ChipFind - документация

Электронный компонент: G32101112

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (30.04.03)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
AnaLink transmitter for 3-wire Pt-100 input
Built-in cable compensation
Built-in signal linearization
Temperature range:
G 3210 1111: -50 to +40C (-58 to +104F)
G 3210 1112: +30 to +120C (+86 to +248F)
G 3210 1113: -10 to +100C (+14 to 212F)
Uses only one channel
Supplied by Dupline
Channel coding by GAP 1605
H2-housing
For mounting on DIN-rail in accordance
with EN 50 022
Product Description
Ordering Key
AnaLink transmitter for con-
nection of external 3-wire Pt-
100 temperature transducer.
The module measures the
temperature and transmits
the value to the controller G
3890 0030, in which the tem-
peratures from all transmit-
ters are logged and printed
out and/or read from a PC.
The module is supplied by
the Dupline
signal which
means easy installation and
flexibility for future expansion.
Type: Dupline
H2 Housing
Temperature range
G 3210 1111
Type Selection
Input Specifications
Signal input
3-wire Pt-100
Temperature range
G 3210 1111: -50 to +40C
G 3210 1112: +30 to +120C
G 3210 1113: -10 to +100C
Resolution
8 bits (~0.35C/LSB)
(G3210 1113: (0.43C/LSB))
Inaccuracy
0.5C (G32101113: 0.6C)
(ambient temperature
G 3210 111.: 25C)
Temperature drift
0.02C/K
(
ambient temperature
G 3210 111.)
Cable length
5 m
Response time
256 pulse trains
(~18 s @ 64 ch.)
Supply Specifications
General Specifications
Channel programming
By GAP 1605
Channel assignment
1 channel
freely programmable
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Humidity (non-condensing)
20 to 80% RH
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
Material
(See Technical Information)
H2-housing
Weight
90 g
Transmitter for Analog Pt-100
Temperature Signal
Types G 3210 1111, G 3210 1112, G 3210 1113
Current consumption
1.7 mA (from Dupline
)
Power dissipation
10 mW
Supply:
Ordering no.
Ordering no.
Ordering no.
Range: -50 to +40C
Range: +30 to +120C
Range: -10 to +100C
By Dupline
G 3210 1111
G 3210 1112
G 3210 1113
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (28.09.99)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3210 1111, G 3210 1112, G 3210 1113
Distance versus No. of Sensors
Wiring Diagram
Accessories
DIN-rail
FMD 411
For further information refer to "Accessories".
Example:
Max. distance for 30 sensors
G 3210 1111: 30 x 2 mA = 60 mA
loop resistance ~ 35
. If 1.5 mm
2
cable @ 12
/km is used, the distance
is:
Dupline
load (mA)
from AnaLink
sensors
DC loop
resistance (
)
2 x 12
/km
35
= 1.45 km max.
S
S: Signal wire
Dimensions (mm)
H1/H2-housing