ChipFind - документация

Электронный компонент: G34296470800

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (28.09.99)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description
Ordering Key
Type: Dupline
H4-housing
Transmitter
No. of channels
Input type
Power supply
4 isolated analog inputs
Inputs individually configurable for 0-20 mA,
4-20 mA or 0-10 VDC
Selectable resolution: 1/1999 or 1/255 of full scale
Selectable data format: 8-bit binary, Analink or 3 1/2
digit BCD
EMC immunity according to EN 50082-2 (industrial
environment)
DIN-rail mounting (EN 50022)
Address-selection through rotary-switches
LED-indication for Supply and Dupline
carrier
LED-indication for invalid switch setting and 4-20 mA
underflow
AC or DC power supply
Type Selection
Supply
Ordering no.
24 VAC
G 3429 6470 024
115 VAC
G 3429 6470 115
230 VAC
G 3429 6470 230
10-30 VDC
G 3429 6470 800
Input Specifications
Dupline
4 input universal
analog input module for
external supply. Analog values
on the inputs are converted
to digital values and transmit-
ted on Dupline
. Inputs are
isolated individually to pre-
vent ground-loops and to
simplify installation. The input
type can be selected as 0-20
mA, 4-20 mA or 0-10 VDC
for each input individually
making a mix of analog input
types on the same input
module possible. The trans-
mission format on Dupline
can be selected to fit the
input module into existing
installations, or simply to use
the most suitable combina-
tion of resolution and speed.
The formats are: 8-bit binary,
Analink and 3 1/2 digit BCD
(with or without multiplexing).
Universal Analog Input Module for DIN-Signals
Type G 3429 6470
G 3429 6470 024
Inputs set to voltage measurement
Inputs set to current measurement
Signal
Signal input
DIN-voltage input
DIN-current input
Signal range
0-10 VDC
0-20 mA / 4-20 mA
Max. input level
50 V
50 mA
Input resistance
125 K
100
shunt resistor
Resolution
A/D
11 bits or 8 bits
11 bits or 8 bits
Transmission
1/1999 or 1/255
1/1999 or 1/255
Settling time t
s
3 s
3 s
Inaccuracy
(ref. temp. 25C)
< 0.05% of full-scale
< 0.05% of full-scale
< 0.2% of reading
< 0.2% of reading
< 1 count
< 1 count
Temperature influence
(ref. temp. 25C)
< 10 ppm/K of full-scale
< 10 ppm/K of full-scale
< 50 ppm/K of reading
< 50 ppm/K of reading
Common mode rejection
> 120 dB (50-60 Hz)
> 120 dB (50-60 Hz)
CMRR Input-Input
> 80 dB (50-60 Hz)
> 80 dB (50-60 Hz)
Normal mode rejection
> 45 dB (50-60 Hz)
> 45 dB (50-60 Hz)
Cable length
< 25 m
< 25 m
Dielectric voltage
Input - Input
250 VAC (rms)
250 VAC (rms)
Input - Dupline
250 VAC (rms)
250 VAC (rms)
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (30.04.03)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Power supply AC-types
Overvoltage cat. lll (IEC 60664)
Rated operational voltage
through term. 21 & 22 230
230 VAC, 15 % (IEC 60038)
115 115 VAC, 15 % (IEC 60038)
024 24 VAC, 15 %
Frequency
45 to 65 Hz
Power consumption
typ. 5 VA
Power dissipation
6 W
Transient protection
230
4 kV
115
2.5 kV
024 800 V
Dielectric Voltage
Supply - Dupline
4 kVAC (rms)
Supply - Signal input
4 kVAC (rms)
Power supply DC-types
Overvoltage cat. lll (IEC 60664)
Rated operational voltage
through term. 21 & 22 800
10.5 V - 30 VDC (Ripple incl.)
Ripple
< 3 V
Reverse polarity protection
Yes
Power consumption
<1.7 W
Power dissipation
< 5 W
Rated impulse withstand
voltage
800 V
Dielectric Voltage
Supply - Dupline
500 VAC (rms)
Supply - Signal input
250 VAC (rms)
Power ON delay
4 s
Indication for
Supply ON
LED, green
Dupline
carrier ON
LED, yellow
Underflow (4-20 mA)
LED, red
Illegal switch setting
LED, red - flashing
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-20 to +85C (-4 to +185F)
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
Material
(see Technical information)
H4-Housing
Weight
300 g
CE-marking
Yes
G 3429 6470
Supply Specifications
General Specifications
Switch Settings
2
1
ON
3
4
Shunt-switches on system top
Current shunts on input 1-4:
ON = 0-20 mA / 4-20 mA
OFF = 0-10 V
Rotary switches in the front
Mode
3 1/2 digit:
Channel group-pair
Mux. address for input 1,
Ex. setting:
rest of the inputs (if enabled)
C or D = C-D
on the following addresses
8-bit:
Channel group
Mux. address for input 1,
rest of the inputs (if enabled)
on the following addresses
Analink:
Channel group
Channel no. for input 1, rest of
the inputs (if enabled) on the
following channels.
