Specifications are subject to change without notice (25.06.99)
1
Photoelectrics
Amplifier, -Processor Controlled
Type S1430 UAP, 3 Inputs/3 Transistor Outputs
Product Description
Ordering Key
Type
Special function
Output type
Power supply
-Processor controlled ampli-
fier for 3 sets of photoelec-
tric sensors, type MOFTR,
MKFTR, MIFTR or MHFTR.
Utilising an 11-pin circular
plug for easy connection,
outputs freely selectable for
NPN/PNP or NO/NC. Self-
diagnostics for system test.
Protected against short-cir-
cuits, reverse wiring or cross
talk from adjacent photoelec-
trics. Multi-voltage power
supply. Sensitivity is indivi-
dually adjustable for each
set of photoelectrics.
-Processor controlled
Amplifier unit for 3 sets of photoelectrics
3 independent outputs
NPN/PNP both NO or NC selectable
Self-diagnostic functions
Alignment failure indication
Multivoltage 12 to 30 VAC/DC
Modulated and synchronized light
Adjustable sensitivity for each channel
LED indications: supply, outputs, signal quality
11-pin plug-in housing
For 115 or 230 VAC use power supplys from SS120-series
Type Selection
Plug type
Ordering no.
Supply: 12 - 30 VAC/DC
Circular, 11 pins
S 1430 UAP 912
Specifications
Supply to photoelectric switch
(cont.)
Receiver
Rx1: Pin 4
Rx2: Pin 7
Rx3: Pin 8
Shield: Pin 5 (common)
Supply voltage (open loop)
5 VDC
Short-circuit current
10 mA
Input resistance
470
Sensitivity
2 ranges,
(% of S
n
)
DIP-Switch selectable
- low sensitivity (25%)
- high sensitivity (100%)
Sensitivity adjustment
with 270:
Turn knob on CH 1, 2, 3
Note:
Maximum range indi-
cated on photoelectric
switch data sheet in high
sensitivity range only
Operation within low
sensitivity range, increa-
ses ambient light and
crosstalk immunity
Operating frequency (f)
Light/dark ratio 1:1
16 Hz
Rated operational voltage (U
B
)
pins 2 & 10
DC
10.8 to 33 VDC
AC
10.8 to 33 VAC, 45 to 65 Hz
Rated operational power
AC supply
4 VA
DC supply
3 W
Power ON delay (t
v
)
< 300 ms
Output function
NPN and PNP switching
Make and break function
DIP-Switch selectable
Output current
Continuous (I
e
)
100 mA per output
Short-time (I)
100 mA max.
Min. load current (I
m
)
0.5 mA
OFF-state current (I
r
)
Max. 100 A
Voltage drop (U
d
)
3.5 VDC
Protection, outputs
Reverse polarity, short-circuit,
transients
Supply to photoelectric switch
Emitter
Tx1: Pin 1
Tx2: Pin 9
Tx3: Pin 6
Shield: Pin 11 (common)
Supply voltage (open loop)
7 V square wave
Current
300 mA short-circuit protected
Output resistance
10
S14 30 UAP 912
2
Specifications are subject to change without notice (25.06.99)
Response time
OFF-ON (t
ON
)
20 ms
ON-OFF (t
OFF
)
20 ms
Indication
Supply ON
LED, green
Output ON
LED, yellow
Signal quality
LED, red
Environment
Overvoltage category
III (IEC 60664)
Degree of protection
IP 20 (IEC 60529, 60947-1)
Pollution degree
3 (IEC 60664/60664A,
60947-1)
Temperature
Operating
-20 to +50C (-4 to +122F)
Storage
-50 to +85C (-58 to 185F)
Weight
150 g
Approvals
CSA
CE-marking
Yes
S 1430 UAP
Specifications (cont.)
Truth Table
Object present
Yes
No
No
Yes
No
No
Dirt on lenses,
misaligned or
--
No
Yes
1)
--
No
Yes
1)
sensitivity too low
Output LED yellow OFF
ON
ON
OFF
ON
ON
Level LED red
OFF
OFF
OFF
OFF
Output NPN/PNP OFF
ON
ON
ON
OFF
OFF
Make switching
Break switching
ON
or
flashing
1)
Under normal operating conditions, the red level indication
LED has to be OFF. The level indication LED will turn on
shortly each time an object enters or exits the sensing
zone, even if the photoelectric switch is correctly installed
and adjusted.
Operation Diagram
Power supply
Object present
Signal quality
!
