Plug
Output
Time range
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
Supply: 24 VDC
Circular
SPDT
0.15 s-220 h
S 1201 156 024
S 1201 156 115
S 1201 156 230
S 1201 156 724
DPDT
0.15 s-220 h
S 1201 166 024
S 1201 166 115
S 1201 166 230
S 1201 166 724
Timers
Multi-function, plug-in time
relays with 20 selectable time
ranges up to 220 h and 4
selectable modes of opera-
tion. Available in various volt-
ages to cover applications
monitored by power supply.
Time ranges
0.15 s -
1.5 s
Selectable by DIP-switch
0.3 s
-
3 s
0.6 s
-
6 s
1.2 s
- 12 s
2.5 s
- 25 s
5 s
- 50 s
10 s
- 100 s
20 s
- 200 s
40 s
- 400 s
1.3 m
- 13 m
2.6 m
- 26 m
5 m
- 50 m
10 m
- 100 m
20 m
- 200 m
40 m
- 400 m
1.4 h
- 14 h
2.8 h
- 28 h
5.5 h
- 55 h
11 h
- 110 h
22 h
- 220 h
Time range accuracy
0 to +10% on max.
min. actual time
set time
Repeatability deviation
1%
Time variation
Within rated power supply
0.05%/V
and ambient temperature
0.2%/C
Reset
Power supply interruption min.
Time and/or relay
200 ms
Housing
Type/function
Output
Power supply
4 selectable functions:
- Delay on operate
- Interval timer
- Symmetrical recycler
(ON- or OFF-time first)
20 selectable time ranges: 0.15 s to 220 h
Automatic start
Knob-adjustable time within range
Oscillator-controlled time circuit
Repeatability deviation:
1%
Output: 10 A SPDT or 8 A DPDT relay
Plug-in type module
S-housing
LED-indication for relay and power supply on
AC or DC power supply
Multi-function
Type S 1201
Power supply AC types
Installation cat. III (IEC 60664)
Rated operational voltage
through pins 2 & 10
230
230 VAC 15%, 45 to 65 Hz
115
115 VAC 15%, 45 to 65 Hz
024
24 VAC 15%, 45 to 65 Hz
Dropout tolerance
40 ms
Rated insulation voltage
2.0 kVAC (rms)
(supply/elec.)
Rated transient protection volt.
4 kV (1.2/50 s)
(line/neutral)
Power supply DC type
Installation cat. III (IEC 60664)
Rated operational voltage 724
24 VDC 15% (pin 2 pos.)
Rated insulation voltage
None
Rated transient protection volt.
4 kV (1.2/50 s)
Consumption
AC supply
2.5 VA
DC supply
1.5 W
Product Description
Ordering Key
Type Selection
Time Specifications
Supply Specifications
S 1201 156 024
2
Specifications are subject to change without notice (07.01.00)
Sockets
S 411
Hold down spring
HF
Mounting rack
SM 13
Socket covers
BB 4
Front mounting bezel
FRS2
Potentiometer lock
PL 3
For further information refer to "Accessories".
For other AC/DC voltages refer to "General Information".
S 1201
Delay on operate
The time period starts when
power supply is applied. At the
end of the set time period, the
relay operates and does not
release until power supply is
interrupted for at least 200 ms.
Interval timer
The relay operates and the
time period starts when power
supply is applied. At the end
of the set time period, the relay
releases. Operation starts a-
gain when reapplying power
supply after an interruption of
at least 200 ms.
Symmetrical recycler
ON-time period first
When power supply is applied
the relay operates and the
time period starts. At the end
of the first set time period, the
relay releases. At the end of
the second set time period (of
the same duration as the first),
the relay operates again.
This sequence continues with
equal long ON- and OFF-time
periods until power supply is
interrupted.
Symmetrical recycler
OFF-time period first
The time period starts when
power supply is applied. At the
end of the first set time period,
the relay operates. At the end
of the second set time period
(of the same duration as the
first), the relay releases.
This sequence continues with
equal long OFF- and ON-time
periods until power supply is
interrupted.
S 1201 156
S 1201 166
Output
SPDT relay
DPDT relay
Basic electrical insulation
250 VAC (rms) (contact/electronics)
250 VAC (rms) (contacts/elec., contact/contact)
Contact ratings (AgCdO)
(micro gap)
(micro gap)
Resistive loads
AC 1
10 A/250 VAC (2500 VA)
8 A/250 VAC (2000 VA)
DC 1
1 A/250 VDC (250 W)
0.4 A/250 VDC (100 W)
or
10 A/25 VDC (250 W)
4 A/25 VDC (100 W)
Small inductive loads
AC 15 2.5 A/230 VAC
2.5 A/230 VAC
DC 13 5 A/24 VDC
5 A/24 VDC
Mechanical life
30 x 10
6
operations
30 x 10
6
operations
Electrical life
AC 1
2.5 x 10
5
operations (at max. load)
2.5 x 10
5
operations (at max. load)
Operating frequency
7200 operations/h
7200 operations/h
Insulation voltages
Rated insulation voltage
2.0 kVAC (rms) (contact/electronics)
2.0 kVAC (rms) (contact/electronics)
Rated transient protection volt.
4 kV (1.2/50 s) (contact/electronics) (IEC 60664)
4 kV (1.2/50 s) (contact/electronics) (IEC 60664)
Output Specifications
General Specifications
Wiring Diagram
Power supply
S 1201 156, S 1201 166
Accessories
Mode of Operation
Power ON delay
200 ms
Power OFF delay
200 ms
Indication for
Power supply ON
LED, green
Output ON
LED, red
Environment
Degree protection
IP 20 B
Pollution degree
2 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
AC types/DC types
200 g/125 g
Approvals
UL, CSA
CE-marking
Yes
Specifications are subject to change without notice (07.01.00)
3
2.6 m - 26 m
5 m
- 50 m
10 m - 100 m
20 m - 200 m
40 m - 400 m
1.4 h - 14 h
2.8 h - 28 h
5.5 h - 55 h
11 h
- 110 h
22 h
- 220 h
Selection of function
DIP-switch selector (1 & 2)
1. Delay on operate
2. Interval timer
3. Recycler,
ON-time period first
4. Recycler,
OFF-time period first
S 1201
1
2
Function/Time Setting
Operation Diagram
Power supply
1. Relay on
2. Relay on
3. Relay on
4. Relay on
Time setting
Knob-adjustable on scale in
per cent of max. time.
DIP-switches for selecting
function and time are placed
behind a small removable
front plate on the time relay.
Selection of time range
DIP-switch selector (3 - 7).
3 4 5 6 7
0.15 s- 1.5 s
0.3 s - 3 s
0.6 s - 6 s
1.2 s - 12 s
2.5 s - 25 s
5 s
- 50 s
10 s
- 100 s
20 s
- 200 s
40 s
- 400 s
1.3 m- 13 m