M O D E L N U M B E R S
CSD2410
CSD2425
CSD2450
CSD2475
CSD2490
CSE2410
CSE2425
CSE2450
CSE2475
CSE2490
OUTPUT SPECIFICATIONS
Operating Voltage (47-63 Hz) [Vrms]
24-280
24-280
24-280
24-280
24-280
Load Current Range
[Arms]
0.15-10
0.15-25
0.15-50
0.25-75
0.25-90
Transient Overvoltage [Vpk]
600
600
600
600
600
Max. Surge Current, (16.6ms) [Apk]
120
250
625
1000
1200
Max. On-State Voltage Drop @ Rated Current [Vpk]
1.6
1.6
1.6
1.6
1.6
Thermal Resistance Junction to Case (R ) [C/W]
JC
1.48
1.02
0.63
0.31
0.28
Maximum I 2 t for Fusing, (8.3 msec.) [A 2sec]
60
260
1620
4150
6000
Max. Off-State Leakage Current @ Rated Voltage [mA]
1.0
1.0
1.0
1.0
1.0
Min. Off-State dv/dt @ Max. Rated Voltage [V/sec]
500
500
500
500
500
Max. Turn-On Time
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
Max. Turn-Off Time
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
Power Factor (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
DC CONTROL
DC CONTROL
(CSD PREFIX)
(CSE PREFIX)
Control Voltage Range
3.5-15 Vdc
15-32 Vdc
Max. Turn-On Voltage
3.5 Vdc
15.0 Vdc
Min. Turn-Off Voltage
1.0 Vdc
1.0 Vdc
Nominal Input Impedence
300 Ohm
2k Ohm
Typical Input Current
15 mA @ 5 Vdc
7mA @ 15 V
All parameters at 25C unless otherwise specified.
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
Heat sinking required, for derating curves see page 2.
Zer
FastFax Document No.162
Zer
Zer
G E N E R A L N O T E S
Low Leakage
SCR Output
Panel Mount
Zero Voltage Switching
SERIES CS.
Rev. 012402
PAGE 1 OF 3
The Series CS has an SCR AC switch
output featuring low off-state leakage
(1mA, snubberless), zero-voltage
switching and a broadened operating
range (24-280Vac). This wide range
permits optimum performance at both
120Vac and 240Vac line voltages.
Manufactured in Crydom's ISO 9001
Certified facility for optimum product
performance and reliability.
2001 CRYDOM CORP, Specifications subject to change without notice.
Series CS
10-90Amp 120/240 Vac AC OUTPUT
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
Dielectric Strength 50/60Hz , Input/Output/Base
4000 Vrms
Insulation Resistance (Min.) @ 500 Vdc
10
9
Ohm
Max. Capacitance Input/Output
10 pF
Ambient Operating Temperature Range
-40 to 80C
Ambient Storage Temperature Range
-40 to 125C
Weight: (typical)
3.0 oz. (86.5g)
Encapsulation:
Thermally Conductive Epoxy
Terminals:
Screws and Saddle Clamps Furnished, Unmounted
APPROVALS
UL
E116949
CSA
LR81689
10143 UG
Crydom Heat Sinks offer excellent
thermal management and are per-
fectly matched to the load current
ratings of Crydom panel mount
relays. Request Crydom's Heat Sink
specification sheet for all the details.
FastFax Document No.162
2001 CRYDOM CORP, Specifications subject to change without notice.
Screw Torque Requirements:
6-32 Screws - 10 in./lbs.,
8-32 and 10-32 Screws - 20in./lbs.
(Screws dry without grease.)
Fastons:
Single pair (up to 25A)
Double pair* (up to 50A).
* Caution: User must connect to both pairs
Series CS
*
VDE
*
GENERAL SPECIFICATIONS
MECHANICAL SPECIFICATIONS
SERIES CS.
Rev. 012402
PAGE 2 OF 3
10-90Amp 120/240 Vac AC OUTPUT
*
All dimensions are in inches (millimeters)
AVAILABLE OPTIONS
-10
Random Turn-On (AC & DC Control)
Phase Controllable (DC Control)
Example: CSD2425-10
F
Faston Terminals (Up to 50A Models)
Example: CSD2425F
P
Internal Overvoltage Protection.
Relay Will Self Trigger Between
450-600 Vpk. Not Suitable For Capacitive Loads.
Agencies Approval Pending.
Example: CSD2425P
G
Input Status LED.
Agencies Approval Pending
Example: CSD2425G
Note:
Control Voltage Range 5-15Vdc
for CSD Models.
.90
(22.9)
FASTON
TERMINAL
.187 X .032
(2 PLCS.)
BASE PLATE
.125 (3.2)
FASTON TERMINAL
.250 X .032 (2 PLCS.)
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.87 REF.
(22.2)
OUTPUT
INPUT
1.00
(25.4)
1.80
(45.7)
.45
(11.4)
1.10
(27.9)
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
SOLID-STATE RELAY
3
4
1
2
--
+
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.90
(22.9)
.45
(11.4)
1.10
(27.9)
8-32 TERMINAL
(2 PLACES )
1.00
(25.4)
6-32 TERMINAL
(2 PLACES)
1.80
(45.7)
SOLID-STATE RELAY
1
2
OUTPUT
3
4
+
--
INPUT
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
BASE PLATE
.125 (3.2)
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
Power Dissipation
Power Dissipation
Power Dissipation
Power Dissipation
Power Dissipation
Power Dissipation
Power Dissipation
Power Dissipation
FastFax Document No.162
2001 CRYDOM CORP, Specifications subject to change without notice.
SERIES CS.
Rev. 012402
PAGE 3 OF 3
Series CS
10-90Amp 120/240 Vac AC OUTPUT
12
8
4
0
2
4
8
10
6
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
110
115
120
Base Plate Temp [

C]
10A
5C/W
3C/W
7C/W
NO HEATSINK
9C/W
CURRENT DERATING CURVES
30
20
10
25
15
5
0
5
10
20
25
15
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
95
120
Base Plate Temp [

C]
25A
1C/W
100
110
3C/W
NO HEATSINK
60
40
20
0
10
20
40
50
30
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
90
Base Plate Temp [

C]
50A
2C/W
1C/W
.5C/W
100
110
120
1.5C/W
NO HEATSINK
120
80
40
0
15
30
60
75
45
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
100
110
120
Base Plate Temp [

C]
75A
.5C/W
95
1C/W
120
80
40
0
20
40
80
0
60
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
100
110
120
Base Plate Temp [

C]
90A
1C/W
.4C/W
.2C/W
90
.5C/W
2C/W
.3C/W
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506