Break switching
ON
or
flashing
Procedure for Test Functions (Dip-Switch Selection)
Transmitter test
(switch 5 in the up position)
When switch 5 is placed in
the up position all yellow and
red LED's on the front of the
unit will flash simultaneously.
Once the test is completed
(approx. 3 scans) and a
wiring fault is detected, such
as reverse polarity or short-
circuit, the transmitter that
has the fault condition will
be indicated by the red LED
being continuously ON. If a
fault condition is not existing
then only the yellow LED will
be ON. If a fault exists, cor-
rect the fault condition and
then repeat the test, this will
ensure proper wiring has
been done. Always
reset
switch 5 for normal opera-
tion of system when testing
completed.
Receiver test
(switch 6 in the up position)
When switch 6 is placed in
the up position all yellow and
red LED's on the front of the
unit will flash simultaneously.
Once the test is completed
(approx.
3 scans) and a
wiring fault is detected, such
as reverse polarity or short-
circuit, the receiver that has
the fault condition will be
indicated by the red LED
being continuously ON. If a
fault condition is not existing
then only the yellow LED will
be ON. If a fault exists, cor-
rect the fault condition and
then repeat the test, this will
ensure proper wiring has
been done. Always
reset
switch 6 for normal opera-
tion of system when testing
completed.
Function test
(switch 5 and 6 in the up position)
When switch 5 and 6 are
both placed in the up positi-
on (simultaneously) the yel-
low and red LED's on the
front of the housing will
begin to flash simultane-
ously and then the LED's
LED Indication
Yellow LED ON
Red LED OFF
Yellow LED ON
Red LED ON
Yellow LED OFF
Red LED ON
Make switching
System Test OK
}
Tx's and Rx's mismatched,
e.g. Rx3 seeing Tx1
}
}
Alignment error or beam
obstructed by object
!
!
!
Signal strength
Time
will cycle from channel 1 to
channel 2 and then to chan-
nel 3. Once the complete
system scan is done the
indication of the system
condition will be displayed
(see below). System test will
continue until switch 5 and 6
are reset.
Specifications are subject to change without notice (25.06.99)
3
S 1430 UAP
Dimensions
Wiring Diagrams
Accessories
- 11 pole circular socket
S111, S111A, S411, ZPD11
- Socket cover for S111
BB1
- Socket cover for S411
BB4
- Holding down spring
HF
- Mounting rack
SM13
- Front panel mounting bezel
FRS2
- Connection cable (2 plugs)
2 x 6/6 modular plugs
2.0 m, 6 wires two plugs
- Power supply for 115/230 VAC SS120-series
- DIN-rail interface
6IODC
Delivery Contents
Output connection cable
1 m, 6 wires one plug
Output connection cable
0.2 m, 6 wires two plugs
Amplifier
S 1430 UAP 912
DIN-rail interface
6IODC
Screw driver
Packaging:
Cardboard box
A B C D
F
+
-
Output
Wire colour coding
A: + (10-40 VDC)
white
B: Output 1 (max. 100 mA)
black
C: Output 2 (max. 100 mA)
red
D: Output 3 (max. 100 mA)
green
E: For handheld tester
yellow
F: - DC
blue
ON sockets
1: Transmitter 1
2: Supply (+ VDC)
3: No connection
4: Receiver 1
5: GND (Receivers)
6: Transmitter 3
7: Receiver 2
8: Receiver 3
9: Transmitter 2
10: Supply (- VDC)
11: GND (Transmitters)
Power Supply
8
9
10
11
7
6
5
4
3
1
2
Rx 1
Rx 2
Rx 1
Rx 3
Tx 1
Tx 2
Rx 1
Tx 3
35
80
84
75
4
5
DIP-Switch (located behind cover):
1: PNP/NPN CH 1 output
2: PNP/NPN CH 2 output
3: PNP/NPN CH 3 output
4: Low sensitivity (25%) / high sensitivity (100%)
5: Test button, transmitters are transmitting, no short, wired correctly
6: Test button, receivers are receiving, no short, wired correctly
5+6 together: System test (transmitter and receiver)
1 2 3 4 5 6
SW
PNP make/NPN break
NPN make/PNP break
sw 1, 2, 3:
Transmitter test
Normal operation
sw 5:
Range 25%
Range 100%, normal operation
sw 4:
Receiver test
Normal operation
sw 6:
System test
sw 5+6:
Normal operation
B C D
F
+
-
10-40
VDC
10-40
VDC
PNP
NPN
6IODC
DIN-rail interface
(DIN EN 50 035, EN 50 022)
output from plug to screw
terminals
Interface