Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (15.02.05)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description
Ordering Key
Type: Dupline
H8-Housing
Type no.
Supply
Dupline
Field- and Installationbus
Dupline
Lonworks Gateway
Type G 3891 0051
Built-in Dupline
channel generator
Lonworks transmission media: FTT-10A
Baudrate: 78 kbps
SNVT_switch variables for all 128 Digital I/O
SNVT_state_64 variables to read/write 64 Dupline
channels in one variable
SNVT_temp_p and SNVT_lev_percent variables for 112
Analink I/O
Split-I/O mode selectable (128 inputs and 128 outputs)
For mounting on DIN-rail (EN 50 022)
LED indicators for supply, Dupline
carrier and fault
LED indicators for Lonworks: Service, Wink and Module
Status
AC power supply
Dupline
to Lonworks gateway
with built-in channelgenerator.
The module, based on FTT-
10A transmission media,
makes Dupline
digital
and analog inputs directly
available as standard
Lonmark network variables.
Also, it is possible to control
Dupline
digital and analog
signals using network
variables. In total, the
module offers 242 input
variables and 242 output
variables. Several Dupline
gateways can be connected
to the same Lonworks net-
work.
Supply
Ordering no.
115/230 VAC
G 3891 0051 230
Type Selection
Lonworks
Transmission media
FTT-10A
Connector
Plug-in screw terminals
Communication Speed
78 kbps
XIF-file
G38910051.xif
Dielectric voltage
Lonworks Dupline
4 kVAC (rms)
Dupline
Output voltage
8.2 V
Output current
100 mA
Short-circuit protection
Yes
All channels ON detector
Yes
Output impedance
15
Sequence time
132.3 ms (@ 128 channels)
Adjustments
1 x 16 pos. rotary switch
No. of Dupline
channels
8 .. 128 in steps of 8
DIP-switch 1
Dupline
mode (Normal/Split I/O)
DIP-switch 2
Not used
DIP-switch 3
Not used
DIP-switch 4
Not used
CE-marking
Yes
Input/Output Specifications
G 3891 0051 230
Power ON delay
< 2.5 s until start of
Dupline
carrier.
< 40 s until correct reading
of AnaLink values
Indication for
Supply ON
LED, green
Dupline
carrier
LED, yellow
Fault
LED, red
Lonworks Service LED
LED, green
Lonworks Wink LED
LED, red
Module Status
LED, green
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-20 to +85C (-4 to +185F)
Humidity (non-condensing)
20 to 80% RH
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
H8-housing
Material
(see Technical information)
Weight
540 g
General Specifications
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (15.02.05)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3891 0051
Mode of Operation
The G38910051 is a Dupline
to Lonworks gateway with
built-in channelgenerator. The
module, based on FTT-10A
transmission media, makes
Dupline
digital and analink
inputs directly available as
standard Lonmark network
variables. Also, it is possible to
control Dupline
digital and
analink signals using network
variables. In total, the module
offers 242 input variables and
242 output variables. Several
Dupline
gateways can be
connected to the same
Lonworks network.
Dupline Configuration
switches
The unit is equipped with the
following Dupline
configuration
switches. (See also switch
settings)
1x16 position rotary-switch for
selecting Number of Dupline
Channels in the range 8..128 (in
steps of 8). The selected letter
indicates the last channel group
available on Dupline
. If e.g. H
is selected, the 64 channels in
groups A..H will be available.
DIP-switch (1) for selection of
Dupline
Operation Mode. In
"Normal" mode, Dupline
operates as a peer-to-peer
system where the channel
generator automatically estab-
lishes a connection between
Dupline
inputs and Dupline
outputs which are coded to the
same Dupline
address. If e.g.
an input coded for B5 is
activated, the output(s) coded
for B5 will also be activated.
Consequently a Dupline
output
can either be activated through
the corresponding Lonworks
network variable or by an active
Dupline
input coded for the
same Dupline
address. In
"Split I/O" mode, the Dupline
inputs and Dupline
outputs are
created independently by the
channel generator. If e.g. an
input coded for B5 is activated,
the Gateway will propagate the
event via the associated
Lonmark network variable (like
in normal mode), but it will not
automatically activate the
Dupline
output(s) coded to B5.
In "Split I/O" mode, the
Dupline
outputs are controlled
exclusively through the Lonmark
network variables.
