ChipFind - документация

Электронный компонент: G21391139

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (28.09.99)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Type: Dupline
Type
Enables displaying of AnaLink signals on
EDM35 panel meters
Operates with standard Dupline
channel generator
Coding by two rotary switches
Easy to use
Built-in prog-lock for all settings
Product Description
Ordering Key
Dupline
input module for
EDM35 panel meters which
can read the signal from any
type of AnaLink sensor. The
1-channel Dupline
address
of the desired AnaLink sen-
sor is selected by means of
two rotary switches. EDM35
panel meters at different
locations can display the
same AnaLink signal.
The Dupline
channel used
must be monostable (stan-
dard Dupline
without spe-
cial function), which means
that all channel generator
types can be used.
Type Selection
Supply
Ordering no.
1 channel
EDM-module
By EDM35
G 2139 1139
Supply Specifications
AnaLink EDM35 Plug-in Card
Power supply
Supplied by EDM35
Type G 2139 1139
G 2139 1139
General Specifications
Range
According to the used
AnaLink sensor. The EDM35
can be scaled to read out
any type
Error indications
EE
Overflow
-EE
Underflow or
Dupline
not connected
EMC
According to IEC 60801-4,
IEC 60801-5
Settings
Scaling: Factory setting:
DP
111.1
HiE
1999
LoE
0
Hi
60.0 [C]
Lo
-30.0 [C]
Calibration: Factory setting:
Range code 7
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (28.09.99)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Wiring Diagram
PROG.
LOCK
DUPLINE
S
Dupline
AnaLink plug-in
module for EDM 35
This new module forms a
link between two successful
product concepts developed
by Carlo Gavazzi: the EDM
35 digital panel meter and
Dupline
-AnaLink. This com-
bination enables reliable
measuring techniques, in
particular in applications
with temperature monitor-
ing, - control and analogue
measuring values.
The analogue measuring val-
ues appearing at different
locations in an installation
are detected by AnaLink
sensors, which are all con-
nected to a twisted pair of
cables. The measuring val-
ues are then displayed either
locally or centrally (up to 5
km away) or both by means
of EDM 35 panel meters.
The display of analogue
measuring values at different
locations in an installation is
made possible by the G
2139 1139 module, which
can be coded so that the
same analogue measuring
value is displayed at many
locations.
Function and setting of the
plug-in module is so simple
that also personnel without
experience in Dupline
can
start up the system success-
fully.
By using this plug-in module
there is no need for the tem-
perature monitoring module
G3890 0030, which is nor-
mally required for applica-
tions with AnaLink sensors.
Instead standard channel
generators can be used, eg
type G 3490 0000 or type
FPD 1901. It should be
noted that the plug-in mod-
ule can only be used in
channels with normal mon-
stable function.
The plug-in module G 2139
1139 features two rotary
switches, with which to
select the 1-channel
Dupline
address of those
AnaLink sensors whose
measuring values must be
displayed. The channel
group is selected with one
switch and the channel num-
ber with the other switch.
This address selection and
as well as the scaling and
setting of the EDM 35 is all
that is needed for the config-
uration.
Description
The following AnaLink sensors can be connected to G 2139 1139:
Type Measuring
Range
Characteristics
G 8911 1010
-30 to +60C
Power supply by Dupline
, Pt 1000 sensor integrated
G 3210 1111
-50 to +40C
Power supply by Dupline
, external Pt 100 sensor required
G 3210 1112
+30 to +120C
Power supply by Dupline
, external Pt 100 sensor required
G 3210 1113
-10 to +100C
Power supply by Dupline
, external Pt 100 sensor required
G 3210 1161
4 to 20 mA
Power supply by Dupline
and 4-20 mA input
G 2139 1139