Specifications are subject to change without notice (18.07.06)
1
Monitoring Relays
Product Description
Ordering Key
Housing
Function
Type
Item number
Output
Power supply
TRMS 3-phase phase sequence, phase loss and
asymmetry monitoring relays
Detect when all 3 phases are present and have the
correct sequence
Detect if asymmetry level is below the set value
Measure on own power supply
Selection of measuring range by DIP-switches
Adjustable asymmetry on relative scale
Adjustable delay function (0.1 to 30 s)
Output: 8 A relay SPDT N.E.
For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPB02) or plug-in module (PPB02)
22.5 mm Euronorm housing (DPB02)
or 36 mm plug-in module (PPB02)
LED indication for relay, alarm and power supply ON
Type Selection
Mounting
Output
Supply: 208 to 240 VAC
Supply: 380 to 415 VAC
Supply: 380 to 480 VAC
DIN-rail
SPDT
DPB 02 C M23
DPB 02 C M48
Plug-in
SPDT
PPB 02 C M23
PPB 02 C M48
Input
L1, L2, L3, N
DPB02: Terminals L1, L2, L3, N
PPB02: Terminals 5, 6, 7, 11
Measure on own supply
Note: Connect the neutral only
if it is intrinsically at the star
centre
Measuring ranges
208 to 240 VAC
177 to 275
VAC
380 to 480 VAC (DPB02CM48) 323 to 550
VAC
380 to 415 VAC (PPB02CM48) 323 to 475
VAC
Ranges
Asymmetry
2 to 22%
of the nominal voltage
True RMS 3-Phase, Phase Sequence/Loss - Asymmetry
Types DPB02, PPB02
Input Specifications
Output
SPDT relay
Rated insulation voltage
250 VAC
Contact ratings (AgSnO
2
)
Resistive loads
AC 1
8 A @ 250 VAC
DC 12
5 A @ 24 VDC
Small inductive loads AC 15
2.5 A @ 250 VAC
DC 13
2.5 A @ 24 VDC
Mechanical life
30 x 10
6
operations
Electrical life
10
5
operations
(at 8 A, 250 V, cos
= 1)
Operating frequency
7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 s)
Output Specifications
DPB 02 C M23
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss and asymmetry with
built-in time delay function.
Supply ranges from 208 to
480 VAC covered by two
multi voltage relays.
DPB02
PPB02
No
otte
e: The input voltage
must not exceed the maxi-
mum rated voltage or drop
below the minumum rated
voltage reported above.







2
Specifications are subject to change without notice (18.07.06)
DPB02, PPB02
Mode of Operation
Connected with the 3 phas-
es (and neutral) DPB02 and
PPB02 operate when all 3
phases are present at the
same time, the phase
sequence is correct and the
asymmetry is under the set
level.
Asymmetry is defined as fol-
lows:
when measuring phase-
phase voltages and also as
follows:
when measuring phase-neu-
tral voltages.
If the asymmetry exceeds
the set level the red LED
starts flashing 2 Hz and the
output relay releases after
the set time period. If the
phase sequence is incorrect
or one phase is lost, the output
relay releases immediately.
Only 200 ms delay occurs.
The failure is indicated by the
red LED flashing 5 Hz after
the alarm condition occurs.
Example 1
(mains network monitoring)
The relay monitors asymme-
try, phase loss and correct
phase sequence.
Example 2
(load monitoring)
The relay releases in case of
interruption of one or more
phases or when the asym-
metry exceeds the set level.
Power supply
Overvoltage cat. III
Rated operational voltage
(IEC 60664, IEC 60038)
through terminals:
L1, L2, L3, N
(DPB02)
5, 6, 7, 11
(PPB02)
M23 - Delta Voltage:
208 to 240 VAC 15%
45 to 65 Hz
M48 (DIN-rail) - Delta Voltage: 380 to 480 VAC 15%
45 to 65 Hz
M48 (DIN-rail) - Star Voltage:
220 to 277 VAC 15%
45 to 65 Hz
M48 (Plug-in) - Delta Voltage: 380 to 415 VAC 15%
45 to 65 Hz
M48 (Plug-in) - Star Voltage:
220 to 240 VAC 15%
45 to 65 Hz
Rated operational power
DPB02CM23, PPB02CM23
13 VA @
230 VAC, 50 Hz
DPB02CM48, PPB02CM48
13 VA @
400 VAC, 50 Hz
Supplied by L1 and L2
Supply Specifications
Power ON delay
1 s 0.5 s or 6 s 0.5 s
Reaction time
Incorrect phase sequence or
total phase loss
< 200 ms
Asymmetry
Alarm ON delay
< 200 ms (delay < 0.1 s)
Alarm OFF delay
< 200 ms (delay < 0.1 s)
Accuracy
(15 min warm-up time)
Temperature drift
1000 ppm/C
Delay ON alarm
10% on set value 50 ms
Repeatability
0.5% on full-scale
Indication for
Power supply ON
LED, green
Alarm ON
LED, red (flashing 2 Hz
during delay time)
Output relay ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3 (DPB02), 2 (PPB02)
Operating temperature
@ Max. voltage, 50 Hz
-20 to 60C, R.H. < 95%
@ Max. voltage, 60 Hz
-20 to 50C, R.H. < 95%
Storage temperature
-30 to 80C, R.H. < 95%
Housing
Dimensions
DPB02
22.5 x 80 x 99.5 mm
PPB02
36 x 80 x 94 mm
Weight
Approx. 120 g
Screw terminals
Tightening torque
Max. 0.5 Nm
acc. to IEC 60947
Approvals
UL, CSA
CE marking
Yes
EMC
Electromagnetic Compatibility
Immunity
According to EN 61000-6-2
Emissions
According to EN 61000-6-3
General Specifications
max{|
V
ph-ph
|}
nom. voltage
max{|
V
ph-n
|}
nom. voltage
Specifications are subject to change without notice (18.07.06)
3
DPB02, PPB02
Adjust the input range set-
ting the DIP switches 3 and
4 as shown below.
Select the desired function
setting the DIP switches 1
and 2 as shown below.
To access the DIP swiches
open the grey plastic cover
as shown below
Selection of asymmetry
and time delay:
Centre knob:
Setting of asymmetry on rel-
ative scale.
Lower knob:
Setting of delay on alarm
time on absolute scale (0.1
to 30 s).
Function/Range/Level and Time Delay Setting
Power ON delay
ON: 6 s 0.5 s
OFF: 1 s 0.5 s
Monitored voltage
ON: Phase-Neutral
OFF: Phase-Phase
Measuring range
SW3
ON
ON
OFF
OFF
SW4
ON
OFF
ON
OFF
M23 Ph-Ph
208 VAC 220 VAC 230 VAC
240 VAC
Voltage
M48 Ph-Ph
380 VAC 400 VAC 415 VAC
480 VAC
Voltage
DPB02 only
M48 Ph-N
220 VAC 230 VAC 240 VAC
277 VAC
Voltage
DPB02 only
Operation Diagrams
4
Specifications are subject to change without notice (18.07.06)
DPB02, PPB02
Dimensions
22.5
8
0
8
3
.
5
99.5
6
3
28.5
DIN-rail
Plug-in
36
8
0
94
28.5
6
3
90
Wiring Diagrams
DPB02
PPB02