1
Cable/bus-bar type current transformer
Panel mounting facility
TACO 110: class 0.5, currents from 800 to 4000 A
TACO 200: class 0.5, currents from 1000 to 6000 A
Product Description
Model
Primary current
Secondary current
Ordering Key
TACO110 800A 1A
Cable/bus-bar type current
transformer with panel mount-
TACO 110
ing facility. Rated primary cur-
rents from 800 A to 6000 A.
Accessories
Current Transformer, 1-Phase AC
Types TACO 110, TACO 200
Type Selection
Primary current
See Range Table
Model
TACO110:
Cable diameter:
Max. 110 mm
TACO200:
Cable diameter:
Max. 200 mm
Rated secondary current
5 A standard
1 A on request
Output Specifications
Input Specifications
Operating frequency
40 to 60 Hz
Max. system voltage
0.72 kV
Rated insulation level
3 kV / 1 min. @ 50 Hz
Short-time current rating
I
th
Typical 100 I
n
/1 s
I
dyn
2.5 I
th
The short-time thermal cur-
rent I
th
is anyway limited by
the cable/bus-bar size
Security factor
5
Standards
According to IEC 60185
Housing
TACO 100
Self-extinguishing thermo-
plastic insulated housing
TACO 200
Fully embodied in resin insu-
lated housing
Mounting
Panel mounting by means
of angle steel supplied with
the CT
Standard accessories
FAST-ON for secondary
terminals
Angle steels for panel
mounting
1 A secondary current
Special features
Sealable terminal cover
Tropicalization
Cable diameter
TACO 110
Max.110 mm
TACO 200
Max. 200 mm
General Specifications
TACO 200
2
Specifications are subject to change without notice
Dimensions (mm)
Wiring Diagram
Range Table
Rated
Rated secondary current 1 A/5 A
primary
Class 0.5
1)
Class 1
1)
Class 5P10
current
Burden
Burden
Burden
800 A
15 VA
30 VA
10 VA
1000 A
20 VA
40 VA
10 VA
1500 A
40 VA
80 VA
10 VA
2000 A
50 VA
100 VA
10 VA
2500 A
60 VA
120 VA
10 VA
3000 A
80 VA
160 VA
10 VA
4000 A
100 VA
200 VA
10 VA
1)
The accuracy class is depending on the burden output. For the same rated primary current, the higher the burden the lower
the class (class down-grade).
Rated
Rated secondary current 1 A/5 A
primary
Class 0.5
1)
Class 1
1)
Class 5P10
current
Burden
Burden
Burden
1000 A
15 VA
30 VA
10 VA
1500 A
15 VA
30 VA
10 VA
2000 A
15 VA
30 VA
10 VA
2500 A
40 VA
80 VA
10 VA
3000 A
40 VA
80 VA
10 VA
4000 A
50 VA
100 VA
10 VA
5000 A
50 VA
100 VA
10 VA
6000 A
50 VA
100 VA
10 VA
TACO 110:
TACO 200:
TACO 110, TACO 200
Output (secondary)
L
N
TACO 110
TACO 200