Specifications are subject to change without notice
1
Shunts for DC current
In accordance with DIN-Standard
Product Description
Model
Range code
Voltage drop
Ordering Key
Shunts for DC current in ac-
cordance with DIN-standard.
Ranges from 1 A to 10000 A.
Accessories
Shunts for DC Currents
Type DER
Type Selection
Range code
Refer to Range and Dimen-
sions Table
Voltage drop
60 mV:
Standard
others:
Special feature
Input Specifications
Accuracy
0.5%
Voltage drop
60 mV (standard)
150 mV or others on request
Maximum overload
1.2 In, continuous overload
10 In x 5 s., up to 250 A
5 In x 5 s., 250 to 2,000 A
2 In x 5 s., 2,000 to 10,000 A
Construction and dimensions In accordance with
DIN 43703 standard
Operating temperature
-25 to + 40C (-13F to + 104F)
Insulated base
Only for models up to 25 A
Special features
Connection cable of 2,5 mm
2
,
length to be specified
Voltage drop of 150 mV or
others
General Specifications
DER 100A 60mV
+
Wiring Diagram
Instrument
Power supply
Load
+
-
+
-