ChipFind - документация

Электронный компонент: G34960004700

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (05.05.03)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Type: Dupline
H4-Housing
Combined module
Interface type
DC supply
Interface for Omron PLC with the function of a master
Plug and play: Automatic communication with specific
PLC/Controllers
Built-in normal Dupline
Channel Generator
128 I/O's and DC power supply on 3 wires
RS232/RS422/RS485 port for interfacing to control
system
Split-I/O mode selectable (128 inputs and 128 outputs)
LED-indications for supply, Dupline
carrier and Com-
port Tx
Galvanically isolated Com-port supplied by internal
DC/DC converter
Product Description
Ordering Key
G 3496 0004 is designed as a
cost-effective solution for
interfacing Dupline
I/O's to a
Omron PLC. It performs three
functions: Dupline
channel
generator, power supply syn-
chronization (enables 3-wire
system with supply) and
RS232/RS422/RS485 inter-
face.
Type Selection
Supply
PLC Interface Conformance
Ordering no.
20-30 VDC
Omron CPM, CPM1A, CQM, SRM1 & C200
G 3496 0004 700
G 3496 0004 700
Input/Output Specifications
Dupline
Plug & Play Master Module
Interface for Omron
Power output
Output voltage
20-30 VDC (pulsating)
Output current
< 3.0 A @ 50C
Short circuit protection
4 A quick acting fuse
Output voltage drop
< 1.0 V
Dupline
carrier
Output voltage
8.2 V (pulsating)
Current
< 60 mA
Short circuit protection
Yes
Scan time
128 channels
132.2 ms
64 channels
69.8 ms
Communication port
Standard
RS232/RS422/RS485
Split I/O mode
Yes, selectable
Normal Dupline mode
Yes, selectable
Connection
9 pole female Sub-D
Dielectric voltage
Com-port Dupline
1 kVAC (rms)
Protocol
HostLink
Baud rate
9600 (Omron Default)
19200
Data bits
7
Start bit
1
Stop bit
2
Parity
Even
Flow-control
None
Type G 3496 0004
Input/Output Specifications (Cont.)
Pin assignment
2-wire RS 485
S/R Data line + (B)
Pin 3
S/R Data line - (A)
Pin 8
GND
Pin 5
4-wire RS 485/RS 422
R Data line + (B)
Pin 3
R Data line - (A)
Pin 8
S Data line + (B)
Pin 2
S Data line - (A)
Pin 7
Direction
Pin 4
(Connect to GND pin 5
when using 4-wire commu-
nication)
RS 232
TX
Pin 1
RX
Pin 9
GND
Pin 5
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Operational voltage (V
in
)
20-30 VDC
Reverse polarity protection
None
Current consumption
< 150 mA + Power load
Power dissipation
< 5 W
Transient protection voltage
800 V
Dielectric voltage
Supply - Dupline
None
Supply - com-port
1 kVAC (rms)
Power ON delay
2 s
Indication for
Com-port Tx
LED, red
Supply ON
LED, green
Dupline
carrier
LED, yellow
Environment
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (12.01.01)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Mode of Operation
The Dupline
Master Module
(DMM) controls a 3-wire bus
with signal, DC-power and
common GND. The DMM is
connected to a standard DC-
supply, which it synchronizes
with the Dupline
carrier signal
before it is output to supply.
The synchronization is neces-
sary in order to enable the
Dupline
and DC-supply to
share the GND-wire.
The Dupline
Master Module is
a Dupline
Channel Generator
with the function of a master.
This means that the 128
Dupline
I/O's will be read/writ-
ten by the DMM and then sent
to the PLC.
The DMM can run in two dif-
ferent modes Normal mode
and split I/O mode. In Normal
mode, Dupline
operates as a
peer-to-peer system, where
the channel generator auto-
matically establishes a con-
nection between Dupline
inputs and Dupline
outputs
which are coded to the same
Dupline
address. If e.g. an
input coded for B5 is activat-
ed, the output(s) coded for B5
will also be activated.
