ChipFind - документация

Электронный компонент: D90910210024

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (28.09.99)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Supply
Ordering no.
24 VAC
D 9091 0210 024
115 VAC
D 9091 0210 115
230 VAC
D 9091 0210 230
No code module required
5 operation modes
Public line remote
Public line central
Private line master
Private line slave
RS 232 interface
Baud rate: 300, 1200, 2400, 4800, 9600 Baud
Protocols: Hayes AT and CCITT V.25 bis
LED-indications for supply, call initiate,
external Dupline
OK and modem connection OK
AC power supply
Product Description
Ordering Key
Dupline
interface for com-
monly available telephone
modems (autodial or leased
line). Hayes AT or CCITT
V.25 protocol with selectable
data format. Event, time or
manually controlled connec-
tion between autonomously
operated remote Dupline
installations and a central
location.
Type Selection
Input/Output Specifications
Communication port
RS 232
25 pole male SUB-D
Pin allocation
TxD
Pin 2
RxD
Pin 3
GND
Pin 7
DCD
Pin 8
DTR
Pin 20
Dielectric voltage
Com. port - Dupline
500 VAC (rms)
Dupline Tx inhibit input
Contact or NPN transistor
Open loop voltage
5 VDC
Short-circuit current
50 A
Contact resistance
10
Cable length
3 m
Dielectric voltage
Input - Dupline
500 VAC (rms)
Input - Com. port
None
Output
1 SPDT relay
Function
Alarm
Contact ratings (AgCdO)
(micro gap)
AC voltage
AC1 5A/48 VAC (240 VA)
DC voltage
DC1 0.7 A/48 VDC (33W)
Load current
100 mA
Mechanical life
30 x 10
6
operations
Elect. life (at max. load) AC 1
2.5 x 10
5
operations
Operating frequency
7200 operations/h
Dielectric voltage
Output - Electronics
4 kVAC (rms)
Supply Specifications
Power supply
Installation cat. III (IEC 60664)
Rated operational
voltage
024
024 VAC 15%
115
115 VAC 15%
230
230 VAC 15%
Frequency
45 to 65 Hz
Voltage interruption
40 ms
Power consumption
Typ. 6 VA
Rated operational withstand
voltage
230
4 kV
024
800 V
Dielectric voltage
Supply - Dupline
4 kVAC (rms)
Supply - Com. port
4 kVAC (rms)
Supply - Input
4 kVAC (rms)
Supply - Output
4 kVAC (rms)
Type: Dupline
Type no.
Supply
Modem Interface
Type D 9091 0210
D 9091 0210 024
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (28.09.99)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
D 9091 0210
General Specifications
Additional Information
Power ON delay
2 s
Indication for
Supply ON (PWR)
LED, green
Call initiate (CI)
LED, green
External Dupline OK (EXD)
LED, yellow
Modem connection OK (CON) LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Humidity (non-condensing)
0 to 80%
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6-55 Hz)
Material
Light grey polystyrol
Weight
600 g
Scope of supply
1 x Modem Interface
D 9091 210...
1 x Power cable, 2 m
PWR 230
1 x User manual
MAN D90xx ENG
Dimensions (mm)
Mode of Operation
D 9091 0210 is a Dupline
modem interface for easy
control of Dupline
networks
through the telephone lines.
Configuration of the interface
is done by means of the con-
figurator type D 9080 or by
means of a personal compu-
ter running the terminal emu-
lator software D 9091 SW01.
The modem interface features
3 main functions for which it
can be configured: public line
mode, private line mode and
RS 232 interface.
For status indication 4 LEDs
are used:
Call initiate (CI): to identify
the dialling modem.
External Dupline
OK (EXD):
indicating that the connect-
ed Dupline
is working pro-
perly.
Modem connection OK
(CON): showing that con-
nection is established be-
tween the 2 modems.
Power supply ON (PWR): to
indicate that power is appli-
ed to the unit.
The Run/program push but-
ton (5) (accessible with a pen
through a hole on the right
side of the housing) is used to
switch the interface to confi-
guration or Run-mode. When
this push button is held down
for 5 s the interface changes
mode. Configuration mode is
indicated by flashing of the
three LEDs - CI, EXD and
CON.
The voltage selector switch (6)
(only on D 9091 0210 230) is
used to adapt the unit to the
supply voltage.
Note: The D 9091 0210 230 is
factory set for 230 VAC.
To change the supply voltage
proceed as follows:
1. disconnect the power
2. remove the 4 housing
screws at the bottom of the
unit.
3. lift off the housing top cover
4. move switch (6) into po-
sition for selected voltage
5. reassemble the unit
6. change supply voltage label
on the rear of the housing
7. connect power cable to
power connector (7).
The relay output (8) deener-
gizes whenever one of the fol-
lowing problems is detected:
Transmission breakdown
Continuous reception of
corrupted data
External Dupline
off-line
Reception of an alarm call
The Dupline
transmission
inhibit input (10) is used to
reset the data buffer and igno-
re the data received from the
counterpart station. For more
details, refer to the description
in the manual.
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (28.09.99)
3
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
D 9091 0210
Power Supply
S: signal wire
Rear view
Top view
Transmission inhibit
Transm.
Inh.
To Modem, PC
or configurator
Wiring Diagram
Functional Description
Accessories
Interface configurator
D 9080
Configuration software for
PC: 3
1
/
2
'' disc
D 9091 SW013
5
1
/
4
'' disc
D 9091 SW015
Configurator cable
RS 232-25M/25F
For further information refer to "Accessories".
1)
Supply ON-LED (PWR)
2)
Call initiate LED (CI)
3)
External Dupline
OK-LED (EXD)
4)
Modem connection OK-LED (CON)
5)
Run/program push button
6)
Supply voltage selector switch (D 9091 0210 230 only)
7)
Power connector
8)
Relay output terminals
9)
Dupline
connection terminals (S = signal, - = common)
10) Dupline
Transmission inhibit input terminals
11) Communication port to modem or configurator (D9080)