ChipFind - документация

Электронный компонент: S1321166724

Скачать:  PDF   ZIP
Specifications are subject to change without notice (25.10.99)
1
Output
DPDT relay
Basic electrical insulation
250 VAC (rms)
(contacts/elec., contact/contact)
Contact ratings (Ag-CdO)
(micro gap)
Resistive loads
AC 1
8 A/250 VAC (2000 VA)
DC 1
0.4 A/250 VDC (100 W)
or
4 A/25 VDC (100 W)
Small inductive loads AC 15
2.5 A/230 VAC
DC 13
5 A/24 VDC
Mechanical life
30 x 10
6
operations
Electrical life
(at max. load)
AC 1
2.5 x 10
5
operations
Operating frequency
7200 operations/h
Insulation voltages
Rated insulation voltage
2.0 kVAC (rms)
(cont./elec.)
Rated transient protection volt. 4 kV (1.2/50 s) (cont./elec.)
(IEC 60664)
Time ranges
10 ms - 999 h
Repeatability deviation
0.1%
Time variation
Within rated ambient temp.
0.004%/C
Reset
Time and/or relay
Intercon. pins 5 & 7,
pin 5 pos., 12 VDC, 6 mA
Pulse duration
10 ms
Power supply interruption
Min. 200 ms (not in functions
with memory)
Sensor supply output
12 VDC, 10 mA
intercon. pins 6 & 7,
pin 6 pos.
Note: pins 6 & 7 must not
be short-circuited
Plug
Output
Time range
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
Supply: 24 VDC
Circular
DPDT
10 ms - 999 h
S 1321 166 024
S 1321 166 115
S 1321 166 230
S 1321 166 724
Housing
Type/function
Output
Power supply
Timers
Programmable Quartz Timer, Multi-function
Type S 1321
Programmable, plug-in, micro-
processor-based multi-function
time relay with 22 selectable
modes of operation and time
range from 10 ms to 999 h.
Function and time settings
easily read on built-in LED-
display. Applicable for most
functions where a timer is
needed. Controlled by contact,
open collector output, sensor
or power supply.
Programmable microprocessor-based
quartz timer with 3-digit 7-segment display
22 functionswithin delay on operate, interval timer,
pulse continuity, symmetrical recycler, asymmetrical
recycler
Time ranges: 10 ms to 999 hrs
Repeatability deviation:
0.1%
Built-in memory
Direct connection for NPN sensor
Output 8 A DPDT relay
Plug-in type module
S -housing
LED-indication for relay and power supply on
AC or DC power supply
Product Description
Ordering Key
Type Selection
Output Specifications
Time Specifications
S 1321 166 024
2
Specifications are subject to change without notice (25.10.99)
Power supply AC types
Installation cat. III (IEC 60664)
Rated operational voltage
through pins 2 & 10
230
230 VAC 15%, 45 to 65 Hz
115
115 VAC 15%, 45 to 65 Hz
024
24 VAC 15%, 45 to 65 Hz
Drop-out tolerance
40 ms
Rated insulation voltage
2.0 kVAC (rms)
Rated transient protection volt. 4 kV (1.2/50 s) (line/neutral)
Power supply DC type
Installation cat. III (IEC 60664)
Rated operational voltage 724
24 VDC 15% (pin 2/A1 pos.)
Rated insulation voltage
None
Rated transient protection volt. 800 V (1.2/50 s)
Consumption
AC supply
4 VA
DC supply
3 W
S 1321
Function 1: Delay on ope-
rate, aut. start, no restart, no
time reset.
Function 2: Delay on ope-
rate, aut. start, no restart,
man. time reset.
Function 3: Delay on ope-
rate, aut. start, man. restart,
no time reset.
Function 4: Delay on ope-
rate, aut. start , man. restart,
man. time reset.
Function 5: Delay on ope-
rate, man. start, man.
restart, no time reset.
Function 6: Delay on ope-
rate, man. start, man.
restart, man. time reset.
Function 7: Delay on ope-
rate, man. start, man. restart,
no time reset, memory.
Function 8: Delay on ope-
rate, man. start, man. restart,
man. time reset, memory.
Function 9: Interval timer,
aut. start, no restart, no time
reset.
Function 10: Interval timer,
aut. start, no restart, man.
time reset.
