Ultrasonic
Diffuse, Programmable Outputs
Types UA 30 CLD .. F. M7
Cylindrical M30 polyester housing
Sensing distance: 150-1500 mm, 250-2000 mm
or 350-3500 mm
Programmable outputs: Analogue (0-10 V or 4-20 mA,
inverted or non-inverted) and 2 PNP open collector,
NO/NC switching outputs, 100 mA
Programmable hysteresis, switching frequency and set
points
RS 232 interface
Power supply: 19 to 30 VDC
8 beam angle
Protection: Short-circuit, reverse polarity, transients
Protection degree IP 67
M16 plug
Product Description
Ultrasonic sensor
Housing style
Housing size
Housing material
Housing length
Detection principle
Sensing distance
Output type
Output configuration
Connection
Type Selection
Housing
Connection
Rated operating
Ordering no.
Ordering no.
diameter
dist. (S
n
)
Analogue 0-10 V
Analogue 4-20 mA
M30
M16
150-1500 mm
UA 30 CLD 15 FK M7
UA 30 CLD 15 FG M7
M30
M16
250-2000 mm
UA 30 CLD 20 FK M7
UA 30 CLD 20 FG M7
M30
M16
350-3500 mm
UA 30 CLD 35 FK M7
UA 30 CLD 35 FG M7
Ordering Key UA 30 CLD 15 FK M7
A family of diffuse ultrasonic
sensors with sensing range
from 150-1500 mm, 250-2000
mm and 350-3500 mm with
programmable settings by
Windows based software.
The programmability of the
sensors gives the possibility
of an universal application in
any area of industrial environ-
ment. The outputs are 0-10V
or 4-20mA and RS232 inter-
face, which make it possible
to communicate with BUS-
systems. Due to use of micro-
processor control the digital
filtering makes the sensor
immune to most electromag-
netic interferences. The con-
trol input enables synchroni-
sation in an easy way.
Specifications
Rated operational volt. (U
e
)
19 to 30 VDC (ripple incl.)
Ripple
10%
Output current (I
e
)
max. 100 mA (continuous)
No-load supply current (I
o
)
35 mA
Off-state current (I
r
)
200
A
Voltage drop (U
d
)
4.5 V
Power-on delay
< 10 ms
Carrier frequency
200 KHz
Protection
Short-circuit, transients and
reverse polarity
Rated insulation voltage
> 1 kV
Control input
Hold/Synchronisation
Output, analogue
UA30CLD..FKM7
Analogue 0-10 or 10-0 VDC,
programmable
Load: > 1 k
UA30CLD..FGM7
Analogue 4-20 or 20-4 mA,
programmable
Load: < 500
Scaling
Programmable
Linearity
0.5%/3 mm
Repeatabilty
0.2%/0.4 mm
Load
4 - 20 mA
max. 500
0 - 10 V
min. 1 k
Output, switching
2 x PNP, open collector,
NO/NC, 100 mA,
programmable.
Programming
- sensor address
(Windows based software)
- analogue output
offset, range, inversion
- 2 set points/Limits
NO/NC, position,
hysteresis
- digital output
Hex, BCD
- cycle time
- over/under range
- transmit time
- offset
- slope
Output, information
Serial HEX/BCD
2
Specifications are subject to change without notice (22.08.2005)
Dimensions
UA 30 CLD .. F. M7
Specifications (cont.)
Interface
RS 232
Indication
Alignment LED
Repeat accuracy (R)
0.2%
Rated operating distance /
resolution
UA30CLD15 .. ..
150-1500 mm / < 1 mm
UA30CLD20 .. ..
250-2000 mm / < 1 mm
UA30CLD35 .. ..
350-3500 mm / < 1 mm
Operating frequency
5-30 Hz, programmable
Response times
UA30CLD15 .. ..
100 ms
UA30CLD20 .. ..
300 ms
UA30CLD35 .. ..
500 ms
Hysteresis (H)
(differential travel)
Programmable
150 mm
250 mm
350 mm
1500 mm
2000 mm
3500 mm
20
20
30
30
40
40
Detection Range
Guaranteed detection of a
target 100 x 100 mm
Possible detection of a
large target
Temperature compensation
Yes
Beam angle
8
Ambient temperature
Operating
-15 to +70C (5 to +158F)
Storage
-25 to +75C (-13 to +167F)
Degree of protection
IP 67 (Nema 1, 3, 4, 6, 13)
Housing material
Polyester PBTP
Connection
Plug
M16, 8-pin
Weight
154 g
Tightening torque
7.6 Nm
CE-marking
Yes
Wiring Diagram
1
7
8
6
4
3
5
R x D
Enable
Hold
Synchronization
T x D
2
SP1
SP2
Sensor
# 1
Sensor
# 10
6
6
Specifications are subject to change without notice (05.09.2005)
3
Installation Hints
Relief of cable strain
Protection of the sensing face
Switch mounted on mobile carrier
To avoid interference from inductive voltage/
current peaks, separate the prox. switch
power cables from any other power cables,
e.g. motor, contactor or solenoid cables
Incorrect
Correct
The cable should not be pulled
A proximity switch should not serve as
mechanical stop
Any repetitive flexing of the
cable should be avoided
Accessories
UDSprog 2000 PC-software, download from
www.carlogavazzi.com/ac
UCP1 Programming Adaptor