ChipFind - документация

Электронный компонент: EBDCD23

Скачать:  PDF   ZIP
Specifications are subject to change without notice (26.10.99)
1
Product Description
Ordering Key
Interval
One shot at supply on and/or supply off
Knob selection of function
Knob-adjustable time pulse duration: 0.15-3 s
Automatic start
Oscillator-controlled time circuit
Repeatability deviation:
0.2%
Output: 5 A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm Euronorm housing
LED-indication for relay and power supply ON
Combined AC and DC power supply
Housing
Function
Type
Output
Power supply
Mono-function one shot in-
terval timer featuring 3 modes
of operation. Knob adjustable
pulse time duration. Often
used in motor applications
where a contactor has to be
started or switched off.
Type Selection
Mounting
Output
Supply: 24 VAC/DC & 115 VAC
Supply: 24 VAC/DC & 230 VAC
For DIN-rail
SPDT
EBD C D11
EBD C D23
Time Specifications
Output Specifications
Time range
0.15 - 3 s
Function
Selectable by rotary switch
F1: Pulse at supply ON
F2: Pulse at supply OFF
F3: Pulse at supply ON
and OFF
Time range accuracy
20% on max.
min. setting: actual time
min. set time
Repeatability deviation
0.2%
Time variation
Within rated power supply
0.2%/V
and ambient temperature
0.2%/C
Reset
Time and relay
Power supply interruption
200 ms
Output
SPDT relay
Rated insulation voltage
250 VAC (contact/elect.)
Contact ratings (AgCdO)
(micro gap)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life
40 x 10
6
operations
Electrical life
10
5
operations
(at max. load)
Operating frequency
7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 s)
Type EBD
Timers
EBD C D23
2
Specifications are subject to change without notice (26.10.99)
Supply Specifications
Power supply
Overvoltage cat. III (IEC 664)
Rated operational voltage
(IEC 38)
through term. A1 & A2 D11
115 VAC, -10/+15%
D23
230 VAC, -10/+15%
frequency
50/60 Hz, -5/+5 Hz
through term. A2 & A3 D11
24 VAC/DC, -10/+15%
D23
24 VAC/DC, -10/+15%
frequency
50/60 Hz, -5/+5 Hz
Voltage interruption
40 ms
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand
voltage
4 kV (1.2/50 s)
Rated operational current
AC
1.5 VA @ 230 VAC
1.5 VA @ 115 VAC
80 mA @ 24 VAC
DC
60 mA @ 24 VDC
General Specifications
EMC
Electromagnetic
Compatibility
Immunity
Acc. to IEC 801-4
Acc. to IEC 801-5
Power ON time
6 s
(before obtaining F2 or F3)
Power ON delay
100 ms
Power OFF delay
200 ms
Indication for
Power supply ON
LED, green
Relay ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
170 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to IEC 947
EBD
Mode of Operation
Shot only at supply ON (F1)
When power supply is applied,
the relay operates and will be
kept energized for the set time
period (0.15-3 s). When power
supply is interrupted, the re-
lay will not operate.
If power supply is applied, in-
terrupted and reapplied dur-
ing the pulse period, the pulse
duration can be extended.
Shot only at supply OFF (F2)
When power supply is applied,
the relay will not operate.
When power supply is inter-
rupted, the relay operates and
will be kept energized for the
set time period (0.15-3 s).
If power supply is interrupted,
reapplied and again interrup-
ted during the pulse period,
the pulse duration can be ex-
tended.
Shot at supply ON & OFF (F3)
When power supply is applied,
the relay operates and will be
kept energized for the set time
period (0.15-3 s). When power
supply is interrupted, the re-
lay operates again and will be
kept energized for the same
set time period.
If power supply is applied or
interrupted for a time period
shorter than the pulse dura-
tion, the ON- and OFF-pulses
can be extended.
Wiring Diagram
N
L
Time and Function Setting
Time setting
Lower knob:
Knob-adjustable on relative
scale.
Function setting
Upper knob:
Selection of F1-F2-F3 on
rotary switch.
24 V
~
Operation Diagram
EBD C D11: 115 V
~
EBD C D23: 230 V
~
Power supply
F1, Relay ON
F2, Relay ON
F3, Relay ON