ChipFind - документация

Электронный компонент: CVTDINAV6DC02X

Скачать:  PDF   ZIP
Specifications are subject to change without notice
1
For DC current/voltage measurement
Field adjustment capability
For DIN-rail mounting
Degree of protection: IP 50
Product Description
Model
Range code
Measurement
Power supply
Setpoints
Rated output
Calibration
Ordering Key
CVT-DIN AV6DD01X
Compact transducer for DC
current/voltage measurements
with field adjustment capabil-
ity. The housing is for DIN-rail
mounting and ensures a
degree of protection of IP 50.
Energy Management
Compact Transducer for DC Measurements
Type CVT-DIN AV2/AV6
Type Selection
Power supply
A:
24 VAC, -15% +10%,
50/60 Hz
1)
B:
48 VAC, -15% +10%,
50/60 Hz
1)
C:
115 VAC, -15% +10%,
50/60 Hz
1)
D:
230 VAC, -15% +10%,
50/60 Hz (standard)
1)
On request
Range code
AV2:
10 VDC - 60 mVDC
(max. 12 VDC - 72 mV)
AV6:
200 VDC - 1 ADC
(max. 240 VDC -
1.2 ADC)
Rated output
1:
Analogue output
0 to 20 mA (standard)
2:
Analogue output
4 to 20 mADC
1)
3:
Analogue output
0 to 10 VDC
1)
4:
Analogue output
0 to 1 VDC
1)
Calibration
X:
Standard calibration
Y:
Special calibration,
use "Y" followed by
requested value
AC supply
230 VAC, -15% +10%,
50/60 Hz (standard)
24 VAC, 48 VAC, 115 VAC,
-15% +10%, 50/60 Hz
(on request)
Power consumption
5 VA
Supply Specifications
Range/load
0 to 20 mA
Load:
500
4 to 20 mA
Load:
500
0 to 10 V
Load:
10 k
0 to 1 V
Load:
10 k
Adjustment
Easy field adjustment from 50
to 130% of the I/U inputs
which can be modified
without any calibrator being
requested
Response time
300 ms
Temperature drift
200 ppm/C
Output Specifications
Input Specifications
Accuracy
(@ 25C 5C, R.H.
60%)
0.5% f.s.,
(0.1 ln/Un to 1 In/Un)
Additional errors
The given accuracy already
includes: power supply, out-
put load influences
Humidity
< 0.3%, 60% to 90% R.H.
Magnetic field
< 0.5%, @400 A/m
Ripple
1% according to IEC
60688-1 and EN 60688-1
Rated input
AV2
60 mV (imp. 10 k
)/
10 VDC (imp. 1.5 M
)
AV6
1 A (1 V internal shunt/imp.1
)
200 VDC (imp. 1.6 M
)
Overload protection
Cont.:
Current
1.2 x rated input
Voltage
1.2 x rated input
For 1 s: Current
20 x rated input
Voltage
2 x rated input
2
Specifications are subject to change without notice
Warm-up time
15 minutes
Operating temperature
0 to 50C (32 to 122F)
(R.H. < 90% non-condensing)
Storage temperature
-10 to 60C (14 to 140F)
(R.H. < 90% non-condensing)
Insulation reference voltage
300 V
rms
to ground
Insulation
2000 V
rms
between output
and measuring input,
output and supply input.
4000 V
rms
between
input/output and ground
Dielectric strength
4000 V
rms
for 1 minute
Noise rejection
CMRR
80 dB, 48 to 62 Hz
CVT-DIN AV2/AV6
Dimensions
General Specifications
EMC
EN 50081-1, EN 50082-1
Safety standards
Safety requirements:
IEC 601010-1, EN 61010-1
Product requirements:
IEC 60688-1, EN 60688-1
Connector
Screw-type,
max. 2.5 mm
2
wire
Housing
Dimensions
4-DIN modules,
58.5 x 89 x 71.5 mm
Material
ABS,
self-extinguishing: UL 94 V-0
Degree of protection
IP 50
Weight
300 g approx.
(packing included)
Approval
CE
Connections
230VAC
115VAC
48VAC
24VAC
~ ~
ADJUSTMENT
INPUT
: current
(1) COM.
INPUT
: voltage
OUTPUT
: 20mA
..
OUTPUT
: 10V/
1
V
.....
}
+
}
+
1 3
4 5 6 8 10 11 12
CVT-DIN
Note
Measurement inputs
Current measurement: between
current input and common (1)
terminals;
Voltage measurement: between
voltage input and common (1)
terminals.