ChipFind - документация

Электронный компонент: S1342156024

Скачать:  PDF   ZIP
Specifications are subject to change without notice (25.10.99)
1
Timers
P-based analogue multi-function timer
10 functions within delay on operate, interval timer,
symmetrical recycler, recycler with fixed ON-time,
time period multiplier
Time ranges: 0.1 s to 100 h
Analogue trigger input for time start and reset
Analogue time set input
Time stop input
Four yellow LEDs each indicating 25% of
remaining time
Plug-in module, S-housing
Output: 5 A SPDT relay
LED-indication for relay and power supply ON
AC or DC power supply
Product Description
Plug-in, P-based multi-func-
tion time relay with 10 select-
able modes of operation and
time ranges from 0.1 s to 100 h.
Function and time range set-
ting by three rotary switches in
Ordering Key
Housing
Type/function
Output
Power supply
the front. Time setting by a
potentiometer in the front or
externally by a voltage 1-10
VDC. Time controlled by an
external voltage 1-10 VDC,
contact or power supply.
Type Selection
Plug
Output
Supply: 24 VAC
Supply:115 VAC
Supply: 230 VAC
Supply: 24 VDC
Circular
SPDT
S 1342 156 024
S 1342 156 115
S 1342 156 230
S 1342 156 724
Output Specifications
Output
SPDT
Rated insulation voltage
250 VAC (rms) (cont./elect.)
Contact ratings (AgCdO)
(micro gap)
(IEC 60947-5-1/IEC 60337)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life
40 x 10
6
operations
Electrical life
10
5
operations (at max. load)
Operating frequency
typ. 5 Hz
Operating time
< 10 ms
Release time (at nom. supply) < 6 ms
Dielectric strength
Dielectric (AC rms)
test voltage
2.0 kVAC (rms) (cont./elect.)
Rated impulse withstand
voltage
4 kV (1.2/50 s) (cont./elect.)
(IEC 60664)
Time Specifications
Time ranges
Selectable by rotary switches
0.1 - 1
s
1 - 10
s
10 - 100
s
0.1 - 1
m
1 - 10
m
10 - 100
m
0.1 - 1
h
1 - 10
h
10 - 100
h
Accuracy
Internal potentiometer
5% 20 ms
External voltage
3%
Repeatability deviation
0.5%
Time variation
within rated ambient temp.
0.1%/C
Digital Multi-function
Type S 1342
S 1342 156 230
2
Specifications are subject to change without notice (25.10.99)
S 1342
Input Specifications
Start/reset pin 5
at max.:
10 V 5%
at min.:
0.1 V
Hysteresis
5%
Pulse length
15 ms
Input impedance
100 k
1%
Input impedance
pin 5 & 9 interconnected
4 k
Max. voltage
30 VDC
External time setting pin 11
1-10 VDC
Accuracy
3% @ time potentiometer
at max. time
Input impedance
270 k
1%
Max. voltage
15 VDC
Time interruption pin 8
Typ. 24 VDC, 5 mA @
nom. supply
Interruption time
10 ms
Recovery time
10 ms
Supply Specifications
Power supply AC types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through pins 2 & 10
230
230 VAC 15%, 45 to 65 Hz
115
115 VAC 15%, 45 to 65 Hz
024
24 VAC 15%, 45 to 65 Hz
Voltage interruption
40 ms
Rated insulation voltage
250 VAC (rms)
Rated operational power
5.0 VA
Rated impulse withstand
voltage
4 kV (1.2/50 s) (line/neutral)
Power supply DC type
Overvoltage cat. III (IEC 60664)
Rated operational volt. 724
24 VDC 15% (pin 2 pos.)
Rated insulation voltage
None
Rated operational power
3.0 W
Rated impulse withstand
voltage
800 V (1.2/50 s)
General Specifications
Power ON delay
200 ms
Power OFF delay
200 ms
A/D conversion time
100 ms
Indication for
Power supply ON
LED, green
Output ON
LED, yellow
Remaining time to elapse
4 LEDs, yellow, 25% each
Environment
Degree of protection
IP 20 B
Pollution degree
2 (IEC 60664)
Operating temperature
0 to +50C (+34 to +122F)
Storage temperature
-50 to +85C (-58 to +185F)
Weight
AC supply
200 g
DC supply
125 g
Approvals
UL, CSA
Function and Time Setting
Knob adjustable time setting
on relative scale (1-10) or by
an external 1-10 VDC voltage.
Left upper knob:
Time period multiplier x 0.1,
x 1.0 and x 10.
Left second knob:
Selection of time range
(seconds, minutes, hours).
Left third knob:
Time setting.
Left lower knob:
Selection of function.
Right knob:
Selection of trigger level 0-10
VDC.
Mode of Operation
In connection with all func-
tions automatic start is possi-
ble by permanent intercon-
nection of pins 5 & 6.
Function 0: Delay on operate,
leading edge, man. start,
man. restart, man. time reset.
Function 1: Interval timer, lea-
ding edge, man. start, man.
restart, man. time reset.
Function 2:
Symmetrical
recycler, OFF-time first, lea-
ding edge, man. start, man.
restart, no time reset.
Function 3:
Symmetrical
recycler, ON-time first, lead-
ing edge, man. start, man.
restart, no time reset.
Function 4: Delay on operate,
trailing edge, man. start, man.
restart, man. time reset.
Function 5: Interval timer,
trailing edge, man. start, man.
restart, man. time reset.
Note: The output relay only
operates when the time peri-
od is running.
Function 6: Interval timer,
trailing edge, man. start, man.
restart, man. time reset.
Function 7: Delay on operate,
leading edge, man. start,
man. restart, man. time reset.
Note: The relay releases on
trailing edge, which means
the trigger pulse must be of
longer duration than the time
period.
Function 8: Recycler with fix-
ed ON-time, leading edge,
man. start, man. restart, no
time reset. Fixed ON-time:
Approx. 0.5 sec.
Function 9: Time period mul-
tiplier, leading edge, man.
start, man. restart, man. time
reset.
Note: Each pulse input adds
the set time to the total timing
period. Max. time period
memory is 256 pulses.
Time stop function: By inter-
connection of pins 7 & 8 the
time function stops, and the
output relay remains either
released or operated. By dis-
connection of pins 7 & 8 the
remaining time period con-
tinues to elapse.
External time setting possible
by an external voltage 1 to 10
VDC at pin 11.
Specifications are subject to change without notice (25.10.99)
3
S 1342
Wiring Diagrams
DC
AC
Start/reset
0.1-10 V
Ext. time set
+
+
Start/reset
0.1-10 V
+
+
Ext. time set
1-10 V
1-10 V
Accessories
Socket
S 411
Hold down spring
HF
Mounting rack
SM 13
Socket cover
BB 4
Front mounting bezel
FRS 2
All 3/4-wire sensor types with NPN open collector output.
For further information refer to "Accessories".
For other AC/DC voltages refer to "General Information".
Operation Diagrams
Power supply
Pulse input (5-7)
F 0 Relay ON
F 1 Relay ON
F 2 Relay ON
F 3 Relay ON
F 4 Relay ON
Power supply
Pulse input (5-7)
F 5 Relay ON
F 6 Relay ON
F 7 Relay ON
F 8 Relay ON
F 9 Relay ON
Pulse/time
multiplier (5-7)