK
CYCLES
HORN CYCLE NOT SELF COMPLETING
AFTER REMOTE OR LOCAL ALARM CONDITION IS REMOVED
SINGLE HORN PULSE IN PROGRESS IS SELF COMPLETING
AFTER LOCAL ALARM CONDITION IS REMOVED
SHADED AND UNSHADED AREAS
ARE DIFFERENT TIME SCALES
5364
SMOKE DETECTOR
WITH
INTERCONNECT
www.allegromicro.com
Dimensions in Inches
(controlling dimensions)
Dimensions in Millimeters
(for reference only)
NOTES: 1. Lead thickness is measured at seating plane or below.
2. Lead spacing tolerance is non-cumulative.
3. Exact body and lead configuration at vendor's option within limits shown.
0.014
0.008
0.300
BSC
Dwg. MA-001-16A in
0.430
MAX
16
1
8
0.280
0.240
0.210
MAX
0.070
0.045
0.015
MIN
0.022
0.014
0.100
BSC
0.005
MIN
0.150
0.115
9
0.775
0.735
0.355
0.204
7.62
BSC
Dwg. MA-001-16A mm
10.92
MAX
16
1
8
7.11
6.10
5.33
MAX
1.77
1.15
0.39
MIN
0.558
0.356
2.54
BSC
0.13
MIN
3.81
2.93
9
19.68
18.67
5364
SMOKE DETECTOR
WITH
INTERCONNECT
115 Northeast Cutoff, Box 15036
Worcester, Massachusetts 01615-0036 (508) 853-5000
The products described here are manufactured under one or more
U.S. patents or U.S. patents pending.
Allegro MicroSystems, Inc. reserves the right to make, from time to
time, such departures from the detail specifications as may be required
to permit improvements in the performance, reliability, or
manufacturability of its products. Before placing an order, the user is
cautioned to verify that the information being relied upon is current.
Allegro products are not authorized for use as critical components
in life-support devices or systems without express written approval.
The information included herein is believed to be accurate and
reliable. However, Allegro MicroSystems, Inc. assumes no responsi-
bility for its use; nor for any infringement of patents or other rights of
third parties which may result from its use.
SAFETY & SECURITY ICs
Part
Number
Function
A3054KU/SU
Multiplexed two-wire Hall-effect sensor
A5348CA
Ionization-type smoke detector with interconnect, timer, and reverse-battery protection
A5349CA
Ionization-type smoke detector with interconnect and timer for ac line operation
A5350CA
Ionization-type smoke detector with interconnect and reverse-battery protection
A5354CA
Ionization-type smoke detector with interconnect and reverse-battery protection
A5358CA
Photoelectric-type smoke detector with interconnect and timer
A5364CA
Ionization-type smoke detector with interconnect, reverse-battery protection,
and temporal horn pattern
A5368CA
Ionization-type smoke detector with interconnect, timer, reverse-battery protection,
and temporal horn pattern