ChipFind - документация

Электронный компонент: DAA01CM24

Скачать:  PDF   ZIP
Specifications are subject to change without notice (24.10.05)
1
Product Description
Ordering Key
Delay on Operate
Multi-voltage delay on oper-
ate timer with 7 selectable
time ranges within 0.1 s and
100 h. For mounting on DIN-
rail (DAA01) or plug-in
(PAA01).
Time range 0.1 s to 100 h
Knob selection of time range
Knob adjustable time setting
Automatic start
Repeatability:
0.2%
Output: 8 A SPDT or 2 x 8 A SPDT relays
For mounting on DIN-rail in accordance with DIN/EN
50 022 or Plug-in
22.5 Euronorm or 36 mm plug-in module housing
Combined AC and DC power supply
LED indication for relay status and power supply ON
Output
1 or 2 x SPDT relays
Rated insulation voltage
250 VAC (rms)
Contact Ratings (AgSnO
2
)
Resistive loads
AC 1
8 A @ 250 VAC
DC 12
5 A @ 24 VDC
Small inductive loads AC 15
2.5 A @ 250 VAC
DC 13
2.5 A @ 24 VDC
Mechanical life
30 x 10
6
operations
Electrical life
10
5
operations
(at 8 A, 250 V, cos
= 1)
Operating frequency
< 7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand
voltage
4 kV (1.2/50 s)
Output Specifications
Type Selection
DAA 01 C M24
Housing
Function
Type
Item number
Output
Power supply
Mounting
Output
Housing
Supply: 24 VDC and 24 to 240 VAC
Supply: 24 to 240 VAC/DC
DIN-rail
1 x SPDT
D-Housing
DAA01CM24
2 x SPDT
DAA01DM24
Plug-in
1 x SPDT
P-Housing
PAA01CM24
2 x SPDT
PAA01DM24
Time Specifications
Time ranges
Knob selectable
0.1 to 1 s
1 to
10
s
6 to
60
s
60 to 600
s
0.1 to 1 h
1 to
10
h
10 to 100
h
Setting accuracy
5%
Repeatability
0.2%
Time variation
Within rated power supply
0.05%/V
Within ambient temperature
0.2%/C
Reset
Power supply interruption
200 ms
Type DAA01, PAA01
Timers
DAA01
PAA01
Power supply
Overvoltage cat. III
Rated operational voltage
(IEC 60664, IEC 60038)
through terminals:
(DAA01C)
A1, A2 or
24 VDC 15% and
(PAA01C)
2, 10
24 to 240 VAC + 10% -15%,
45 to 65 Hz
(DAA01D)
A1, A2 or
24 to 240 VAC/DC
(PAA01D)
2, 10
+ 10% - 15%,
45 to 65 Hz
Supply Specifications
Voltage interruption
10 ms
Rated operational power
AC supply
4 VA
DC supply
1.5 W
2
Specifications are subject to change without notice (24.10.05)
L(+)
N(-)
m
m
A1
15
25
16
26
18
28
A2
DAA01C...
DAA01D...
DAA01D...
DAA01, PAA01
Power ON delay
100 ms
Reaction time
Instantaneous contact
< 20 ms from power ON
Indication for
Power supply ON
LED, green
Output relays ON
LED, yellow
(flashing when timing)
Environment
(EN 60529)
Degree of protection
IP 20
Pollution degree
3 (DAA01), 2 (PAA01)
(IEC 60664)
Operating temperature
-20 to +60C, R.H. < 95%
Storage temperature
-30 to +80C, R.H. < 95%
Housing dimensions
DIN-rail version
22.5 x 80 x 99.5 mm
Plug-in version
36 x 80 x 94 mm
Weight
Approx. 130 g
Screw terminals (DAA01)
Tightening torque
Max. 0.5 Nm according to
IEC EN 60947
Approvals
UL, CSA
RINA (DAA01 only)
CE marking
Yes
EMC
Electromagnetic Compatibillity
Immunity
According to EN 61000-6-2
Emission
According to EN 61000-6-3
Timer Specifications
According to EN 61812-1
General Specifications
Operating Diagram
Power supply
Relay 1
Relay 2
(Delayed)
Relay 2
(Istantaneous)
T
T
LED
Wiring Diagrams
Centre knob:
Lower knob:
Time setting on relative
Setting of time range
scale: 1 to 10 with respect
to the chosen range
Time Setting
Mode of Operation
The yellow LED, flashing
when timing, is ON as soon
as the relay turns ON.
The second relay can operate
as instantaneous or delayed
changeover contact. The
selection is made by a DIP-
switch placed under the plas-
tic door on the device's front.
The set delay period begins
as soon as the power supply
is connected. At the end of
the set delay the relay oper-
ates and does not release
until the power supply is
interrupted for at least 200
ms. If the power supply is
interrupted for at least 200
ms before the relay operates
the time is set to zero and the
circuit is ready for a new time
period.
m
L(+)
N(-)
m
2
1
11
4
8
3
9
PAA01C...
PAA01D...
PAA01D...
10
DAA01
PAA01
ON
OFF
ON
OFF
ON
OFF
DAA01C...
DAA01D...
DAA01D...
PAA01C...
PAA01D...
PAA01D...
Specifications are subject to change without notice (24.10.05)
3
DAA01, PAA01
22.5
80
83.5
99.5
63
28.5
Dimensions
36
80
94
28.5
63
90
DIN-rail
Plug-in