Function 11: Interval timer,
aut. start, man. restart, no
time reset.
Function 12: Interval timer,
aut. start, man. restart, man.
time reset.
Function 13: Interval timer,
man. start, man. restart, no
time reset.
Function 14: Interval timer,
man. start, man. restart,
man. time reset.
Function 15: Interval timer,
man. start, man. restart, no
time reset, memory.
Function 16: Interval timer,
man. start, man. restart,
man. time reset, memory.
Function 17: Pulse continu-
ity, aut. start, man. restart,
man. time reset.
Function 18: Pulse continu-
ity, man. start, man. restart,
man. time reset.
Function 19:
Symmetrical/asymmetrical
recycler, aut. start, OFF-time
first.
Funtion 20:
Symmetrical/asymmetrical
recycler, aut. start, ON-time
first.
Function 21:
Symmetrical/asymmetrical
recycler, aut. start, OFF-time
first, memory.
Function 22:
Symmetrical/asymmetrical
recycler, aut. start, ON-time
first, memory.
Note: In function 00 the
timer is on standby.
Supply Specifications
General Specifications
Mode of Operation
Power ON delay
< 200 ms
Power OFF delay
min. 200 ms
Indication for
Power supply ON
LED, green
Output ON
LED, yellow
Environment
Degree of protection
IP 20 B
Pollution degree
2 (IEC 60664)
Operating temperature
-20 to +50C (-4 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
AC supply
200 g
DC supply
125 g
Approvals
UL, CSA
Display
LEDs: 3-digit, 7-segment
indicates remaining time
Height of digits
7 mm
Memory
Selected time and function
are stored in RAM module
approx. 10 years
Accuracy
0.02%
Specifications are subject to change without notice (25.10.99)
3
Power supply
S 1321 166
S 1321
Wiring Diagrams
Power supply
S 1321 166
Power supply
S 1321 166
Contact
Open collector
Sensor
3-wire
NPN
sensor
Programming of function
and/or time range
Press FUNC and TIME but-
tons simultaneously for
approx. 3 s. When display
shows "- - -" release switches
and press immediately FUNC
or TIME respectively for pro-
gramming function number
and/or time.
Programming of function
In programming mode, press
TIME to increment right flas-
hing digit. Press FUNC to pro-
ceed to next digit and TIME to
increment it, etc. Press FUNC
to end programming se-
quence. If a higher number
than 22 is selected for functi-
on, the display show "Err".
After approx. 3 s the display
returns to the last selected
function and a new function
number can be selected.
Programming of time
In time programming mode,
press TIME to increment first
flashing digit. Press FUNC to
go to next digit. Press TIME
again to increment this digit,
etc.
To select decimal point, press
FUNC and TIME to change
position (xxx. or xx.x or x.xx).
To select time range, press
FUNC and press TIME to
change position of time range
indicator on the display (S for
seconds, M for minutes, H for
hours). Press FUNC to accept.
If a recycler function has been
selected, press FUNC to set
second time value after the
same criteria as above.
Finally, press FUNC to end
programming sequence.
Status of time/function
During operation the selected
function and time values may
be read without disturbing the
operation.
Status of selected function
Press FUNC. The display
shows function number.
When the button is released,
the display returns to current
time value.
Status of selected time
Press TIME. The display
shows selected time value.
For recyclers press TIME
twice to read second time
range. When the button is re-
leased, the display shows
selected time range for
approx. 3 s before returning
to current time value.
Sockets
S 411
Hold down spring
HF
Mounting rack
SM13
Socket covers
BB 4
Front mounting bezel
FRS 2
All 3-wire sensor types with NPN open collector output.
For further information refer to "Accessories".
For other AC/DC voltages refer to "General Information".
Function/Time Setting
Accessories
4
Specifications are subject to change without notice (25.10.99)
Power supply
Pulse
Function 13
Function 14
Function 15
Function 16
Function 17
Function 18
Function 19
Function 20
Function 21
Function 22
Mode of Operation
* Memory whose contents are retained when there is a loss
power supply. Counting is continued at reconnection of
power supply. One time unit may be lost.
Power supply
Pulse
Function 1
Function 2
Function 3
Function 4
Function 5
Function 6
Function 7
Function 8
Function 9
Function 10
Function 11
Function 12