ChipFind - документация

Электронный компонент: DMB71DM24

Скачать:  PDF   ZIP
Specifications are subject to change without notice (16.12.05)
1
Product Description
Ordering Key
Multifunction
Multi-voltage timer with 7
knob-selectable functions
and 7 knob-selectable time
ranges within 0.1s and 100h.
For mounting on DIN-rail.
Housing 17.5 mm wide for
SPDT version and 35.5 mm
for DPDT version, suitable
both for back and front panel
mounting.
Wide power supply range:
24 VDC and 24 to 240 VAC
or 12 to 240 VAC/DC.
Selectable time range 0.1 s to 100 h
7 knob selectable functions:
Op
-
delay on operate
In
-
interval
Io
-
interval on trigger open
Id
-
double interval
Dr
-
delay on release
R
-
symmetrical recycler ON first
Rb
-
symmetrical recycler OFF first
Automatic or manual start
Repeatability:
0.2%
Output: 5 A SPDT or 5 A DPDT relays
For mounting on DIN-rail in accordance with DIN/EN 50 022
17.5 mm (DMB51C) or 35.5 mm (DMB71D) DIN-rail
housing (DIN 43880)
Combined AC and DC power supply
LED indication for relay status and power supply ON
Output
SPDT or DPDT relay
Rated insulation voltage
250 VAC (rms)
Contact Ratings (AgSnO
2
)
DMB51 (SPDT):
Resistive loads
AC 1
5 A @ 250 VAC
DC 12
5 A @ 24 VDC
Small inductive loads AC 15
2.5 A @ 250 VAC
DC 13
2.5 A @ 24 VDC
DMB71 (DPDT)
Resistive loads
AC 1
5 A @ 250 VAC
Small inductive loads AC 15
3 A @ 250 VAC
DC 13
3 A @ 24 VDC
Mechanical life
30 x 10
6
operations
Electrical life
10
5
operations
(at 5 A, 250 V, cos
= 1)
Operating frequency
< 7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand
voltage
2.5 kV (1.2/50 s)
Output Specifications
Type Selection
DMB 51 C M24
Housing
Function
Type
Item number
Output
Power supply
Time Specifications
Time ranges
Knob selectable
0.1 to 1 s
1
to 10 s
6
to 60 s
60 to 600 s
0.1 to 1 h
1
to 10 h
10 to 100
h
Setting accuracy
5%
Repeatability
0.2%
Time variation
Within rated power supply
0.05%/V
Within ambient temperature
0.2%/C
Reset
Manual reset of time and/or
Close the trigger contact
relay
between pins A1 and Y1
Pulse duration
100 ms
Power supply interruption
200 ms
Automatic start
Connect pins A1 and Y1
Types DMB51, DMB71
Timers
Mounting
Output
Housing
Supply:
Supply:
12 to 240 VAC/DC
24 VDC and 24 to 240 VAC
DIN-rail
SPDT
Mini-D
DMB 51 C W24
DMB 51 C M24
DIN-rail
DPDT
Mini-D
DMB 71 D W24
DMB 71 D M24
DMB51
DMB71