Setting of 0+9-F is not valid.
A-P
0-F
2
1
ON
3
4
6
5
7
8
10
9
Function switches in the front
Offset on input 1-4
ON = 4-20 mA
OFF = 0-20 mA / 0-10 V
No. of enabled inputs
OFF ON
: 1
ON
OFF : 2
ON
ON
: 3
OFF OFF : 4
Mode (Format)
OFF OFF : Analink
OFF ON
: 8-bit binary
ON
OFF : 3 1/2 digit BCD
ON
ON
: Reserved for future use
Multiplex ON/OFF
(Only used in 3 1/2 digit BCD and 8-bit binary mode)
ON
= Data is multiplexed
OFF = Data from input 1 is transmitted on the group (or grouppair) rotarysw. A-P is set to,
data from input 2, 3, 4 (if enabled) on the following groups (or grouppairs)
Reserved for future use
Don't care
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (28.09.99)
3
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3429 6470
Wiring Diagram
Mode of Operation
The G3429 6470 is a univer-
sal analog input module with
4 inputs. Each input can be
configured individually to
current or voltage measure-
ment. The transmission for-
mat is selectable and sup-
ports all Dupline
analog pro-
tocols Analink, 8-Bit or 3 1/2
digit BCD. Coding of the
module is solely done by dip-
and rotary-switches located
on the module, so the GAP
1605 programmer is not
needed.
With reference to the dia-
gram on the previous page,
the setting of the module
should be performed in the
following way:
Please note that no signals
must be applied to the inputs
before the correct mode
(current or voltage) is select-
ed by means of the 4 shunt
switches on the top of the
system.
Set the range of each input
(0/4-20 mA or 0/2-10 V) by
means of the switches 1-4
on the front of the module,
and select the actual number
of inputs used with switches
5 and 6.
The module only take up
Dupline
addresses ac-
cording to the number of
enabled inputs, and the select-
ed transmission protocol
(mode) set by switches 7 and
8.
Address allocation for the
Analink protocol:
If all four inputs are enabled,
the module will use four
Dupline
channels in consec-
utive order, starting from the
address set on the two rotary
switches on the front of the
unit.
Example: Setting of "D7"
means that input 1 transmits
on Dupline
channel D7,
input 2 transmits on D8,
input 3 transmits on E1 and
input 4 transmits on E2.
Address allocation for the
8-bit binary protocol:
If all four inputs are enabled
and non multiplexed mode is
selected (switch 9), the mo-
dule will use four Dupline
channel groups (32 channels)
in consecutive order, starting
from the group set on the
first rotary switch (A-P). The
second rotary switch (0-F) is
not used in this mode.
Example: Setting of "F" on
the first rotary switch means
that input 1 transmits on
Dupline
group F, input 2
transmits on G, input 3 trans-
mit on H and input 4 trans-
mits on I.
If multiplexed mode is select-
ed the module will use one
Dupline
channel group (8
channels). The first rotary
switch (A-P) is used to set
the group and the second
rotary switch (0-F) to set the
multiplex address to be used
by the first input, no. 1.
Example: Setting of "F" on
the first rotary switch and "0"
on the second, means that
input 1 transmits on Dupline
group F mux. adr. 0, input 2
transmits on F mux. adr. 1,
input 3 transmits on F mux.
adr. 2 and input 4 transmits
on F mux. adr. 3.
Address allocation for the 3
1/2 digit BCD protocol:
If all four inputs are enabled
and non-multiplexed mode is
selected (switch 9) the mo-
dule will use four Dupline
channel group-pairs (64
channels) in consecutive
order. The first rotary switch
(A-P) is used to set the start
group pair. The second rotary
switch (0-F) has no function
in this mode.
Example: Setting of "C" or
"D" on the first rotary switch
means that input 1 transmits
on Dupline
group-pair C-D,
input 2 transmits on E-F,
input 3 transmits on G-H and
input 4 transmits on I-J.
If multiplexed mode is select-
ed the module will use one
Dupline
channel group-pair
(16 channels). The first rotary
switch (A-P) is used to set
the group-pair and the
second rotary switch (0-F) to
set the multiplex address to
be used by the first input, no.
1.
Example: Setting of "C" or
"D" on the first rotary switch
and "8" on the second,
means that input 1 transmits
on Dupline
group-pair C-D
mux. adr. 8, input 2 transmits
on C-D mux. adr. 9, input 3
transmits on C-D mux. adr. A
and input 4 transmits on C-D
mux. adr. B.
Note
The selected transmission
protocol is valid for all
enabled inputs. The module
can not transmit different
protocols at the same time.
Analog transmitters must not
be used in systems where
channel generators with 2 or
3 sequences are installed.
Accessories
DIN Rail
FMD 411
For further information refer to "Accessories".
1
2
3
4
21
22
27
28
S
Supply
24
23
6
7
8
5
26
25
+ -
+ -
+ -
Input
1
Input
2
Input
3
Input
4
+ -
5VA
3,5W
(+)
(-)
Dimensions (mm)
H4-housing