ChipFind - документация

Электронный компонент: EIIC0245A

Скачать:  PDF   ZIP
Specifications are subject to change without notice
1
Current and Voltage Controls
Type EII
AC/DC over current metering
(open circuit) relay
Current measuring through internal shunt
3 position rotary switch for selection of measuring range
Measuring ranges: 0.4 mA - 10 A
Adjustable current limit on relative scale
Adjustable time function (0.1-10 s)
Adjustable hysteresis
Programmable latching at set level
Output: 5 A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm Euronorm housing
LED-indication for relay and power supply ON
Galvanically separated power supply
Ordering Key
Housing
Function
Type
Output
Power supply
Measuring range
EII is a precise AC/DC over
current metering relay and
often used in applications
where small loads have to be
controlled. The advantage of
Product Description
using the latch function is that
the output relay can be kept
energized so that e.g. a short-
circuit can be indicated.
Type Selection
Input Specifications
Output Specifications
Output
SPDT relay
Rated insulation voltage
250 VAC (contact/elect.)
Contact ratings (AgCdO)
(micro gap)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life
40 x 10
6
operations
Electrical life
10
5
operations
(at max. load)
Operating frequency
7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 s)
1-Phase AC/DC Over Current
EII C 230 20mA
Mounting
Output
Measuring range
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
For DIN-rail
SPDT
0.4 - 20 mA
EII C 024 20mA
EII C 115 20mA
EII C 230 20mA
SPDT
10 - 500 mA
EII C 024 500mA
EII C 115 500mA
EII C 230 500mA
SPDT
0.2 - 5 A
EII C 024 5A
EII C 115 5A
EII C 230 5A
SPDT
0.4 - 10 A
EII C 024 10A
EII C 115 10A
EII C 230 10A
Input
Through terminals Y1 & Y2
current level
Measuring ranges
Internal resist. Max. curr.
20 mA type
Rotary
1: 0.4 - 2 mA
50
50 mA
Switch
2: 1 - 5 mA
50
50 mA
Position
3: 4 - 20 mA
50
50 mA
500 mA type
Rotary
1: 10 - 50 mA
3.9
600 mA
Switch
2: 40 - 200 mA
3.9
600 mA
Position
3: 100 - 500 mA
3.9
600 mA
5 A type
Rotary
1: 0.2 - 1 A
0.05
6 A
Switch
2: 0.4 - 2 A
0.05
6 A
Position
3: 1 - 5 A
0.05
6 A
Max. current for 10 s
30 A
10 A type
Rotary
1: 0.4 - 2 A
0.01
12 A
Switch
2: 1 - 5 A
0.01
12 A
Position
3: 2 - 10 A
0.01
12 A
Max. current for 10 s
40 A
Max. line voltage
277/480 VAC/DC
2
Specifications are subject to change without notice
EII
General Specifications
Power ON delay
< 2 s
Power OFF delay
> 200 ms
Reaction time
< 200 ms
worst case reaction time
may be up to 5 x
Adjustable delay on operate
built-in (0.1-10 s).
Accuracy
Input
10% (DC/AC @ 50 Hz)
ON delay
10 s, -1/+3 s on max.
< 0.1 s on min.
Temperature drift
0.2%/C (
0.11%/F)
Indication for
Power supply ON
LED, green
Output ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
140 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to IEC 60947
Approvals
UL, CSA
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
(IEC 60038)
through pins A1 & A2
024
24 VAC, -10/+15%
115
115 VAC, -10/+15%
230
230 VAC, -10/+15%
Voltage interruption
40 ms
Dielectric voltage
2 kVAC (RMS)
Rated impulse withstand
voltage
4 kV (1.2/50 s)
Rated operational power
1.5 VA
Mode of Operation
EII measures both AC and DC
over current through an inter-
nal shunt.
Example 1
(no connection between ter-
minals Z1 & Z2)
The relay operates when the
measured value exceeds the
set level for more than the set
delay time.
The relay releases when the
current drops min. 5% below
the set level (see hysteresis),
or when power supply is inter-
rupted.
Example 2
(connection between termi-
nals Z1 & Z2)
The relay operates and latches
in operating position when the
measured value exceeds the
set level for more than the set
delay time.
Provided that the voltage has
dropped min. 5% below the
set point (see hysteresis), the
relay will release when the in-
terconnection between termi-
nals Z1 & Z2 is interrupted, or
power supply is interrupted.
If the measured value is above
the set level when power sup-
ply is applied, the relay will
operate immediately with no
time delay.
The yellow LED is flashing until
the delay-time has expired or
the measured value drops
below the fixed hysteresis
(5%) again.
Range/Level/Time Setting
Upper knob:
Setting of current range on
rotary switch.
Centre knob:
Current level setting on rela-
tive scale.
Lower knob:
Setting of ON delay on abso-
lute scale (0.1-10 s).
Hysteresis
Normally 5%. The hysteresis
can be extended by inserting
a resistor between terminals
Z1 & Z2.
Approx.
10%: 39 k
25%: 12 k
50%: 4.7 k
75%: 2.2 k
Latch: <500
Specifications are subject to change without notice
3
EII
Wiring Diagrams
Example 1
Example 2
N
L
L
N
+
+
PE
PE
Hysteresis
adjustment
Latch/Hysteresis
adjustment
Power supply
Set level
Relay ON
Hysteresis
Power supply
Latch ON
Set level
Relay ON
Hysteresis
Operation Diagrams
T
T
T
T