DIP-switch (2), DIP-switch (3)
and DIP-switch (4) are not used
in this module.
The Service-pin, located on the
front of the module on the right-
hand side, can be used
during commissioning and
maintenance. When activated,
the G38910051 sends a
Lonworks service message
containing its 48-bit unique ID
on the network. This information
can be used by a network
management tool (e.g.
Lonmaker) to install and
configure the node.
Dupline
Input Data
A part of the Gateway input
processor reads all the 128
Dupline
-channels as Digital
inputs and another part reads
the 112 channels (C1 to P8) as
Analink inputs. Each Dupline
digital input has a Lonmark
network variable of type
SNVT_switch assigned to it.
It is also possible to read
the status of the Dupline
digital input by using the vari-
ables nvo_state_64_AH and
nvo_state_64_IP, which are of
the type SNVT_state_64. Each
of these variables contains the
status of 64 Dupline
channels
(A1-H8, I1-P8) and they are
effective in use when a Lon-
works device needs to read the
status of several Dupline
channels.
There is also a Lonmark
network variable assigned to
each Dupline
analink input in
the range C1-P8. It has been
chosen to make two commonly
used variable types available,
namely SNVT_temp_p (channels
C1-I8) and SNVT_lev_percent
(J1-P8). So temperature
sensors need to be assigned an
address in the range C1-I8, and
analink devices with 0-20 mA,
4-20 mA or 0-10 VDC inputs
must be assigned an address in
the range J1-P8. Also, in order
to achieve the correct scaling
for an Analink temperature
sensor, it is necessary to use
the G89111010 or G86111010,
which both operate in the range
30 to +60 C. See table
"Lonwork network variables for
further information".
Dupline
Output Data
There are 128 network variables
of type SNVT_switch available
for control of the digital status
of each Dupline
channel. It is
also possible to perform the
control by using the network
variables nvi_state_64_AH (cov-
ering A1-H8) or nvi_state_64_IP
(covering I1-P8), which are of
the type SNVT_state_64. These
are effective in use if one Lon-
work node need to control sev-
eral Dupline
channels. If Nor-
mal mode is selected on DIP-
switch (1), the outputs can also
be controlled from Dupline
Wiring Diagrams
Power supply
230 VAC
Power supply
115 VAC
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21, 22, 23 & 24 See wiring diagram
230
230 VAC 15% (IEC 60038)
115
115 VAC 15% (IEC 60038)
Frequency
45 to 65 Hz
Rated operational power
11 VA
Rated impulse withstand
voltage
230
4 kV
115
2.5 kV
Dielectric voltage
Supply - Dupline
4 kVAC (rms)
Supply - RS 485
4 kVAC (rms)
21
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
29
22
30
23
31
24
32
25
33
26
34
27
35
28
36
DUPLINE
SUPPLY
115V
P
N
N
P
115V
SHIELD
GND
SER
VICE
PIN
NET B
NET A
DUPLINE
SETTINGS
1
2 3 4
ON
NO.
CHANNELS
+
D
D
1
2
3
4
LEDS STATUS
SERVICE
BUTTON
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (15.02.05)
3
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3891 0051
transmitters coded for the
same address as the output
(OR-function).
For control of Dupline
analog
outputs, there are 112 network
variables of type SNVT_lev_
percent available, one for each
channel in the range C1-P8). If
e.g. the value 50% is sent to
such a variable, the output of a
4-20mA Dupline
module with
this address will be 12 mA.
Important note:
The Neuron chip ID is printed
on a label on the bottom side of
the module.
Mode of Operation (cont.)
