1
Type EID
Current and Voltage Controls
AC/DC under current metering (closed
circuit) relay
Current measuring through internal shunt
3 position rotary switch for selection of measuring range
Measuring ranges:
0.4 mA - 10 A
Adjustable current limit on relative scale
Adjustable time function (0.1-10 s)
Adjustable hysteresis
Output: 5 A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm Euronorm housing
LED-indication for relay and power supply ON
Galvanically separated power supply
Ordering Key
Housing
Function
Type
Output
Power supply
Measuring range
Input Specifications
Input
Through terminals Y 1 & Y2
current level
Measuring ranges
Internal resist. Max. curr.
20 mA type
Rotary
1: 0.4 - 2 mA
50
50 mA
Switch
2: 1 - 5 mA
50
50 mA
Position
3: 4 - 20 mA
50
50 mA
500 mA type
Rotary
1: 10 - 50 mA
3.9
600 mA
Switch
2: 40 - 200 mA
3.9
600 mA
Position
3: 100 - 500 mA
3.9
600 mA
5 A type
Rotary
1: 0.2 - 1 A
0.05
6 A
Switch
2: 0.4 - 2 A
0.05
6 A
Position
3: 1 - 5 A
0.05
6 A
10 A type
Rotary
1: 0.4 - 2 A
0.01
12 A
Switch
2: 1 - 5 A
0.01
12 A
Position
3: 2 - 10 A
0.01
12 A
Max. current
for 10 s
40 A
Max. line voltage
277/480 VAC/DC
Output Specifications
Output
SPDT relay
Rated insulation voltage
250 VAC, (contact/elect.)
Contact ratings (AgCdO)
(micro gap)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life
40 x 10
6
operations
Electrical life
10
5
operations
(at max. load)
Operating frequency
7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 s)
EID is a precise AC/DC under
current metering relay and of-
ten used in applications where
small loads have to be con-
trolled. The built-in LED's in-
dicate the exact status of the
output relay. Through the built-
in shunt it is possible to meas-
ure loads up to 10 A.
Product Description
Type Selection
1-Phase AC/DC Under Current
Mounting
Output
Measuring range
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
For DIN-rail
SPDT
0.4 - 20 mA
EID C 024 20mA
EID C 115 20mA
EID C 230 20mA
SPDT
10 - 500 mA
EID C 024 500mA
EID C 115 500mA
EID C 230 500mA
SPDT
0.2 - 5 A
EID C 024 5A
EID C 115 5A
EID C 230 5A
SPDT
0.4 - 10 A
EID C 024 10A
EID C 115 10A
EID C 230 10A
EID C 230 20mA
2
Specifications are subject to change without notice
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
(IEC 60038)
Through pins A1 & A2 024
24 VAC 15%, 45 to 65 Hz
115
115 VAC 15%, 45 to 65 Hz
230
230 VAC 15%, 45 to 65 Hz
Voltage interruption
40 ms
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand
voltage
4 kV (1.2/50 s)
Rated operational power
1.5 VA
General Specifications
EID
Power ON delay
< 2 s
Power OFF delay
> 200 ms
Reaction time
< 200 ms
worst case reaction time
may be up to 5 x
Adjustable delay on release
built-in (0.1-10 s)
Accuracy
Input
10% (DC/AC @ 50 Hz)
OFF delay
10 s, -1/+3 s on max.
< 0.1 s on min.
Temperature drift
0.2%/C (
0.11%/F)
Indication for
Power supply ON
LED, green
Output ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
140 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to IEC 60947
Approvals
UL, CSA
EID measures both AC and
DC under current through an
internal shunt.
Example 1
The relay operates when the
measured value exceeds the
set level plus hysteresis.
When the current drops below
the set level for more than
the set delay, or when power
supply is interrupted, the relay
releases.
The yellow LED is flashing until
the delay has expired, or until
the measured value exceeds
the set level plus the hystere-
sis.
Mode of Operation
Wiring Diagram
Example 1
Relay ON
Operation Diagram
Power supply
Set level
Hysteresis
Upper knob:
Setting of current range on
rotary switch.
Centre knob:
Current level setting on rela-
tive scale.
Lower knob:
Setting of OFF delay on abso-
lute scale (0.1-10 s).
Hysteresis
Normally 5%. The hysteresis
can be extended by inserting
a resistor between terminals
Z1 & Z2.
Approx.
10%: 39 k
25%: 12 k
50%: 4.7 k
75%: 2.2 k
100%: 1.5 k
Range/Level/Time Setting
Hysteresis
adjustment
Supply Specifications