Specifications are subject to change without notice
1
Type EIC
Current and Voltage Controls
AC/DC under current (closed circuit)
metering relay
Measuring through external shunt
3-position rotary switch for selection of measuring range
Measuring range:
10-50 mV, 12-60 mV, 30-150 mV or
20-100 mV, 24-120 mV, 60-300 mV
Adjustable limit on relative scale
Adjustable time function (0.1-10 s)
Adjustable hysteresis
Output: 5 A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm Euronorm housing
LED-indication for relay and power supply ON
Galvanically separated power supply
Housing
Function
Type
Output
Power supply
EIC C 230
Product Description
Ordering Key
EIC is a precise AC/DC under
current (shunt) metering re-
lay. Measures the voltage of
an externally connected stan-
dard shunt also for high cur-
rent applications. The built-in
LED's indicate the exact sta-
tus of the output relay.
Type Selection
Mounting
Output
Measuring range
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
For DIN-rail
SPDT
10 - 300 mV
EIC C 024
EIC C 115
EIC C 230
Input Specifications
Input
Through terminals Y1 & Y2
Range x 1
Through terminals Y1 & Y3
Range x 2
Measuring ranges
Internal resist. Max. volt.
x 1 input:
Rotary
1: 10 - 50 mV
270
1 V
Switch
2: 12 - 60 mV
270
1 V
Position
3: 30 - 150 mV
270
1 V
x 2 input:
Rotary
1: 20 - 100 mV
540
2 V
Switch
2: 24 - 120 mV
540
2 V
Position
3: 60 - 300 mV
540
2 V
Max. line voltage
277/480 VAC/DC
Output Specifications
Output
SPDT relay
Rated insulation voltage
250 VAC (contact/elect.)
Contact ratings (AgCdO)
(micro gap)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life
40 x 10
6
operations
Electrical life
10
5
operations
(at max. load)
Operating frequency
7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 s)
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
(IEC 60038)
Through term. A1 & A2 024
24 VAC 15%, 45 to 65 Hz
115
115 VAC 15%, 45 to 65 Hz
230
230 VAC 15%, 45 to 65 Hz
Voltage interruption
40 ms
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand
voltage
4 kV (1.2/50 s)
Rated operational power
1.5 VA
1-Phase AC/DC Under Current (Shunt)
2
Specifications are subject to change without notice
EIC
General Specifications
Power ON delay
< 2 s
Power OFF delay
> 200 ms
Reaction time
< 200 ms
worst case reaction time
may be up to 5 x
Adjustable delay on release
built-in (0.1-10 s)
Accuracy
Input
10% (DC/AC @ 50 Hz)
OFF delay
10 s, -1/+3 s on max.
< 0.1 s on min.
Temperature drift
0.2%/C (
0.11%/F)
Indication for
Power supply ON
LED, green
Output ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
140 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to IEC 60947
Approvals
UL, CSA
Mode of Operation
EIC measures both AC and
DC current (voltage) through
an external standard shunt.
Example 1
The relay operates when the
measured value exceeds the
set level plus the hysteresis.
When the voltage (current)
drops below the set level for
more than the set delay, or
when power supply is inter-
rupted, the relay releases.
The yellow LED is flashing un-
til the delay has expired, or
until the measured value ex-
ceeds the set level plus the
hysteresis.
Range/Level/Time Setting
Upper knob:
Setting of current (voltage)
range on rotary switch.
Centre knob:
Level setting on relative scale.
Lower knob:
Setting of OFF delay on abso-
lute scale (0.1-10 s).
Hysteresis
Normally 5%. The hysteresis
can be extended by inserting
a resistor between terminals
Z1 & Z2.
Approx.
10%: 39 k
25%: 12 k
50%: 4.7 k
75%: 2.2 k
100%: 1.5 k
Wiring Diagram
Example 1
Operation Diagram
Power supply
Set level
Relay ON
Hysteresis
Hysteresis
adjustment