ChipFind - документация

Электронный компонент: FAA01DM24

Скачать:  PDF   ZIP
Specifications are subject to change without notice (26.07.05)
1
Product Description
Ordering Key
Delay on Operate
Delay on operate timer with
4 functions and selectable
time ranges from 0.05 sec-
onds to 300 hours.
Housing 48 x 48 mm for
front panel mounting and on
8-pin or 11-pin socket.
Time range 0.05 s to 300 h
Knob selection of time range
Knob adjustable time setting
Knob selection of operating mode (4 functions):
A
- delay on operate
B
2
- symmetrical recycler ON first
E
- interval
J
- one shot
Automatic start
Repeatability: 0.3% on full scale
Output: 5 A DPDT relay
48 x 48 mm housing for front panel mounting
8 or 11 pin sockets
LED indication for relay status and power supply ON
Type Selection
FAA 01 D M24
Housing
Function
Type
Item number
Output
Power supply
Mounting
Output
Plug
Supply: 100 to 240 VAC
Front or socket
DPDT
11-pin
FAA01DM24
Front or socket
DPDT
8-pin
FAA08DM24
Time Specifications
Time ranges
Selectable by front knob
Repeatability
0.3% on full scale
(10 ms max in the range
of 1.2 s)
Setting accuracy
5% on full scale 50 ms
Voltage drift
0.5% on full scale
(10 ms max in the range of
1.2 s)
Temperature drift
2% on full scale
(10 ms in the range
of 1.2 s)
Reset
Power supply interruption
>100 ms
Pulse width
>50 ms
Types FAA01, FAA08
Timers
Power Supply
Overvoltage cat II
Rated operational voltage
(IEC 60947-1)
throuhgt terminals:
(FAA01DM24)
2, 10
100 to 240 VAC +10%-15%
50 / 60 Hz
(FAA08DM24)
2, 7
100 to 240 VAC +10%-15%
50 / 60 Hz
Power consumption
Rated operational power
10VA @ 240 VAC, (50 Hz)
Supply Specifications
Time unit
sec
min
hrs
10h
Full scale
setting
1.2
0.05 to 1.2
0.5 to 12
3
0.125 to 3
1.25 to 3
12
0.5 to 12
5 to 120
30
1.25 to 30
12.5 to 300
Output
DPDT relay
Output insulation resistance
> 100 M
(at 500 VDC)
Contact Ratings (AgCdO
12
)
Resistive loads
AC 1
5 A @ 250 VAC / 30 VDC
Mechanical life
1 x 10
7
operations
Electrical life
1 x 10
5
operations
(5 A at 250 VAC, cos
= 1,
1.8 x 10
3
operations/h)
Operating frequency
< 1800 operations/h
Output Specifications
2
Specifications are subject to change without notice (26.07.05)
FAA01, FAA08
Function and Time Setting
Range and operation mode selection
Operating mode display window
Operating mode selector
(function A, B
2
, E, J)
Scale range display windows
Time unit selector (sec, min, hrs, 10h)
Time setting knob (set time)
Power indicator (green)
(Flashes when timer operates;
on when timer stops operating)
Time range selector
(1.2, 3, 12 and 30 at full scale)
Output indicator (red)
(Lit when output is ON)
Time unit display window
Mode of Operation
Function A
Delay on operate
The set delay period begins
as soon as the power supply
is connected. At the end of
the set delay the relay oper-
ates and doesn't release
until the power supply is
interrupted for at least 100
ms.
Function B
2
Symmetrical recycler
(ON first)
The relay operates and the
time period start as soon as
the power is applied. At the
end of the first set time peri-
od, the relay releases. At the
end of the second time peri-
od (equal to the first), the
relay operates again. This
sequence continues with
equal ON- and OFF- time
periods until the power sup-
ply is interrupted for at least
100 ms.
Function E
Interval
The relay operates and the
time period begins as soon
as the power is applied. The
relay releases at the end of
the time period or when the
power supply is disconnect-
ed for at least 100 ms.
Function J
One shot
The time period begins as
soon as the power supply is
connected and at the end of
this period the relay operates
for 1s.
Indication for
Power supply On
LED, green
(flashing when timing)
Output ON
LED, red
Environment
Degree of protection
IP 40
(front panel)
Operating temperature
-10 to +55 C (14 to 131 F)
Ambient humidity
35 to 85% RH
Housing dimesions
48 x 48 mm
Weight
Approx. 95 g
CE marking
Yes
EMC
Electromagnetic Compatibillity
Immunity
According to EN 61000-6-1
Emission
According to EN 61000-6-3
General Specifications
Upper right knob:
Setting of function
A - delay on operate
B
2
- simmetrical recycler
E
- interval
J
- one shot
Lower right knob:
Time unit selector
sec (seconds)
min (minuts)
hrs
(hours)
10h (10 hours)
Lower left knob:
Time range selector
1.2, 3, 12 and 30
Centre knob:
Time setting on relative
scale
Specifications are subject to change without notice (26.07.05)
3
FAA01, FAA08
Operating Diagrams
T
T
Power supply
LED "POWER"
Relay
Function E - Interval
T
T
1s0.6s
1s0.6s
Power supply
LED "POWER"
Relay
Function J - One Shot
T
T
T
T
T
Power supply
LED "POWER"
Relay
Power supply
T
LED "POWER"
Relay
T
Function A - Delay ON operate
Function B
2
- Symmetrical Recycler (ON first)
Wiring Diagrams
L(+)
N(-)
m
m
2
1
11
4
8
3
9
10
FAA01
L(+)
N(-)
m
m
2
1
8
4
5
3
6
7
FAA08
Dimensions
48
39
81.6
68.2
15
9
48
48
48
39
6
15
60,2
81,6
FAA01 - FAA08