Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description
Ordering Key
Type: Dupline
H8-housing
GSM phone
Master channel generator
Supply
Master Channel Generator
Types G 3800 0016, G 3800 1016
Programmable channel generator
Automatic data exchange between multiple networked Master
Generators, allowing systems with up to 4096 I/O points
Option for built-in GSM Modem for monitoring and control
via SMS
User-friendly configuration via Windows 98/2000/NT/XP
software
Real-time, timer and logic functions
Analog set-point control and monitoring
Light and Rollerblind control functions
Alarm Monitoring
Option for Radio controlled clock for high real time accuracy
2 x RS232 ports for configuration and Dupline data read/write
1 x RS485 port for networking of up to 32 Master Generators
Modbus-RTU protocol
Built-in software driver for external radio modem
4 digital inputs / 4 digital outputs on-board
H8-housing for DIN-rail mounting (EN50022)
AC or DC power supply
Programmable channel gene-
rator with built-in dedicated
intelligent functions for light
and roller blind control, alarm
monitoring and analog set-
point control. In addition to
that, there is realtime-, timer-
and logic- functions. Pro-
gramming is easily performed
through Windows-based con-
figuration software. An
optional built-in GSM modem
can be used for monitoring
and control of Dupline signals
via SMS. Up to 32 Master
generators can be networked
as slaves in a RS485 network
using the Modbus protocol.
The unit has 4 digital inputs
and 4 digital outputs on-
board, and it is possible to
create links to other Dupline
networks via external Radio
Modem. The G3800X016 is
different from the G3800X015
in that it has the capability to
perform automatic data
exchange with up to 32 other
G3800X016's in a RS485 net-
work, enabling up to 4096
I/O-points in one system.
Serial Port
RS 232
COM 1
115 kBaud
COM 2
9600 Baud, adjustable
Data format
8 bit
COM 1, COM 2
No parity, 1 stop bit
9-pole female SUB-D
Pin assignment
TxD
Pin 2
RxD
Pin 3
GND
Pin 5
Dielectric voltage
Com.port - Dupline
2 kVAC (rms)
Protocol
Modbus-RTU
RS 485
Termination
Pin 27
When in use,
connect to pin 31
Fs-B
Pin 28
When in use,
connect to pin 30
Fs-A
Pin 29
When in use,
connect to pin 31
+ (B)
Pin 30
- (A)
Pin 31
GND
Pin 32
V+
Pin 33
*)
Protocol
Modbus-RTU
Dupline
Output
Dupline
carrier
Output voltage
8.2 V
Current
< 130 mA
Short-circuit protection
Yes
Input/Output Specifications
G 3800 1016 230
Sequence time
32 channels / 128 channels
38.6 ms / 132.3 ms
Digital outputs
4 PNP transistors
Function
Programmable
Output voltage V
DD
35 VDC
Output current
100 mA
Output voltage drop
2 V
Off-state leakage current
100 A
Short-circuit protection
None
Built-in protective diodes
None
Dielectric voltage
Output - Dupline
4 kVAC (rms)
Output - Input
200 V
Inductive loads
External noise suppression
required
Inputs
Digital
6 - 30 VDC
Voltage
ON > 5.5 V; OFF < 1.5 V
Current
6 mA
Dielectric voltage
Input - Dupline
4 kVAC
GSM Modem
Siemens cellular engine
TC35
Dual Band
EGSM900 and GSM1800
Output power
Class 4 (2 W) EGSM900
Class 1 (1 W) GSM1800
Antenna connector
FME
*)
V+ and GND may be used as supply for digital I/O's, if RS 485 is not used.
Supply
Ordering no.
