ChipFind - документация

Электронный компонент: S102166924

Скачать:  PDF   ZIP
Specifications are subject to change without notice (19.11.99)
1
Plug
Output
Time range
Supply:
24 VAC/DC & 115-230 VAC
Circular
DPDT
0.1 s - 10 h
S 102 166 924
Timers
Time ranges: 0.1 s to 10 h
2 contact functions: - DPDT delay on operate
- One instantaneous, one delayed
Easy time and function setting
Knob-adjustable time setting
Automatic start functions
Repeatability:
0.2%
Output: 2 x 5 A SPDT relay
Plug-in module, S-housing
LED-indication for relay and power supply ON
24 VAC/DC and 115 to 230 VAC power supply
Cadmium-free contacts
Timer in accordance with IEC 61812-1
Product Description
Multi-voltage delay on opera-
te timer with 6 selectable time
ranges from 0.1 s up to 10 h
for standard 11-pin circular
sockets. Can be configured
with one instantaneous out-
put contact, which can be
used in applications where an
output is desired immediately
when power supply is applied.
Ordering Key
Housing
Type/function
Output
Power supply
Type Selection
Time Specifications
Time ranges
Selectable by DIP-switch
0.1 - 1 s
1 - 10 s
0.1 - 1 m
1 - 10 m
0.1 - 1
h
1 - 10
h
Setting accuracy
5%
Repeatability
0.2%
Time variation
Within rated power supply
0.05%/V
and ambient temperature
0.2%/C
Reset
Power supply interruption
200 ms
Output Specifications
Output
2 x SPDT relay
Rated insulation voltage
250 VAC (rms) (cont./elect.)
Contact ratings (AgNi)
(micro gap)
(IEC 60947-5-1/IEC 60337)
Resistive loads
AC 1
5 A/250 VAC
DC 1
5 A/24 VDC
Small inductive loads AC 15
5 A/250 VAC
DC 13
2 A/24 VDC
Mechanical life
30 x 10
6
operations
Electrical life
AC 1
10
5
operations
(at max. load)
Operating frequency
7200 operations/h
Insulation voltage
Rated insulation voltage
2.0 kVAC (rms) (cont./elect.)
Rated impulse withstand volt. 4 kV (1.2/50 s) (cont./elect.)
(IEC 60664)
Delay on Operate
Type S 102
S 102 166 924
Supply Specifications
Power supply AC connection Overvoltage cat. III (IEC 60664)
Rated operational voltage
Through pins 2 & 10
115-230 VAC, -15 to +15%
50/60 Hz, -5/+5 Hz
or pins 2 & 6
24 VAC, -15 to +15%
50/60 Hz, -5/+5 Hz
Voltage interruption
40 ms
Rated insulation voltage
None
Rated impulse withstand volt. 4 kV (1.2/50 s) (pin 2 & 10)
Power supply DC connection Overvoltage cat. III (IEC 60664)
Rated operational voltage
Through pins 2 & 6
924
24 VDC, -15 to +15%
(pin 2 positive)
Voltage interruption
40 ms
Rated insulation voltage
None
Rated impulse withstand volt. 1 kV (1.2/50 s) (pin 2 & 6)
Rated operational current
AC supply
75 mA @ 230 VAC
40 mA @ 115 VAC
55 mA @ 24 VAC
DC supply
35 mA @ 24 VDC
2
Specifications are subject to change without notice (19.11.99)
Operation Diagram
S 102
Mode of Operation
Contact function 1
DPDT delay on operate
The delay period begins when
power supply is applied. At
the end of the set delay, both
relay contacts will operate and
will not release until power
supply is interrupted. If power
supply is interrupted for at
least 200 ms before the relay
operates, the time circuit is
reset to zero and the relay is
ready for a new time period.
Contact function 2
One instantaneous,
one delayed
Relay contact 2 operates
instantaneously when power
supply is applied. After expi-
ration of the set delay, relay
contact 1 operates.
Both contacts remain in ON-
position until power supply is
interrupted. After 200 ms the
time relay is ready for renew-
ed start.
Wiring Diagram
Accessories
Socket
S 411
Hold down spring
HF
Mounting rack
SM 13
Socket cover
BB 4
General Specifications
Power ON delay
200 ms
Power OFF delay
200 ms
Indication for
Power supply ON
LED, green
(flashing during time delay)
Timer output ON
LED, yellow
Environment
Degree of protection
IP 20
Pollution degree
2 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
100 g
Approvals
UL, CSA
CE-marking
Yes
EMC
Electromagnetic
Compatibility
Immunity
Acc. to EN 50082-2
Emission
Acc. to EN 50081-1
Timer specifications
Acc. to IEC 61812-1
Contact 1 (15, 16, 18)
Contact 2 (25, 26, 28)
15
A1
N
115-230V
24V (-)
16
26
18
28
3
9
1
11
6
4
8
2
25
A2
A3
115-230V
L
24V (+)
10
Functions selectable by DIP-switch
Power supply
Contact function 1
Contact function 2
T
T
T
Function and Time Setting
DIP-switch selector
x 1
sec.
min.
hrs.
x 0.1
A
B
A
B
A
B
Shown example:
min. x 0.1, function 2
ON OFF