ChipFind - документация

Электронный компонент: G88302149230

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (14.01.05)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Power supply AC types
Installations cat. III (IEC 60664)
Rated operational voltage
through wire L & N
230
230 VAC 15% (IEC 60038)
Frequency
45 to 65 Hz
Drop-out tolerance
40 ms
Power consumption
Typ. 3.3 VA
Power dissipation
2 W
Transient protection volt. 230
4 kV
Insulation voltage
Supply - Dupline
4 kVAC (rms)
Supply - Outputs
4 kVAC (rms)
Dupline
- Outputs
4 kVAC (rms)
Product Description
Ordering Key
Type: Dupline
Housing
Receiver
No. of channels
Output type
Power supply
Output Module for Rollerblind Motor
Type G 8830 2149 230
Up/down control of 1 rollerblind motor
Up/down interlocking for motor
AC power supply
Channel coding by GAP 1605
Design for mounting in Euro box
Dupline
output module for
up/down control of one
rollerblind motor. A built-in
up/down interlocking function
protects the motors. The
motor requires two Dupline
channels, one for "UP" and
one for "DOWN". For intelli-
Type Selection
Supply
Ordering no.
2 channel
5 A/250 VAC
230 VAC
G 8830 2149 230
gent control of the rollerblind
motors it is recommended to
use the Master Generator
G3800x01x which has this
function built in.
Output Specifications
Outputs
1 SPST relay & 1 SPDT relay
Resistive loads
AC 1
5 A/250 VAC (1250 VA)
DC 1
0.25 A/250 VDC (62 W)
or
Inductive loads
AC 15
2.5 A/230 VAC
DC 13
5 A/24 VDC
Mechanical lifetime
30 x 10
6
operations
Electrical lifetime
(at max load)
AC 1
2.0 x 10
5
operations
Operating frequency
7200 operations/h
Insulation voltage
Outputs - Dupline
4 kVAC (rms)
Response time
1 pulse train
G 8830 2149 230
Supply Specifications
General Specifications
Output OFF delay
Upon loss of Dupline
carrier
20 ms
Power ON delay
Typ. 2 s
Power OFF delay
1 s
Environment
Pollution degree
3 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions (h x w x d)
50 x 50 x 30
Material
ABS
Weight
100 g
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (14.01.05)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
D+
D-
Supply
L N
Brown Blue
White
Black
O1
O2
Brown
Orange
Red
N
L
M
1
G 8830 2149 230
Mode of Operation
As indicated on the wiring
diagram, there are two relays
in series to control the motor.
O1 is used to switch the
Motor ON/OFF and O2 is
used to control the direction
of the Motor UP/DOWN. In
this way, it is made sure that
the motors are not controlled
UP and DOWN at the same
time (interlocking). O1 and O2
may be coded individually by
means of the code pro-
grammer GAP 1605. The de-
fault setting of the module is
to switch all outputs off in
case of loss of Dupline
carrier signal.
The Master Generator
G380X01X provides intelligent
functions that makes it easy
for the user to control the
rollerblind motors individually
or several at the same time
(all UP or all DOWN).
Wiring Diagram
Accessories
Programming cable to GAP 1650
GAP-TPH-CAB
Dimensions (mm)
50
50
30
Wiring Connections
Bus:
White =
Dupline signal, D+
Black =
Dupline signal, D-
Supply:
Brown =
L
Blue =
N
Output:
Brown =
O1, Motor on/off
Orange =
O2, Motor up/down
Red =
O2, Motor up/down
Bus wires:
2 x 0,75 mm
2
250V isolation, single core, 150 mm
Supply, Output:
5 x 1,5 mm
2
250V isolation, single core, 150 mm
Dot
Programming Cable
GAP-TPH-CAB