ChipFind - документация

Электронный компонент: DI3DINAV6D10XX

Скачать:  PDF   ZIP
Specifications are subject to change without notice
1
3-dgt P-based indicator for DC currents
or voltages
Selectable input range
DIN-rail mounting
Degree of protection (front): IP 40
Product Description
Model
Range code
Measurement
Power supply
Setpoints
Options
Ordering Key
DI3-DINAV6DD0XX
3-dgt P-based meter with
double input for DC currents
or voltages. With 18 select-
able input ranges. The hous-
ing is for DIN-rail mounting
and ensures a degree of pro-
tection (front) of IP 40.
Panel Meters and Controllers
DC Ammeter and Voltmeter
Type DI3-DIN AV6
Type Selection
Power supply
A:
24 VAC, -15% +10%,
50/60 Hz
1)
B:
48 VAC, -15% +10%,
50/60 Hz
1)
C:
115 VAC, -15% +10%,
50/60 Hz
1)
D:
230 VAC, -15% +10%,
50/60 Hz (standard)
1)
On request
AC supply
230 VAC, -15% +10%,
50/60 Hz (standard)
24 VAC, 48 VAC, 115 VAC,
-15% +10%, 50/60 Hz
(on request)
Power consumption
3.2 VA
Supply Specifications
Input Specifications
Rated input
1 A/60 mV/100 V/500 VDC
Overload protection
Cont.
Current:
1.2 x rated input
Voltage:
1.2 x rated input
For 1 s Current:
5 x rated input
Voltage:
2 x rated input
Accuracy
(@ 25C 5C, R.H.
60%)
0.5% f.s., 1 dgt
Temperature drift
350 ppm/C
Display
7-segment LED, h 14.2 mm,
3 digits
Sampling rate
1 time/s
Indication
Max.
999
Min.
-99
Over range
EEE
Under range
-EE
Input range selection
DIP-switch selectable
Decimal point position
DIP-switch selectable
Operating temperature
0 to 50C (32 to 122F)
(R.H. < 90% non-condensing)
Storage temperature
-10 to 60C (14 to 140F)
(R.H. < 90% non-condensing)
Insulation reference voltage
300 V
rms
to ground
Dielectric strength
4000 V
rms
for 1 minute
Noise rejection
NMRR
40 dB, 40 to 60 Hz
CMRR
100 dB, 40 to 60 Hz
EMC
IEC 60801-2, IEC 60801-3,
IEC 60801-4 (level 2),
EN 50 081-1, EN 50 082-1
Safety standards
EN 61 010-1, IEC 61010-1,
VDE 0411
Connector
Screw-type
Housing
Dimensions
89 x 53,5 x 58.5 mm
(3-DIN modules)
Material
ABS, self-extinguish.: UL 94 V-0
Degree of protection
Front: IP 40
Weight
Approx 200 g
Approvals
CE, CSA
General Specifications
2
Specifications are subject to change without notice
DI3-DIN AV6
46
54.5
49.5
58.5
45
53.5
89
Dimensions (mm)
Wiring Diagram
V
A
Front Panel Description
1. Display
3-dgt (maximum read-out 999).
Alphanumeric indication by means of 7-segment display
for:
- Displaying of the measured value, over-range.
1
Range Table
Measure-
Connection
Dec. point
Input impedance/
Resolution
Range
ment
position
volt. drop
code
100 V
Direct
99.9
1 M
0.1 V
AV6
500 V
Direct
999
1 M
1 V
AV6
1 A
Direct
999
1 V
1 mA
AV6
1.5 A
60 mV/1.5 A shunt
9.99
13 k
10 mA
AV6
2.5 A
60 mV/2.5 A shunt
9.99
13 k
10 mA
AV6
4 A
60 mV/4 A shunt
9.99
13 k
10 mA
AV6
6 A
60 mV/6 A shunt
9.99
13 k
10 mA
AV6
10 A
60 mV/10 A shunt
9.99
13 k
10 mA
AV6
15 A
60 mV/15 A shunt
99.9
13 k
100 mA
AV6
25 A
60 mV/25 A shunt
99.9
13 k
100 mA
AV6
40 A
60 mV/40 A shunt
99.9
13 k
100 mA
AV6
60 A
60 mV/60 A shunt
99.9
13 k
100 mA
AV6
100 A
60 mV/100 A shunt
99.9
13 k
100 mA
AV6
150 A
60 mV/150 A shunt
999
13 k
1A
AV6
250 A
60 mV/250 A shunt
999
13 k
1A
AV6
400 A
60 mV/400 A shunt
999
13 k
1A
AV6
600 A
60 mV/600 A shunt
999
13 k
1A
AV6
1000 A
60 mV/1000 A shunt
999
13 k
1A
AV6
+
-
1
2
3
4
5
6
7
8
IN
IN
A
IN
V/Hz
9
IN+
60mV
Power supply
NC
NC
Voltage measurements - direct
+
-
1
2
3
4
5
6
7
8
IN
IN
A
IN
V/Hz
9
IN+
60mV
Power supply
NC
NC
Current measurements - direct
+
-
1
2
3
4
5
6
7
8
IN
IN
A
IN
V/Hz
9
IN+
60mV
Power supply
NC
NC
Current measurements - shunt