ChipFind - документация

Электронный компонент: G34910000230

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (30.04.03)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description
Ordering Key
Type: Dupline
Type number
Power supply
Fiber Optic Interface
Type G 3491 0000
Dupline
to fibre optics interface
Computer to Dupline
network access
Fibre optic LAN-ring for up to 63 Dupline
systems
Galvanic isolation 4000 VAC
Watchdog output
For mounting on DIN-rail (EN50022)
LED-indications for supply, Dupline
and fail
AC power supply
Dupline
interface for signal
transmission via fibre optics.
For applications in environ-
ments with high noise tran-
sients, for signal transmission
in explosive areas or for con-
nections of up to 63 auto-
nomous Dupline
installations
in a fibre optics LAN.
Supply
Ordering no.
24 VAC
G 3491 0000 024
115 VAC
G 3491 0000 115
230 VAC
G 3491 0000 230
Type Selection
Fibre optics interface
Material
Polymer
Type
Dtep-index
Max. loss
220 dB/km (660 nm)
Typical loss
190 dB/km (660 nm)
Numerical aperture
0.47
Dimensions
2.2 0.1 mm
Cable length
50 m
Connector type
2 sockets
Hewlett Packard types
HFBR-4513 (blue)
HFBR-4503 (black)
Output
1 NPN transistor
Function
Watchdog
Output voltage
35 VDC
Output current
100 mA
Output voltage drop
2 V
Off-state leakage current
100 A
Short-circuit protection
None
Built-in protective diodes
None
Dielectric voltage
Output - Dupline
4 kVAC (rms)
Inductive loads
External noise suppression
required
Settings
Device no.
6 DIP-switches
Baudrate
DIP-switch
Test mode
DIP-switch
Input/Output Specifications
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 230
230 VAC 15% (IEC 60038)
115
115 VAC 15% (IEC 60038)
024
24 VAC 15% (IEC 60038)
Frequency
45 to 65 Hz
Rated operational power
Typ. 3 W
Power dissipation
4 W
Rated impulse withstand
voltage
230
4 kV
115
2.5 kV
024 800
V
Dielectric voltage
Supply-RS232C
4 kVAC (rms)
G 3491 0000 230
Power ON delay
< 200 ms
Indication for
Supply ON
LED, green
Dupline
carrier
LED, yellow
Fail
LED, red
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-20 to +85C (-4 to +185F)
Humidity (non-condensing)
20 to 80% RH
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
Material
(see "Technical Information")
H4-housing
Weight
250 g
General Specifications
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (06.03.03)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3491 0000
Selection of Device No. and Baudrate
Mode of Operation
The Optolink is used for one
of the following 3 purposes:
1. Dupline
LAN-Ring with
Computer Interface
In the majority of applications
the Optolink is used to build
up a local area network of up
to 63 Dupline
systems. With
this a maximum of 8064
Dupline
channels may be
controlled and monitored by a
computer. The LAN-ring is
created through fibre optic
cable with a maximum dis-
tance of 50 m between
Optolinks. The connection to
the computer is established
by means of the interface G
3491 0090. Each Optolink is
set up for a unique device
number between 01 and 63
while the computer is device
number 00. The computer
can read/write data from/to
individual Optolinks by refer-
ring to the device numbers.
For protocol and communica-
tion information please refer
to the data brochure DAT OPL
ENG.
2. Split of a Dupline
System
In case of Dupline
routing
through areas with high elec-
tromagnetic interference or
through potentially explosive
areas the signal transmission
is to be done via fibre optic
cabling. The great advantage
of this is that optical transmis-
sion is totally immune to elec-
trical and magnetic distur-
bance. For this application a
Dupline
system is split into
two systems with one
Optolink each. The connec-
tion be-tween the two sys-
tems is done by fibre optic
cables. Here both Optolinks
must be set up for device
number 00. Establishment of
commu-nication is automatic
and no other adjustments or
soft-ware is required by the
user.
3. Dupline
System Distan-
ceIncrease
If Dupline
is used in very ex-
tensive applications where no
other means of communica-
tion, e.g. telephone line is
available, several Optolinks
may be daisychained.
If, for instance, two Dupline
systems are connected via
Optolink the distance is dou-
bled (2 x 10 km). The proce-
dure and set-up is the same
as under 3 above but it
should be noted that the
reaction time per pair of
Optolinks increases by app.
0.45 s.
Wiring Diagram
Accessories
Optical Plugs
HFBR-4513 (blue)
HFBR-4503 (black)
Fibre Optic Cable, single
Link Fibre-S-X.. (.. = length in m)
Fibre Optic Cable, dual
Link Fibre-D-X.. (.. = length in m)
Data brochure
DAT OPL
1
2
21
22
AC power supply
ON
2
5
2
1
2
3
4
5
6
7
8
The desired device no.,
baudrate and test is set by
means of 8 DIP-switches
at the rear of the housing
SW
ON
OFF
1
Test mode
Normal
2
19200 Baud
9600 Baud
3-8
Device no.
Scope of supply
1 x Optolink
G 3491 0000
20 cm fibre optic cable
Link Fibre-S
2 x Optical plugs
HFBR-4513 (blue)
HFBR-4503 (black)
G3491
0090
Power
Supply
Dupline
63
Dupline
62
Dupline
1
Dupline
2
Power Supply
Power Supply
Power Supply
Power Supply
Optolink
device
no. 63
Optolink
device
no. 62
Optolink
device
no. 1
Optolink
device
no. 2
RS 232
Dupline
LAN-Ring
Watchdog NPN
+ -
s
0.1 A
35 V
4