ChipFind - документация

Электронный компонент: EBED1151M

Скачать:  PDF   ZIP
Specifications are subject to change without notice (27.12.99)
1
Mounting
Output
Time range
Supply:
Supply:
Supply:
Supply:
24 VAC/DC
24 VAC/DC
115 VAC
230 VAC
& 115-230 VAC
For DIN-rail
SPDT
0.1 s - 1 m
EBE C T23 1M
SPDT
1 m - 10 h
EBE C T23 10H
DPDT
0.1 s - 1 m
EBE D 024 1M
DPDT
1 m - 10 h
EBE D 024 10H
DPDT
0.1 s - 1 m
EBE D 115 1M
DPDT
1 m - 10 h
EBE D 115 10H
DPDT
0.1 s - 1 m
EBE D 230 1M
DPDT
1 m - 10 h
EBE D 230 10H
Timers
Interval, Delay on Release
Type EBE
Time range 0.1 s to 10 h
Pulse start
Knob-adjustable time setting
Knob selection of time range
Oscillator-controlled time circuit
Repeat accuracy:
0.2%
Output: 5 A SPDT or 5 A DPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm housing
LED-indication for relay and power supply ON
Combined AC and DC power supply
Product Description
Ordering Key
Housing
Function
Type
Output
Power supply
Time range
Type Selection
Mono-function, pulse con-
trolled interval timer with 3
selectable time ranges with-
in 0.1 s to 1 m or 1 m to 10 h.
For mounting on DIN-rail.
Often used in applications
such as flushing systems,
dosing plants, lighting
systems, etc.
Time Specifications
Time ranges
Type 1 M
Selectable by rotary switch
0.1 s - 1 s
1 s - 10 s
0.1 m - 1 m
Type 10 H
Selectable by rotary switch
1 m - 10 m
0.1 h - 1 h
1 h - 10 h
Repeat accuracy
0.2%
Time range accuracy
10% on max.
min. actual time
min. set time
Range 1 s
Min. time
0.15 s
Temperature drift
0.2%/C (
0.11%/F)
Reset
Power supply interruption
200 ms
Interconnect terminals
A1 & Y1
Reaction time:
100 ms
Output Specifications
Output
Type C
SPDT relay
Type D
DPDT relay
Rated insulation voltage
250 VAC (contact/elect.)
Contact ratings (AgCdO)
(micro gap)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life
40 x 10
6
operations
Electrical life
10
5
operations
(at max. load)
Operating frequency
7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 s)
EBE C T23 1M
2
Specifications are subject to change without notice (27.12.99)
EBE
General Specifications
EMC
Electromagnetic
Compatibiliry
Immunity
Acc. to IEC 60801-4
Acc. to IEC 60801-5
Power ON delay
< 200 ms
Power OFF delay
200 ms
Indication for
Power supply ON
LED, green
Output ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3
Operating temperature
-20 to+50C (-4 to +122F)
Storage temperature
-50 to+85C (-58 to +185F)
Weight
170 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to
IEC60947
Approvals
UL, CSA
CE-marking
Yes
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
(IEC 60038)
through term. A1 & A2 T23
115-230 VAC, -10/+15%
frequency
50/60 Hz, -5/+5 Hz
through term. A1 & A3 T23
24 VAC/DC, -10/+15%
frequency
50/60 Hz, -5/+5 Hz
through term. A1 & A2 024
24 VAC/DC, -10/+15%
frequency
50/60 Hz, -5/+5 Hz
through term. A1 & A2 115
115 VAC, -15/+15%
frequency
50/60 Hz, -5/+5 Hz
through term. A1 & A2 230
230 VAC, -15/+15%
frequency
50/60 Hz, -5/+5 Hz
Voltage interruption
40 ms
Dielectric voltage
None
Rated impulse withstand
voltage
4 kV (1.2/50 s)
Rated operational current
EBE C
25 mA @ 24 VDC
40 mA @ 24 VAC
30 mA @ 115 VAC
50 mA @ 230 VAC
EBE D
30 mA @ 24 VDC
50 mA @ 24 VAC
30 mA @ 115 VAC
40 mA @ 230 VAC
Wiring Diagrams
EBE C
EBE D
Operation Diagram
Mode of Operation
Power supply must be con-
stantly applied.
When terminals A1 & Y1 are
interconnected, the relay
operates, and when A1 & Y1
are disconnected, the time
period starts.
When the time has expired,
the relay releases, and the
relay is ready for a new
sequence.
When interconnecting A1 &
Y1 before the relay has
released the time period is
reset, and a new time period
starts when disconnecting
A1 & Y1.
Time Setting
Selection of time ranges
Upper knob:
3-position rotary switch.
Time setting
Lower knob:
Knob-adjustable on relative
scale 1-10.