Ordering no.
w. GSM telephone
115/230 VAC
G 3800 0016 230
G 3800 1016 230
10-30 VDC
G 3800 0016 800
G 3800 1016 800
Type Selection
Inrush current
1 A
Rated impulse withstand volt. 800 V
Dielectric voltage
Supply - Dupline
500 V
Supply - Output
200 V
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (21.08.2006)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3800 0016, G 3800 1016
Real-time clock
Accuracy
Better than 1 minute/month
Internal back-up time
Typ. 48 hours
Power ON delay
< 2.5 s
Indication for
Supply ON
LED, green
ON Line
LED, yellow
COM 1
LED, red
COM 2
LED, red
RS 485
LED, red
GSM
LED, red
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-20 to +85C (-4 to +185F)
Humidity (non-condensing)
20 to 80% RH
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
Material
(see "Technical Information")
H8-housing
Weight
640 g
General Specifications
Wiring Diagrams
RS 485
21
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
29
22
30
23
31
24
32
25
33
26
34
27
35
28
36
G 3800 0016 230
DUPLINE
115V
P
N
N
P
115V
12 VA
+
D
D -
0,1 A
30 V
1
2
3
4
(B)
(A)
V-
V+
V-
V+
V+
1
2
3
4
1
2
3
4
IN
V-
V+
V -
S-in
T
Fs-B Fs-A
6-30 VDC
Supply
Inputs
Outputs
Out
Supply Specifications
Power supply
AC-Types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 24
jumper term. 22 & 23
230 VAC 15% (IEC 60038)
Power on term. 21 & 23
Neutral on term. 22 & 24
115 VAC 15% (IEC 60038)
Frequency
45 to 65 Hz
Rated operational power
Typ. 7 VA/3 W
Power dissipation
G38000016
6 W
G38001016
7 W
Rated impulse withstand
voltage
230 V
4 kV
115 V
2.5 kV
Dielectric voltage
Supply - Dupline
4 kVAC (rms)
Supply - Output
4 kVAC (rms)
Supply - Input
4 kVAC (rms)
Supply - Com. ports
4 kVAC (rms)
Heat dissipation
4 W
Power supply
DC-Types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22
10 to 30 VDC
DC supply
terminal 24 and 25
- 50 Hz for synchronizing
the clock
- in case of voltage break
(AC) the log will automatically
update itself until 10 mSec
before the loss of current
Reverse polarity protection
Yes
Rated operational power
6 W
Power dissipation
G38000016
6 W
G38001016
7 W
Radio Contr.
Clock
6-30 VDC
Inputs
Outputs
Out
Radio Contr.
Clock
RS 485
21
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
29
22
30
23
31
24
32
25
33
26
34
27
35
28
36
G 3800 0016 800
DUPLINE
+
D
D -
1
2
3
4
(B)
(A)
V-
V+
V-
V+
V+
1
2
3
4
1
2
3
4
IN
V-
V+
V -
S-in
+
-
T
Fs-B Fs-A
Supply
10-30 VDC
10-265 VAC
AC monit. input
Supply Specifications (cont.)
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (21.08.2006)
3
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3800 0016, G 3800 1016
Mode of Operation
Intelligent functions
The G3890x016 Master Genera-
tor is a programmable channel
generator which is particularly
well suited for building automa-
tion applications due to the dedi-
cated intelligent functions for
lighting control, rollerblind con-
trol, temperature control and
alarm monitoring. In addition to
that the unit can be configured
to perform real-time, logic and
timer functions. The windows-
based configuration software is
extremely easy to use due to the
pre-programmed functions.
Master Generator configuration
The Master Generator is as
default configured to operate as
a standard channel generator
without intelligent functions. In
order to make use of the intelli-
gent functions the Master Gen-
erator must be configured by
means of the user-friendly win-
dows-based configuration soft-
ware. This is included in the
package and has to be installed
on a Win 95/98/2000/NT/XP PC.
When the configuration is com-
pleted the configuration is down-
loaded into the Master Genera-
tor via COM1 (RS232 port). The
configuration can be saved on a
file and it is also possible to
upload the configuration from a
Master Generator.