2
Specifications are subject to change without notice (16.12.05)
DMB51, DMB71
Power ON delay
100 ms
Indication for
Power supply ON
LED, green
Output relays ON
LED, yellow
(flashing when timing)
Environment
(EN 60529)
Degree of protection
IP 20
Pollution degree
2 (IEC 60664)
Operating temperature
-20 to +60C, R.H. < 95%
Storage temperature
-30 to +80C, R.H. < 95%
Housing dimensions
DMB51C
17.5 x 81 x 67.2 mm
DMB71D
35.5 x 81 x 67.2 mm
Weight
75 g
Screw terminals
Tightening torque
Max. 0.5 Nm according to
IEC EN 60947
Approvals
UL, CSA
RINA (DMB 51 only)
CE Marking
Yes
EMC
Electromagnetic Compatibillity
Immunity
According to EN 61000-6-2
Emissions
According to EN 61000-6-3
General Specifications
Power supply
Overvoltage cat. II
Rated operational voltage
(IEC 60664, IEC 60038)
through terminals:
(DMB51C)
A1, A2 M24:
24 VDC 15% and
24 to 240 VAC + 10% -15%,
45 to 65 Hz
W24:
12 to 240 VDC + 10% -15%
and
12 to 240 VAC
+ 10% -15%, 45 to 65 Hz
(DMB71D)
A1, A2 M24:
24 VDC 15%
24 to 240 VAC + 10% -15%,
45 to 65 Hz
W24
12 to 240 VDC + 10% -15%
and
12 to 240 VAC +10% -15%,
45 to 65 Hz
Voltage interruption
10 ms
Rated operational power
(DMB51C)
AC supply:
4 VA
DC supply:
1.5 W
(DMB71D)
AC supply
5.5 VA
DC supply
2 W
Supply Specifications
Upper knob:
Setting of function:
Op - delay on operate
In - interval
Io - interval on trigger open
Id - double interval
Dr - delay on release
R - symmetrical recycler
(ON first)
Rb - symmetrical recycler
(OFF first)
Centre knob:
Time setting on relative scale:
1 to 10 with respect to the
chosen range.
Lower knob:
Setting of time range
Time Setting
Mode of Operation
Function Op
Delay on operate
The time period begins as
soon as the trigger contact
is closed.
At the end of the set delay
time the relay operates and
does not release until the
trigger contact is closed
again or the power supply is
disconnected. If the trigger
contact is closed before the
end of the delay time, the
device resets and a new
time period starts.
Function In
Interval
The relay operates and the
time period begins as soon
as the trigger contact is
closed. The relay releases at
the end of this period or
when the power supply is
disconnected. The relay
operates again when the trig-
ger contact is closed again. If
the trigger contact is closed
before the end of the delay
time, the device resets and a
new time period starts.
Function Io
Interval on trigger open
The relay operates and the
time period begins as soon
as the trigger contact is
opened. At the end of the
set delay or when the power
supply is disconnected the
relay releases. The relay
operates again when the
trigger contact is opened
again. If the trigger contact
is opened before the end of
the delay time the relay
keeps ON and a new time
period begins.
Function Id
Double interval
The relay operates and the
time period begins as soon
as the trigger contact is
closed. The relay releases at
the end of this period or
when the power supply is
disconnected. When the
trigger contact is opened
the relay operates again for
the set delay period. If the
trigger contact is opened
before the end of the first
time period the second one
begins; if the trigger contact
is closed before the end of
the second time period the
device resets and the first
time period begins again.
Function Dr
Delay on release
The relay operates as soon
as the trigger contact is
closed. The time period
begins when the trigger con-
tact is opened. The relay
releases at the end of the
set delay time or when the
power supply is disconnect-
ed. The relay operates again
when the input contact is
closed again. If it is opened
before the end of the delay
time the relay keeps ON, a
new time period begins as
soon as the contact is
closed again.
Specifications are subject to change without notice (16.12.05)
3
DMB51, DMB71
Mode of Operation (cont.)
Function R
Symmetrical recycler, ON-
time period first
The relay operates and the
time period begins as soon
as the input contact is
closed. After the set delay
period the relay releases for
the same time period. This
sequence continues with
equal ON- and OFF-time
periods until the power sup-
ply is interrupted.
Function Rb
Symmetrical recycler,
OFF-time period first
The time period begins as
soon as the input contact is
closed. The relay is OFF
during the set delay period,
after this time it operates for
the same time period. This
sequence continues with
equal OFF- and ON-time
periods until the power sup-
ply is interrupted.
Additional Load
It's possible to wire an addi-
tional load (i.e. a relay)
between pins Y1 and A2,
driven by the trigger contact
without damaging the
device.
Yellow LED working
mode
Timing: Slow blinking
Relay ON: See operation
diagrams
Incorrect knobs position:
Fast blinking
Operating Diagrams
Power supply
Relay ON
Trigger input
T
T
LED
Function Op - Delay on operate - Manual start
Power supply
Relay ON
T
T
LED
Function Op - Delay on operate - Automatic start
Power supply
Relay ON
Trigger input
T
T
LED
Function In - Interval - Manual start
Power supply
Relay ON
T
LED
Function In - Interval - Automatic start
T
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Wiring Diagram
DMB51CM...
DMB51CW...
DMB71DM...
S
Y1
L(+)
18
26
28
16
A1
A2
15
25
N(-)
DMB71DW...
DMB71DM...
DMB71DW...
4
Specifications are subject to change without notice (16.12.05)
DMB51, DMB71
Function Dr - Delay on release
Power supply
Relay ON
Trigger input
T
LED
Power supply
Relay ON
T
T
T
T
LED
Trigger input
Function Rb - Symmetrical recycler (OFF first)
Power supply
Relay ON
T
T
T
T
LED
Trigger input
ON
OFF
ON
OFF
ON
OFF
Function R - Symmetrical recycler (ON first)
67.2
18.7
4
5
17.5
8
1
2
Dimensions
DMB51
DMB71
67.2
67.2
18.7
18.7
4
5
4
5
35.5
35.5
8
1
8
1
2
Operating Diagrams (cont.)
Function Io - Interval on trigger open
Power supply
Relay ON
Trigger input
T
T
LED
Function Id - Double interval
Power supply
Relay ON
Trigger input
T
T
LED
ON
OFF
ON
OFF