Consequently, a Dupline
-out-
put can either be activated
through the output-data
received on DMM or by an
active Dupline
input coded
for the same Dupline
-
address. In "Split I/O" mode,
the channel generator treats
the Dupline
inputs and
Dupline
outputs indepen-
dently. If e.g. an input coded
for B5 is activated, the DMM
will make the information avail-
able for the PLC (like in normal
mode), but it will not automati-
cally activate the Dupline
out-
put(s) coded to B5. The
Dupline
outputs are con-
trolled exclusively through the
output data received from the
PLC. In this mode, up to 128
Dupline
inputs and 128
Dupline
outputs are available,
since an input and an output
coded to the same Dupline
address can operate indepen-
dently.
G 3496 0004
General Specifications
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
H4-Housing
Material
(see Technical information)
Weight
100 g
Dip-Switch Setting
Sw.3
On:
19200 baud
Off:
9600 baud (Default Omron setting)
Sw.4
On:
Split I/O Channel Generator Mode
(See "Mode of Operation")
Off:
Normal Dupline
Monostable Channel
Generator Mode
Sw.5
On:
64 Dupline
channels
Off:
128 Dupline
channels
Memory Mapping
Dupline
Omron
Dupline
Omron
Channel
Channel
Read
Write
Read
Write
A1
LR0000
LR0800
E1
LR0200
LR1000
A2
LR0001
LR0801
F1
LR0208
LR1008
A3
LR0002
LR0802
G1
LR0300
LR1100
A4
LR0003
LR0803
H1
LR0308
LR1108
A5
LR0004
LR0804
I1
LR0400
LR1200
A6
LR0005
LR0805
J1
LR0408
LR1208
A7
LR0006
LR0806
K1
LR0500
LR1300
A8
LR0007
LR0807
L1
LR0508
LR1308
B1
LR0008
LR0808
M1
LR0600
LR1400
B8
LR0015
LR0815
N1
LR0608
LR1408
C1
LR0100
LR0900
O1
LR0700
LR1500
D1
LR0108
LR0908
P1
LR0708
LR1508
Table of the memory mapping to the PLC
Wiring Diagram
1
2
3
4
21
22
27
28
Supply in
20-30 V DC
24
23
6
7
8
5
26
25
+
-
Power out
GND
Dupline Signal
RS 232
RS 485
3W
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (12.01.01)
3
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Installation Hints
IMPORTANT
The PLC must be in Monitor-mode. Termination switch on
CIF11 must be in OFF position
TX-LED
Slow flashing
No communication
Check the wiring.
Fast flashing
Communication OK.
No Dupline
Carrier-LED
Dupline
Short curcuit
Short curcuit between the
two Dupline
wires.
Accessories
Through Com. Module
Cable Sub-D 9M/6Wires for Com.
Module with Screw term.
RS-422-OM1
Peripheral Port
Cable Sub-D 9M/SCSI
RS-422-OM2
Additional Information
Scope of supply
1 x Master Module
G3496 0004 700
Pin Assignment
1
9
8
7
6
5
4
3
2
8
6
5
4
3
SDB
RDB
SDA
SG
RDA
+ 5 V
in
(G 2196 0004 only)
7
2
G 2196 0004
G 3496 0004
RS-422-OM1
CIF11
G 3496 0004
1
9
8
7
6
5
4
3
2
OMRON SCSI
plug 20 pol
Pink 1 - Red
Pink 1 - Black
Orange 1 - Red
Orange 1 - Black
Grey 1 - Red
Grey 1 - Black
White 1 - Red
White 1 - Black
Yellow 1 - Red
Pink 2 - Red
Pink 2 - Black
Grey 2 - Red
Grey 2 - Black
White 2 - Red
White 2 - Black
Yellow 2 - Red
RS-422-OM2