M O D E L N U M B E R S
AC CONTROL
HA6025
HA6050
HA6090
HA60125
D C CONTROL
HD6025
HD6050
HD6090
HD60125
OUTPUT SPECIFICATIONS
Nominal Line Voltage (
10%) [Vrms]
600
600
600
600
Operating Voltage Range (47-63 Hz) [Vrms]
48-660
48-660
48-660
48-660
Max. Load Current
[Arms]
25
50
90
125
Min. Load Current, [mArms]
40
40
40
150
Transient Overvoltage [Vpk]
1200
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
250
625
1,200
1,750
Max. On-State Voltage Drop @ Rated Current [Vpk]
1.7
1.7
1.7
1.7
Thermal Resistance Junction to Case (R
JC) [ C/W]
1.02
0.63
0.28
0.22
Maximum I 2 t for Fusing, (8.3 msec.) [A 2sec]
260
1,620
6,000
12,700
Max. Off-State Leakage Current @ Rated Voltage [mArms]
5
5
5
5
Min. Off-State dv/dt @ Max. Rated Voltage [V/sec]
500
500
500
500
Max. Turn-On Time
1/2 Cycle (DC Input), 10.0 msec (AC Input)
Max. Turn-Off Time
1/2 Cycle (DC Input), 40.0 msec (AC Input)
Power Factor (Min.) with Max. Load
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
DC CONTROL
AC CONTROL
AC CONTROL
( D P R E F I X )
( A P R E F I X )
( E S U F F I X )
Control Voltage Range
3-32 Vdc
90-280 Vrms (60Hz)
18-36 Vrms
Max. Reverse Voltage
-32 Vdc
---
---
Max. Turn-On Voltage
3.0 Vdc
90 Vrms
18 Vrms
Min. Turn-Off Voltage
1.0 Vdc
10 Vrms
4.0 Vrms
Nominal Input Impedance
See Note
60K Ohms
9.0K Ohms
Typical Input Current
2.0 mA
2mA @ 120 Vrms, 4mA @ 240 Vrms
3mA @ 24 Vrms
G E N E R A L N O T E S
All parameters at 25C unless otherwise specified.
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
Heat sinking required, for derating curves see page 2.
24 Vac Input option, E suffix.
Turn-on time for random turn-on versions is 0.02 msec (DC Control Models).
Input circuitry incorporates active current limiter.
No internal snubber.
Zero Voltage and Random
Turn-On Switching
Panel Mount
1200V Blocking Capability
600Vac - the preferred
choice in Canada
FastFax Document No.159
SERIES HA/HD60.
Rev. 031802
PAGE 1 OF 3
Featuring state-of-the-art Surface
Mount Technology, these SPST-NO
relays deliver proven reliability in the
most demanding applications.
Output consists of an SCR AC switch
and is available in zero-cross, random
turn-on (phase controllable) and ver-
sions with either AC or DC input (coil)
control.
Manufactured in Crydom's ISO 9001
Certified facility for optimum product
performance and reliability.
Series HA60/HD60
25-125Amp 600 Vac AC Output
2002 CRYDOM CORP, Specifications subject to change without
notice.
Integrated Overvoltage
Protection by Automatic
Self Turn-On (Suffix P)
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base
4000 Vrms
Insulation Resistance (Min.) @ 500 Vdc
10
9
Ohm
Max. Capacitance Input/Output
8 pF
Ambient Operating Temperature Range
-40 to 80C
Ambient Storage Temperature Range
-40 to 125C
MECHANICAL SPECIFICATIONS
Weight: (typical)
3.0 oz. (86.5g)
Encapsulation: Thermally
Conductive
Epoxy
Terminals:
Screws and Saddle Clamps Furnished, Unmounted
APPROVALS
UL
E116950
CSA LR81689
VDE 10143 UG
Crydom Heat Sinks offer excellent
thermal management and are per-
fectly matched to the load current
ratings of Crydom panel mount
relays. Request Crydom's Heat Sink
specification sheet for all the details.
FastFax Document No.159
SERIES HA/HD60.
Rev. 031802
PAGE 2 OF 3
Series HA60/HD60
25-125Amp 600 Vac AC Output
2002 CRYDOM CORP, Specifications subject to change without
notice.
Screw Torque Requirements:
6-32 Screws - 10 in./lbs.,
8-32 and 10-32 Screws - 20in./lbs.
(Screws dry without grease.)
Fastons:
Single pair (up to 25A)
Double pair* (up to 50A).
*Caution: User must connect to both pairs
.90
(22.9)
FASTON
TERMINAL
.187 X .032
(2 PLCS.)
BASE PLATE
.125 (3.2)
FASTON TERMINAL
.250 X .032 (2 PLCS.)
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.87 REF.
(22.2)
1
2
OUTPUT
4
3
INPUT
1.00
(25.4)
1.80
(45.7)
.45
(11.4)
1.10
(27.9)
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
.90
(22.9)
FASTON
TERMINAL
.187 X .032
(2 PLCS.)
BASE PLATE
.125 (3.2)
FASTON TERMINAL
.250 X .032 (2 PLCS.)
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.87 REF.
(22.2)
1
2
OUTPUT
4
3
INPUT
1.00
(25.4)
1.80
(45.7)
.45
(11.4)
1.10
(27.9)
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
All dimensions are in inches (millimeters)
AVAILABLE OPTIONS
E
24 VAC Input (18-36 Vac)
Example: HA6025E
-10
Random Turn-On (AC & DC Control)
Phase Controllable (DC Control)
Example: HD6090-10
F
Faston Terminals (Up to 50 Amp Models)
Example: HD6050F
P
Internal Overvoltage Protection.
Relay Will Self Trigger Between
900-1200 Vpk. Not Suitable For
Capacitive Loads.
Agencies Approval Pending.
Example: HD6025P
G
Input Status LED.
Agencies Approval Pending
Example: HD6050G
Note:
Control Voltage Range 4.5-32Vdc
for DC Control Models.
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.90
(22.9)
.45
(11.4)
1.10
(27.9)
8-32 TERMINAL
(2 PLACES )
1.00
(25.4)
6-32 TERMINAL
(2 PLACES)
1.80
(45.7)
SOLID-STATE RELAY
1
2
OUTPUT
3
4
+
--
INPUT
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
BASE PLATE
.125 (3.2)
Ordering System: Combination of the
suffixes should be made in the following order:
EFPG-10.
Example: HA6050EFPG-10
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
FastFax Document No.159
SERIES HA/HD60.
Rev. 031802
PAGE 3 OF 3
Series HA60/HD60
25-125Amp 600 Vac AC Output
Base Plate Temp [C]
60
40
20
0
10
20
40
50
30
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
90
50A
2C/W
.5C/W
100
110
120
1.5C/W
NO HEATSINK
120
80
40
0
20
40
80
0
60
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
100
110
120
Base Plate Temp [

C]
90A
1C/W
.4C/W
90
.5C/W
30
20
10
25
15
5
0
5
10
20
25
15
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
95
120
Base Plate Temp [

C]
25A
1C/W
100
110
3C/W
NO HEATSINK
2C/W
160
80
40
120
0
30
60
120
0
90
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [C]
Power Dissipation
100
110
120
Base Plate Temp [

C]
125A
.5C/W
.4C/W
90
1C/W
.2C/W
1C/W
.2C/W
C U R R E N T D E R A T I N G C U R V E S
2002 CRYDOM CORP, Specifications subject to change without
notice.
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506