Name
Type
Description
nvo_switch_A1
SNVT_switch
Input status A1
nvo_switch_A2
SNVT_switch
Input status A2
nvo_switch_A3
SNVT_switch
Input status A3
- - - - -
nvo_switch_A8
SNVT_switch
Input status A8
nvo_switch_B1
SNVT_switch
Input status B1
- - - - -
nvo_switch_P7
SNVT_switch
Input status P7
nvo_switch_P8
SNVT_switch
Input status P8
- - - - -
nvo_state_64_AH SNVT_state_64
Input status for all
channel in groups A-H
nvo_state_64_IP SNVT_state_64
Input status for all
channel in groups I-P
Lonworks network variables
Digital input variables
Name
Type
Description
nvi_switch_A1
SNVT_switch
Output control A1
nvi_switch_A2
SNVT_switch
Output control A2
nvi_switch_A3
SNVT_switch
Output control A3
- - - - -
nvi_switch_A8
SNVT_switch
Output control A8
nvi_switch_B1
SNVT_switch
Output control B1
- - - - -
nvi_switch_P7
SNVT_switch
Output control P7
nvi_switch_P8
SNVT_switch
Output control P8
- - - - -
nvi_state_64_AH SNVT_state_64
Output control for all
channel in groups A-H
nvi_state_64_IP
SNVT_state_64
Output control for all
channel in groups I-P
Digital output variables
Name
Type
Description
nvo_temp_p_C1 SNVT_temp_p
Analink Temperature C1
nvo_temp_p_C2 SNVT_temp_p
Analink Temperature C2
nvo_temp_p_C3 SNVT_temp_p
Analink Temperature C3
- - - - -
nvo_temp_p_C8 SNVT_temp_p
Analink Temperature C8
nvo_temp_p_D1 SNVT_temp_p
Analink Temperature D1
- - - - -
nvo_temp_p_I7
SNVT_temp_p
Analink Temperature I7
nvo_temp_p_I8
SNVT_temp_p
Analink Temperature I8
nvo_lev_percent_J1 SNVT_lev_percent
Analink Input Value J1
nvo_lev_percent_J2 SNVT_lev_percent
Analink Input Value J2
- - - - -
nvo_lev_percent_J8 SNVT_lev_percent
Analink Input Value J8
nvo_lev_percent_K1 SNVT_lev_percent
Analink Input Value K1
- - - - -
nvo_lev_percent_P7 SNVT_lev_percent
Analink Input Value P7
nvo_lev_percent_P8 SNVT_lev_percent
Analink Input Value P8
Analog input variables
Name
Type
Description
nvi_lev_percent_C1 SNVT_lev_percent
Analink Output Value C1
nvi_lev_percent_C2 SNVT_lev_percent
Analink Output Value C2
nvi_lev_percent_C3 SNVT_lev_percent
Analink Output Value C3
- - - - -
nvi_lev_percent_C8 SNVT_lev_percent
Analink Output Value C8
nvi_lev_percent_D1 SNVT_lev_percent
Analink Output Value D1
- - - - -
nvi_lev_percent_I7
SNVT_lev_percent
Analink Output Value I7
nvi_lev_percent_I8
SNVT_lev_percent
Analink Output Value I8
nvi_lev_percent_J1 SNVT_lev_percent
Analink Output Value J1
nvi_lev_percent_J2 SNVT_lev_percent
Analink Output Value J2
- - - - -
nvi_lev_percent_J8 SNVT_lev_percent
Analink Output Value J8
nvi_lev_percent_K1 SNVT_lev_percent
Analink Output Value K1
- - - - -
nvi_lev_percent_P7 SNVT_lev_percent
Analink Output Value P7
nvi_lev_percent_P8 SNVT_lev_percent
Analink Output Value P8
Analog output variables
The LON network variables are divided into 17 functionals blocks. There are no control functions built into the functional blocks.
There are 16 blocks with all the variables belonging to a certain Dupline group: Group A, Group B, Group C,.............., Group P
There is 1 block where all Dupline digital inputs and outputs can be accessed effectively through SNVT_state_64 variables: AllDigital
Du line
Fieldbus
Installationbus
4
Specifications are subject to change without notice (15.02.05)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Switch Settings
ON
1 2 3 4
Number of Dupline Channels
A: Group A
8 channels
B: Groups A..B
16 channels
P: Groups A..P
128 channels
1: Dupline Operation Mode
OFF:
Normal (Peer-to-Peer)
ON:
Split I/O mode
2: Not used
3: Not used
4: Not used
G 3891 0051
Lonworks LED Indicators (right hand side of the module)
ON
OFF
Blinking
LED 2
The node is unconfigured
The node is unconfigured
The node has an application but is not yet
and application less
and installed in a network
installed in a network (unconfigured).
LED 3
Normal state
A wink command is received on the Lonworks
LED 4
The module has been
A hardware error has
Software error. Restart the module.
initiated correct and is
occured. (solid red LED)
working ok. (solid green LED)
Dimensions (mm)