ChipFind - документация

Электронный компонент: G34304249230

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (30.04.03)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Power supply AC types
Installations cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 230
230 VAC 15% (IEC 60038)
115
115 VAC 15% (IEC 60038)
024
24 VAC 15%
Frequency
45 to 65 Hz
Drop-out tolerance
40 ms
Power consumption
Typ. 3.5 VA
Power dissipation
9 W
Transient protection volt. 230
4 kV
115
2.5 kV
024
800 V
Insulation voltage
Supply - Dupline
4 kVAC (rms)
Supply - Outputs
4 kVAC (rms)
Dupline
- Outputs
4 kVAC (rms)
Power supply DC types
Installation cat. III (IEC 60664)
Operational voltage
through term. 21 & 22 824
15 to 30 VDC (ripple included)
Ripple
3 V
Reverse-polarity protection
Yes
Current consumption
100 mA
Inrush current
1 A
Transient protection volt.
800 V
Insulation voltage
Supply - Dupline
200 VAC (rms)
Supply - Outputs
4 kVAC (rms)
Dupline
- Outputs
4 kVAC (rms)
Product Description
Ordering Key
Type: Dupline
H4-housing
Receiver
No. of channels
Output type
Power supply
Output Module for Rollerblind Motors
Type G 3430 4249
Up/down control of 2 rollerblind motors
Up/down interlocking for each motor
H4-housing
For mounting on DIN-rail (EN 50022)
LED-indications for supply Dupline
carrier and
motor up/down
AC or DC power supply
Channel coding by GAP 1605
Dupline
output module for
up/down control of two
rollerblind motors. A built-in
up/down interlocking function
protects the motors. Each
motor requires two Dupline
channels, one for "UP" and
one for "DOWN". There is a
Type Selection
Supply
Ordering no.
4 channel
5 A/250 VAC
24 VAC
G 3430 4249 024
115 VAC
G 3430 4249 115
230 VAC
G 3430 4249 230
15 to 30 VDC
G 3430 4249 824
LED indication for "UP" and
"DOWN" for each motor. For
intelligent control of the
rollerblind motors it is
recommended to use the
Master Generator
G38900014230, which has
this function built in.
Output Specifications
Outputs
2 SPST x 2 SPDT relays
Isolated in groups of
2 x 2
Contact ratings (AgCdO)
(micro gap)
Resistive loads
AC 1
5 A/250 VAC (1250 VA)
DC 1
0.25 A/250 VDC (62 W)
or
Inductive loads
AC 15
2.5 A/230 VAC
DC 13
5 A/24 VDC
Mechanical lifetime
30 x 10
6
operations
Electrical lifetime
(at max load)
AC 1
2.0 x 10
5
operations
Operating frequency
7200 operations/h
Insulation voltage
Outputs - Dupline
4 kVAC (rms)
Response time
1 pulse train
G 3430 4249 024
Supply Specifications
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (12.12.00)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
S
1
8
7
6
5
4
3
2
~ ~
21
28
27
26
25
24
23
22
Out
2
Out
1
Power Supply
(+) (-)
O3
O1
O2
O4
G 3430 4249
General Specifications
Output OFF delay
Upon loss of Dupline
carrier
20 ms
Power ON delay
Typ. 2 s
Power OFF delay
1 s
Indication for
Supply ON
LED, green
Output ON
4 LEDs, red
(one per motor or direction)
Dupline
carrier
LED, yellow
Environment
Degree of protection
IP 20 B
Pollution degree
3 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
Material
(see Technical informations)
H4-housing
Weight
300 g
Mode of Operation
As indicated on the wiring
diagram, there are two relays
in series to control each
motor. O1 is used to switch
Motor 1 ON/OFF and O2 is
used to control the direction
of Motor 1 UP/DOWN. Corre-
spondingly O3 (ON/OFF) and
O4 (UP/DOWN) are used to
control Motor 2. In this way, it
is made sure that the motors
are not controlled UP and
DOWN at the same time
(interlocking). O1, O2, O3 and
O4 may be coded individually
by means of the code pro-
grammer GAP 1605. The de-
fault setting of the module is
to switch all outputs off in
case of loss of Dupline
carri-
er signal.
The Master Generator
G38900014 provides intel-
ligent functions that makes it
easy for the user to control
the rollerblind motors individ-
ually or several at the same
time (all UP or all DOWN).
Wiring Diagram
Accessories
DIN-rail
FMD 411
For further information, see "Accessories".
S: Signal wire
Dimensions (mm)
H4-housing