GSM Modem Option
The G38001016 Master Genera-
tor has a built-in GSM Modem
which enables monitoring and
control of Dupline signals via
SMS messages to/from mobile
GSM telephones. There are 3
different ways to use SMS mes-
saging:
The Master Generator can be
programmed to send out event-
based SMS messages. The
event can be a channel switch-
ing ON or OFF, or it can be an
analog signal crossing a set-
point.
Requests for status of digital
or analog data can be sent and
answered via SMS messages
Status of digital channels can
be controlled by sending com-
mands via SMS messages
In order to make use of the GSM
modem, the following is required:
A SIM-card with the pin-code
9090 needs to be inserted into
the slot in the front of
G38001016. The SIM-card must
be a 3V type.
A GSM antenna needs to be
connected to the FME connector
on G38001016. If the unit is
installed in a metal enclosure,
the antenna must be installed
outside the enclosure and con-
nected to the Master Generator
via a cable (an antenna of this
type is available as accessory).
An LED in the front of
G38001016 indicates the status
of the GSM modem. By emitting
different blink patterns, the LED
indicates "connecting", "SIM-
card missing", "No network
found", "No response from
modem", "SMS sent" and "SMS
received".
Radio Controlled Clock Option
It is possible to equip the
G3800x016 with an external
antenna for radio-controlled
clock in order to achieve high
timing accuracy in connection
with real-time functions and
event time stamps. When the
antenna ANT2 is used, the
G3800x016 will receive accurate
timing signals from the DCF77
transmitter located in Frankfurt
a.M., Germany. The antenna out-
puts the demodulated signals to
the Master Generator via an
open collector driver.
The DCF77 transmitter covers all
of Central Europe since the
transmission radius is at least
1000 km. For longer distance the
use of ANT2 depends on receiv-
er conditions. ANT2 connects to
the G3800x016 terminals.
RS232 ports
The Master Generator is provid-
ed with two RS232 ports (COM1
and COM2) which both can be
used by PC's/PLC's for
read/write of Dupline data using
the Modbus-RTU protocol.
COM1 is also used for download
and upload of configuration files
(created by the Master Genera-
tor configuration software) and
for firmware upgrades. If the
option for an external radio
modem is desired, it needs to be
connected to COM2. COM1 has
a fixed baudrate of 115 kBaud,
while the baudrate of COM2 is
adjustable.
RS485 port
The RS485 port enables net-
working of up to 32 Master Gene-
rators with or without automatic
data exchange. This enables
control and monitoring of up to
4096 data points. If desired, it is
also possible to use Ethernet
instead of RS485. In that case
each Master Generator must be
equipped with a converter. A
Modbus Device Address needs
to be assigned to each Master
Generator during configuration.
In a network with automatic data
exchange, one Master Generator
is configured as RS485 Master,
and will thus synchronize a con-
tinual automatic data exchange
between all the Master Genera-
tors. When programming the
individual Controllers it is then
possible to make references to
signals in other Dupline net-
works. For example the wind
speed value measured by a sen-
sor in one Dupline network, can
be used in the roller blind control
function in the other Dupline net-
works. It is also possible to
make e.g. "all lights OFF" func-
tions for a big building by acti-
vating a single pushbutton. A PC
or PLC, connected to one of the
COM-ports of the G3800X016
operating as RS485 Master, gets
access to all 4096 data points
using the Modbus protocol.
Also, using the PC makes it pos-
sible to change the configuration
in any of the Master Generators
in the network.
In a network without automatic
data exchange, a PC or PLC
need to be RS485 Master and all
the Master Generators will oper-
ate as Modbus-RTU slaves. This
makes it possible for the PC or
PLC to read/write data from any
of the 32 Master Generators.
See following RS485 networking
diagram for both operating
modes.
