ChipFind - документация

Электронный компонент: G34302249230

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (28.09.99)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description
Ordering Key
Type: Dupline
H4-housing
Receiver
No. of channels
Output type
Power supply
Receiver for Digital Signals
Types G 3430 1149, G 3430 2249, G 3430 4443
1-, 2- or 4-channel receiver
Galvanically separated SPDT or SPST
relay outputs
Load: 1 x 10 A/250 VAC
2 x 10 A/250 VAC
4 x 5 A/250 VAC
H4-housing
For mounting on DIN-rail (EN 50022)
LED-indications for supply, outputs and
Dupline
carrier
AC or DC power supply
Channel coding by GAP 1605
(see the data sheet on GAP 1605 for details)
Dupline
receiver.
SPDT relay outputs for con-
trol of 1or 2 loads of up to 250
Type Selection
Supply
Ordering no.
Ordering no.
Ordering no.
1 channel
2 channels
4 channels
10 A/250 VAC
10 A/250 VAC
5 A/250 VAC
24 VAC
G 3430 1149 024
G 3430 2249 024
G 3430 4443 024
115 VAC
G 3430 1149 115
G 3430 2249 115
G 3430 4443 115
230 VAC
G 3430 1149 230
G 3430 2249 230
G 3430 4443 230
10 to 30 VDC
G 3430 1149 800
15 to 30 VDC
G 3430 2249 824
G 3430 4443 824
VAC/10 A or SPST relay out-
puts for control of 4 loads of
up to 250 VAC/5 A.
Output Specifications
G 3430 1149 ...
G 3430 2249 ...
G 3430 4443 ...
(1 channel)
(2 channels)
(4 channels)
Outputs
1 SPDT relay
2 SPDT relays
4 SPST relays
Isolated in groups of
1 x 1
2 x 1
4 x 1
Contact ratings (AgCdO)
(micro gap)
(micro gap)
(micro gap)
Resistive loads
AC 1
10 A/250 VAC (2500 VA)
10 A/250 VAC (2500 VA)
5 A/250 VAC (1250 VA)
DC 1
1 A/250 VDC (250 W)
1 A/250 VDC (250 W)
0.25 A/250 VDC (62 W)
or
10 A/25 VDC (250 W)
10 A/25 VDC (250 W)
5 A/25 VDC (125 W)
Inductive loads
AC 15
2.5 A/230 VAC
2.5 A/230 VAC
2.5 A/230 VAC
DC 13
5 A/24 VDC
5 A/24 VDC
5 A/24 VDC
Mechanical lifetime
30 x 10
6
operations
30 x 10
6
operations
30 x 10
6
operations
Electrical lifetime
(at max load)
AC 1
2.5 x 10
5
operations
2.5 x 10
5
operations
2.0 x 10
6
operations
Operating frequency
7200 operations/h
7200 operations/h
7200 operations/h
Dielectric voltage
Outputs - Dupline
4 kVAC (rms)
4 kVAC (rms)
4 kVAC (rms)
Response time
1 pulse train
1 pulse train
1 pulse train
G 3430 4443 024
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (30.04.03)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3430 1149, G 3430 2249, G 3430 4443
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 230
230 VAC 15% (IEC 60038)
115
115 VAC 15% (IEC 60038)
024
24 VAC 15%
Frequency
45 to 65 Hz
Voltage interruption
40 ms
Rated operational power
G 3430 1149 024/115/230 Typ. 3.5 VA
G 3430 2249 024/115/230
Typ. 4.5 VA
G 3430 4443 024/115/230
Typ. 3.5 VA
Power dissipation
G 3430 1149 024/115/230
6.5 W
G 3430 2249 024/115/230
8 W
G 3430 4443 024/115/230
8 W
Rated impulse withstand
voltage 230
4
kV
115
2.5 kV
024
800 V
Dielectric voltage
Supply - Dupline
4 kVAC (rms)
Supply - Outputs
4 kVAC (rms)
Power supply DC types
Overvoltage cat. III (IEC 60664)
Operational voltage
through term. 21 & 22 800
10 to 30 VDC (ripple included)
824
15 to 30 VDC (ripple included)
Ripple
3 V
Reverse-polarity protection
Yes
Rated operational current
G 3430 1149 800
150 mA
G 3430 2249 824
150 mA
G 3430 4443 824
100 mA
Power dissipation
G 3430 1149 800
5.5 W
G 3430 2249 824
5.5 W
G 3430 4443 824
6 W
Inrush current
1 A
Rated impulse withstand
voltage
800 V
Dielectric voltage
Supply - Dupline
200 VAC (rms)
Supply - Outputs
4 kVAC (rms)
General Specifications
Output OFF delay
Upon loss of Dupline carrier
20 ms
Power ON delay
Typ. 2 s
Power OFF delay
1 s
Indication for
Supply ON
LED, green
Output ON
LED, red (one per output)
Dupline
carrier
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
Material
(see Technical informations)
H4-housing
Weight
G 3430 1149, G 3430 2249
250 g
G 3430 4443
300 g
Mode of Operation
1-channel receiver with
change-over contact output
The output is coded by
means of the code program-
mer GAP 1605.
The output is normally OFF.
When a transmitter coded to
the selected channel is acti-
vated, the output turns on
and remains on until the
respective channel becomes
deactivated. The default set-
ting is such that upon loss of
Dupline
carrier the output
goes off.
2-channel receiver with two
change-over contact out-
puts
Each output may be coded
individually by means of the
code programmer GAP 1605.
The outputs are normally off.
When a transmitter coded to
the selected channel is ac-
tivated, the output turns on
and remains on until the re-
spective channel becomes
deactivated. The default set-
ting of the module is such
that upon loss of Dupline
carrier all outputs go off.
4-channel receiver with
four normally open contact
outputs
Each output may be coded
individually by means of the
code programmer GAP 1605.
The default setting of the
module is such that upon
loss of Dupline
carrier all
outputs go off.
For changing the default set-
ting, please refer to the data-
sheet on GAP 1605.
Operation Diagram
Dupline
carrier
Transmission on channel 1
Output 1
Transmission on channel 2
Power supply
Output 2
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (28.09.99)
3
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3430 1149, G 3430 2249, G 3430 4443
Wiring Diagrams
Accessories
DIN-rail
FMD 411
For further information, see "Accessories".
2 channels G 3430 2249
AC (DC) supply
1 channel G 3430 1149
AC (DC) supply
4 channels G 3430 4443
AC (DC) supply
Out-
put 1
Out-
put 2
Out Out
1
2
(+) (-)
Power
supply
(+) (-)
Out Out
3
4
Power
supply
(+) (-)
Power
supply
Output
S: Signal wire
S: Signal wire
S: Signal wire