ChipFind - документация

Электронный компонент: G89102217

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (29.08.03)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Type: Dupline
Type
Smoke detector operating according to the Tyndall
effect
Detection of smoke-developing smouldering and
flaming fires
Without radioactive sources
Detection area up to 60 m
2
Transmission of alarms and life signal via Dupline
Operating voltage supplied by Dupline bus
Product Description
Ordering Key
Smoke detector G8910 2217
allows early detection of
smoke-developing smoulder-
ing and flaming fires. The
smoke detector operates on
the proven principle of light
scattering. The sensing
chamber contains a light
source and a light sensor
positioned so that light only
hits the sensor when airborne
particles enter the chamber
(Tyndall effect), thereby gen-
erating the electric signal.
This design eliminates the
need for a radioactive source.
G8910 2217 only requires to
be connected to Dupline. All
signals, ie smoke alarm, sta-
tus signal - indicating correct
connection between the
smoke detector and the built-
in Dupline circuit board - as
well as signal indication of
successful self-testing are
transmitted via the Dupline
bus.
G89102217 features LED
indication of alarm and oper-
ational state of the detector. A
test button allows manual
testing of the alarm function,
while simultaneously an alarm
is transmitted via the Dupline
bus.
Type Selection
Supply
Ordering no.
Supplied by Dupline
G 8910 2217
G 8910 2217
Supply Specifications
Smoke Detector
Supply
Supplied by Dupline
Rated operational current
0.2 mA
Type G8910 2217
General Specifications
Channel programming
By GAP 1605 and special
cable GAP-TPH-CAB
Channel assignment
I/O number 1
Alarm signal (active on
alarm)
I/O number 2
Status signal (active when
Dupline signal wires and
smoke detector are
connected: Every 50 sec.
This channel is active for
one cycle)
Indication
Red LED (short flash once
every 50 sec. (life signal):
Smoke detector is OK.
Short flash every 0.6 sec.:
Fire alarm)
Input Specifications
Detector
Optical (Tyndall effect)
Response level
Acc. to EN 12239 (95)
General Specifications (cont.)
Environment
Degree of protection
IP 42
Operating temperature
5 to 40C (41 to 104F)
Storage temperature
-50 to 85C (-58 to 185F)
Connection
Screw terminals.
Wire diameter 0.4 - 1.5 mm
See wiring layout
Housing
For installation on ceilings.
Dimensions
80 x 80 mm
Material
Polycarbonate
Colour
White
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (29.08.03)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 8910 2217
Dimensions
80
60
4
80
40
Wiring Layout
Position of the
PCB (A) in G8910
2217: The Dupline
signal wire is led
through the hold-
ing device (E) and
fastened at the
screw terminals
(B). Subsequently,
the PCB is fitted in
the G8910 2217
so that the con-
tacts (C) lead into
the holes.
Notes on Applications
To achieve minimum protec-
tion, a G8910 2217 should be
installed in each sleeping area
and/or on each floor. A smoke
detector installed in each
room will ensure higher pro-
tection (except in the kitchen
and bathroom, where steam
may cause false alarms).
The following guidelines must
be observed when using
G8910 2217:
The floor area and floor-to-
ceiling height in rooms must
not exceed 60 m
2
and 6 m
respectively.
The width and length of hall-
ways and narrow corridors
must not exceed 3 m and
15 m respectively.
The smoke detector should
be mounted as close as
possible to the centre of the
room.
A gap of at least 0.5 m from
walls and furniture must be
observed.
The G8910 2217 must NOT
be mounted at the following
locations:
Near to ventilation ducts or
strong draughts.
Directly in the apex of
pitched roofs (a minimum
distance of 30 cm from the
apex must be observed).
In rooms where - under nor-
mal conditions - a lot of
steam, dust or smoke is
present (for example in
workshops, bathrooms and
laundry rooms).
Address coding of
the PCB (A) with
hand encoder
cable GAP-TPH-
CAB and connec-
tion of the Dup-
line signal wires
at the screw ter-
minal (B).
Programming cable
to GAP 1605
GAP-TPH-CAB
Accessories