ChipFind - документация

Электронный компонент: G34305545230

Скачать:  PDF   ZIP
Supply Specifications (cont.)
Fail polarity state delay
Upon loss of Dupline
carrier
20 ms
Power ON delay
typ. 2s
Indication for:
Supply ON
LED, Green
Dupline
carrier
LED, Yellow
Output ON
LED, red (one per output)
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
-5 to +50C (+23 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
5 G (11ms)
Vibration
2 G (6 to 55Hz)
Housing
H4-housing
Weight
400 g
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (29.09.2005)
1
Dupline is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description
Ordering Key
Type: Dupline
H4-housing
Receiver
Number of channels
Output type
Power supply
Output Module
Type G 3430 5545
8-channel receiver
Relay load: 16A
Module load: 32A (16 A per relay)
Galvanically separated SPST relay outputs
H4-housing
For mounting on DIN-rail (EN 50022)
LED-indications for supply, Dupline
carrier and outputs
AC power supply
Address coding by GAP 1605
Dupline receiver
designed to
be a part of the Dupline
concept for Building Automa-
tion. SPST relay outputs for
Type Selection
Supply
Ordering no.
24 VAC
G3430 5545 024
115 VAC
G3430 5545 115
230 VAC
G3430 5545 230
control of 8 loads of up to
250 VAC/16 A.
Output Specifications
Outputs
8 SPST relays
Contact ratings (AgSn02)
(micro gap)
Resistive loads
AC1
16 A
Mechanical lifetime
5x10
6
operations
Electrical lifetime
1x10
5
operations/250 V, 12 A
Minimum load
100 mA/12 V
Operating frequency
60 operations/min.
Dielectric voltage
Outputs Dupline
4 kVAC (rms)
Response time
1 pulse train
G 3430 5545 024
Supply Specifications
Power Supply
Overvoltage cat. III
(IEC 60664)
Rated operational voltage
Through term. 21 & 22
230 VAC, +/- 10%
(IEC 60038)
115 VAC, +/- 10% (IEC 60038)
24 VAC, +/- 10%
Frequency
45 to 65 Hz
Rated operational power
Typ. 2,5 VA
Power dissipation
4 W
Rated impulse withstand
voltage
230 4
kV
115 2,5
kV
024 800
V
Dielectric voltage
Supply Dupline
4 kVAC (rms)
Supply Outputs
2 kVAC (rms)
Mode of Operation
8-channel receiver with 8
normally open contact out-
puts. Each output is coded
by means of the code pro-
grammer GAP 1605. For
changing the default setting,
please refer to the datasheet
on GAP 1605.
The outputs are normally
OFF. When a transmitter
coded to the selected chan-
nel is activated, the output
turns ON and remains ON
until the respective channel
becomes deactivated. The
default setting is such that
upon loss of Dupline carrier
all the outputs go OFF.
Note: At delivery some of the
relays might be ON due to
transportation bumps. To be
sure that the relays are OFF,
connect the module to power
and Dupline and transmit on
channels A1-8 once.
Note: Due to the construc-
tion with bistable relays, the
module is intended for heat-
ing and light control only.
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (29.09.2005)
Dupline is a registered trademark. A product of the CARLO GAVAZZI Group
21 22 23 24 25 26 27 28
1 2 3 4 5 6 7 8
5
6
7
8
1
2
3
4
Supply
L1/L2/L3
D+
N
N
L N
L1/L2/L3
D -
Wiring Diagram
Accessories
DIN-rail FMD
411
For further information, see "Accessories".
8 channels G 3430 5545
SPST relay output
G 3430 5545 ...
Operation Diagram
Dupline
carrier
Transmission on channel for output 1
Output 1 (term. 25 & 23)
Transmission on channel for output 2
Power supply
Output 2 (term. 25 & 24)
Default setting (fail polarity): OFF
Dimensions (mm)
H4-housing
Output Specifications, Relay Data
Load
Test conditions
Typical number
of operations
250 V, 12 A, cos
=1
1800/h, 50% DC, +70C
1.0 x 10
5
250 V, 8 A, cos
=1 1800/h, 50% DC, +70C
3.5 x 10
5
250 V, 4 A, cos
=1
1800/h, 50% DC, +70C
5.0 x 10
5
250 V, 3 A, cos
=1
1800/h, 50% DC, +70C
7.5 x 10
5
230 V, 550 W
filament lamps
I
in
40 A
peak
I
off
= 2.5 A
60/h, 8% DC, +22C
2.0 x 10
5
230 V, 1000 W
filament lamps
I
in
71.5 A
peak
I
off
= 4.5 A
60/h, 8% DC, +25C
7.0 x 10
4
230 V, 900 W
fluorescent tubes
(25 x 36 W)
parallel compensated,
30 F
360/h, 50% DC, +25C
1.0 x 10
4
230 V, compressor
I
in
21 A
peak
I
off
=3.5 A
cos
= 0.5
500/h, 20% DC, +25C
1.7 x 10
5
250 V, 8 A, cos
= 0.3
360/h, 50% DC, +25C
1.0 x 10
5