Modbus-RTU protocol
Using the Modbus-RTU com-
mands 2 and 3 through COM1,
COM2 or RS485 makes it possi-
ble to read any type of Dupline
data (digital, analink, multiplexed
analog or counter data). The sta-
tus of digital and multiplexed
analog data and reset of counter
can be controlled via the com-
mands 5, 6 and 16. See manual
for memory map information.
Software
The Dupline Data Access soft-
ware package (type no. DUP-
DATACC) has been developed
specifically for the Master Gen-
erator. It contains two software
tools that provide easy access
from a PC to Dupline digital,
analog and counter data via one
of the RS232 or RS485 ports.
The DDE-driver provides a
Dynamic Data Exchange inter-
face, which can be used from
applications that support client
side DDE such as Microsoft
EXCEL. Getting Dupline data
into an EXCEL spreadsheet is a
simple copy-and-paste opera-
tion. The Dupline ActiveX driver
provides an ActiveX interface,
which is a Microsoft standard for
communication between two
products. The Dupline ActiveX
driver can be used from any
development tool that supports
client side ActiveX such as
Microsoft Visual Basic, Delphi
and Borland C++ builder.
The Dupline Data Access pack-
age can be used on single Mas-
ter Generators as well as Master
Generator networks.
Radio Modem driver
The Master Generator has a
built-in driver for control of an
external Radio Modem, which
can be used to create wireless
links where no cable is available
in parts of an installation. One
Master Generator must be
defined as the central MGEN
and up to 32 Master Generators
can be defined as remote
MGEN's. The central MGEN is
continuously polling and updat-
ing the Dupline data from all
remote MGEN's via the radio
modem network, and in this way
it makes the entire system oper-
ate as one big Dupline network.
Apart from increased reaction
time (depending on the number
of remote MGEN's), the system
will operate as if it was one Mas-
ter Generator connected to all
the I/O-modules with cable. The
Master Generator supports the
Radio Modem type 2ASxE and
all 3AS types from the Finnish
manufacturer SATEL (www.satel.fi).
Find below an application dia-
gram for the Radio Modem
option.
Note: Analink modules cannot
be used with Radio Modems.
On-board I/O
The Master Generator has 4 dig-
ital inputs and 4 digital outputs
on-board. These have been
implemented to reduce the cost
of remote stations with only a
few signals (e.g. in connection
with an SMS alarm system or
radio modem remote stations).
The onboard I/O's are used via
the logic functions of the Master
Generator, where they can be
assigned to specific channel
addresses.
Du line
Fieldbus
Installationbus
4
Specifications are subject to change without notice (21.08.2006)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3800 0016, G 3800 1016
Master Generator Network
Dupline #2
Dupline #1
Interface #1
Interface #2
I/O modules
Digital
Analogue
Counter
I/O modules
Digital
Analogue
Counter
Modbus/RS485
PC
Dupline #1
Dupline #32
MGEN Master #32
Modbus/RS485
PC
Modbus/RS232
Dupline #2
MGEN Slave #1
MGEN Slave #2
Without automatic data exchange
With automatic data exchange
Pin Assignment, COM1, COM2
RS 232 Cable
2
3
5
11
9
7
9-pin male
to controller
15-pin female
to radio modem
5
9
1
6
Pin
Signal
2
T x D
3
R x D
5
Signal Ground
2
3
5
2
3
5
9-pin male
to controller
9-pin female
to PC
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (21.08.2006)
5
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Radio Modem Application
Central MGEN
Remote MGEN #2
Remote MGEN #1
RS232
Accessories
Dupline Data Access Software DUPDATACC
GSM Antenna 900 MHz
ANT1
Antenna for
Radio controlled clock
ANT2
1 x Master Channel Generator
G 3800 x016 xxx
1 x User manual
MAN G 3800 0016 ENG
1 x RS 232 cable
RS 232-9 M/9 F
1 x Configuration software
SW G 38xx16
Scope of Supply
ANT1
ANT2
RS232
RS232
G 3800 0016, G 3800 1016
Dimensions (mm)
H8-housing