600 A
STANDARD DIODES
Bulletin I27402
1
IRKD600.. SERIES
SUPER MAGN-A-PAK
TM
Power Modules
Major Ratings and Characteristics
Parameters
IRKD600..
Units
I
F(AV)
600
A
@ T
C
82
C
I
F(RMS)
1120
A
@ T
C
82
C
I
FSM
@ 50Hz
19.0
KA
@ 60Hz
20.1
KA
I
2
t
@ 50Hz
1805
KA
2
s
@ 60Hz
1683
KA
2
s
I
2
t
18050
KA
2
s
V
RRM
range
800 to 2000
V
T
STG
range
- 40 to 150
C
T
J
range
- 40 to 150
C
Features
High current capability
3000 V
RMS
isolating voltage with non-toxic substrate
High surge capability
High voltage ratings up to 2000V
Industrial standard package
UL recognition pending
Typical Applications
Rectifying bridge for large motor drives
Rectifying bridge for large UPS
Next Data Sheet
Index
Previous Datasheet
To Order
IRKD600.. Series
2
ELECTRICAL SPECIFICATIONS
Voltage Ratings
Voltage
V
RRM
, maximum repetitive
V
RSM
, maximum non-
I
RRM
max.
Type number
Code
peak reverse voltage
repetitive peak rev. voltage
@ T
J
max.
V
V
mA
08
800
900
12
1200
1300
16
1600
1700
20
2000
2100
IRKD600..
50
I
F(AV)
Maximum average forward current
600
A
180 conduction, half sine wave
@ Case temperature
82
C
I
F(RMS)
Maximum RMS forward current
1120
A
180 conduction, half sine wave @ T
C
= 82C
I
FSM
Maximum peak, one-cycle forward,
19.0
KA
t = 10ms
No voltage
non-repetitive surge current
20.1
t = 8.3ms
reapplied
16.2
t = 10ms
100% V
RRM
17.2
t = 8.3ms
reapplied
Sinusoidal half wave,
I
2
t
Maximum I
2
t for fusing
1805
KA
2
s
t = 10ms
No voltage
Initial T
J
= T
J
max.
1683
t = 8.3ms
reapplied
1319
t = 10ms
100% V
RRM
1230
t = 8.3ms
reapplied
I
2
t
Maximum I
2
t for fusing
18050
KA
2
s t = 0.1 to 10ms, no voltage reapplied
V
F(TO)1
Low level value of threshold voltage
0.70
V
(16.7% x
x I
F(AV)
< I <
x I
F(AV)
), T
J
= T
J
max.
V
F(TO)2
High level value of threshold voltage
0.77
(I >
x I
F(AV)
), T
J
= T
J
max.
r
f1
Low level value of forward slope resistance
0.28
m
(16.7% x
x I
F(AV)
< I <
x I
F(AV)
), T
J
= T
J
max.
r
f2
High level value of forward slope resistance
0.25
(I >
x I
F(AV)
), T
J
= T
J
max.
V
FM
Maximum forward voltage drop
1.24
V
I
pk
= 1800A, T
J
= 25C, t
p
= 10ms sine pulse
Parameter
IRKD600..
Units Conditions
Forward Conduction
V
INS
RMS isolation voltage
3000
V
t = 1 s
I
RRM
Maximum peak reverse and off-state
50
mA
T
J
= T
J
max., rated V
RRM
applied
leakage current
Parameter
IRKD600..
Units Conditions
Blocking
Next Data Sheet
Index
Previous Datasheet
To Order
IRKD600.. Series
3
Parameter
IRKD600..
Units Conditions
Thermal and Mechanical Specifications
T
J
Max. junction operating temperature range
- 40 to 150
C
T
stg
Max. storage temperature range
- 40 to 150
R
thJC
Max. thermal resistance, junction to
0.065
K/W
Per junction, DC operation
case
R
thC-hs
Max. thermal resistance, case to
0.02
K/W
heatsink
T
Mounting torque 10%SMAP to heatsink
6 - 8
Nm
busbar to SMAP
12 - 15
wt
Approximate weight
1500
g
Case style
Super Magn-a-Pak
See outline table
IRK
D
600
-
20
1
2
3
1
-
Module type
2
-
Circuit configuration D = 2 diodes in series
3
-
Current rating
4
-
Voltage code: Code x 100 = V
RRM
(See Voltage Ratings Table)
4
Device Code
Ordering Information Table
R
thJC
Conduction
(The following table shows the increment of thermal resistance R
thJC
when devices operate at different conduction angles than DC)
Conduction angle
Sinusoidal conduction Rectangular conduction
Units
Conditions
180
0.009
0.006
120
0.011
0.011
90
0.014
0.015
K/W
T
J
= T
J
max.
60
0.021
0.022
30
0.037
0.038
+
-
~
1
2
3
A mounting compound is recommended and the
torque should be rechecked after a period of 3 hours
to allow for the spread of the compound
To Order
Next Data Sheet
Index
Previous Datasheet
IRKD600.. Series
4
Outline Table
All dimensions in millimeters (inches)
To Order
Next Data Sheet
Index
Previous Datasheet