ChipFind - документация

Электронный компонент: RJT3A60D25

Скачать:  PDF   ZIP
Specifications are subject to change without notice (12.05.2006)
1
3 in 1 semiconductor contactor
Three control inputs - three independently switched
poles
Direct copper bonding (DCB) technology
LED indication for each pole
Housing free of moulding mass
Input range: 4 32 VDC
Operational ratings: up to 3x25AAC, 600VAC
Non-repetitive peak voltage: up to 1200V
p
Opto-isolation > 4000 VAC
rms
Product Description
Ordering Key
This product is designed in
such a way as to replace elec-
tro-mechanical contactors,
especially when switching is
frequent. It has an integrated
heatsink and over-voltage pro-
tection. The heatsink is
moved to the back for optimal
space saving in the panel and
easy wire mounting at the front
of the relay.
The relay with antiparallel
thyristor output can be used
for resistive and inductive
loads.
RJT3A comes with 3 indepen-
dently controlled poles, with
three LEDs to indicate status
of each control input.
Each zero switching relay
switches ON when the sinu-
soidal curve crosses zero and
switches OFF when the cur-
rent crosses zero.
Solid state relay
Three-in-one (Trio)
Number of switching poles
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Solid State Relays
3 Independently Switched Poles
Integrated heatsink
Type RJT3A - Trio
Type selection
Switching mode
Rated operational voltage
Control voltage
Rated operational current
A: Zero switching
23: 230 VACrms
D:
4
- 32 VDC
20: 3 x 20 AAC
rms
(MIDI)
60: 600 VACrms
25: 3 x 25 AAC
rms
(POWER)
Rated operational
Control voltage
Rated operational current
voltage
3 x 20 (MIDI)
3 x 25 (POWER)
230 VACrms
4-32VDC
RJT3A23D20
RJT3A23D25
600 VACrms
4-32VDC
RJT3A60D20
RJT3A60D25
Selection Guide
RJ T 3 A 60 D 25
MIDI
POWER
General Specifications
RJT3A23...
RJT3A60...
Operational voltage range
24 - 280 VAC
48 - 660 VAC
Non-rep. peak voltage
650 V
p
1200 V
p
Operational frequency range
45 - 65 Hz
45 - 65 Hz
Power factor
0.5 @ 230 VACrms
0.5 @ 600 VACrms
Approvals
UL, cUL
UL, cUL
CE-marking
Yes
Yes
Pollution degree
2
2
2
Specifications are subject to change without notice (12.07.2006)
RJT3A
Input Specifications
Control voltage range
4 - 32 VDC
Pick-up voltage
3.8 VDC
Reverse voltage
32 VDC
Drop-out voltage
1 VDC
Maximum input current
12 mA
Response time pick-up
<1 cycle
Response time drop-out
<1 cycle
Output Specifications
RJT3A...20 (MIDI)
RJT3A...25 (POWER)
Rated operational current
AC51
@Ta=25C
3 x 20 A
3 x 25 A
AC53a @Ta=25C
3 x 15 A
3 x 15 A
Min. opertional current
150 mA
150 mA
Rep. overload current t=1s
<125 A
<125 A
Non rep. surge current
Tj(init.)= 25C and t=10ms
580 Apk
580 Apk
Off-state leakage current @ rated voltage & frequency
< 3 mA
< 3 mA
I
2
t for fusing (t = 10 ms)
1680 A
2
s
1680 A
2
s
Critical dI/dt
50 A/s
50 A/s
On-state voltage drop @ rated current
1.6 Vrms
1.6 Vrms
Critical dV/dt off-state
500 V/s
500 V/s
Operating Temperature
-30 to +70C (-22 to + 158F)
Storage temperature
-40 to +80C (-40 to +170F)
Weight
MIDI
Approx. 380 g
POWER
Approx. 680 g
Housing material
PBT, Flame retardant
Conductors
Size
0.5...4.0 mm
2
(AWG 20...12)
2 x 0.5...2.5 mm
2
(2 x AWG 20...14)
Tightening torque max.
0.6 Nm with Posidrive 0 bit
Terminal screws
M3
Insulation
Thermal Specifications
Rated insulation voltage
Input to output
4000 VACrms
Output to case
4000 VACrms
Housing Specifications
All dimensions in mm
All dimensions in mm
1
0
2
.
5
Dimensions
RJT3A..25
MIDI
POWER
RJT3A..20
Specifications are subject to change without notice (12.05.2006)
3
* Note: dotted line indicates UL rating for RJT3..20
Connection Examples
4-32VDC
A2
3
L2
5
L3
A1
1
L1
4
T2
6
T3
2
T1
A4
0V
LOAD
A2
3
L2
5
L3
A1
1
L1
4
T2
6
T3
2
T1
A4
0V
LOAD
4-32VDC
4-32VDC
A3
A3
L1 L2 L3
1-Phase Loads
3-Phase Loads
L1 L2 L3
4-32VDC
RJT3A60D25
Derating Curve
(100% duty on 3 Poles)
Dissipation Curve
(100% duty on 3 Poles)
T
o
tal Power dissipation (W)
Surrounding temperature (C)
RJT3..25
RJT3..20
Load Current per phase (A)
0 5 10 15 20 25
20 25 30 35 40 45 50 55 60 65 70
RJT3..20
RJT3..25
100
80
60
40
20
0
Terminal Layout
Load Curr
ent per phase (A)
26
24
22
20
18
16
14
12
10
8
6
Application of DC voltage across ter-
minals A1-A4 will activate pole L1-
T1. The top green LED indicates the
status of the control input across ter-
minals A1-A4.
Application of DC voltage across ter-
minals A2-A4 will activate pole L2-
T2. The middle green LED indicates
the status of the input voltage across
terminals A2-A4.
Application of DC voltage across A3-
A4 will activate pole L3-T3. The bot-
tom green LED indicates the status
of the input voltage across terminals
A3-A4.
For 3-Phase control, A1, A2 and A3
can be connected together to switch
all three poles simultaneously.
4
Specifications are subject to change without notice (12.07.2006)
RJT3A
Derating vs. Spacing Curves
RJT3...20
RJT3...25
Surrounding Temp. (C)
Note: Assuming 100% duty on 3 poles
Load Curr
ent per Phase (A)
Surrounding Temp. ( C)
22.5mm
10.0mm
6.0mm
3.0mm
0.0mm
22.5mm
10.0mm
6.0mm
3.0mm
0.0mm
Load Curr
ent per Phase (A)