ChipFind - документация

Электронный компонент: E2E-X5MY2-US-N

Скачать:  PDF   ZIP

Document Outline

R
2
Short Barrel Inductive Prox
E2E 2-WIRE AC
Short Barrel 2-Wire AC Prox Sensors
Meet IP67
H
Thick nickel-plated brass barrel has wrench
flats for easy installation
H
Solid potted internal circuitry withstands
shocks and water washdown to IP67
H
High visibility indicator
H
Choose prewired models with or without
short-circuit protection and connector
models
Ordering Information
J
PREWIRED SENSORS WITHOUT SHORT-CIRCUIT PROTECTION
WHEN ORDERING, PLEASE NOTE:
Omron has added the suffix "-N" to E2E part numbers for ordering purposes only; the suffix "-N" will not
appear on the product.
Type
Size
Sensing distance
Part number
yp
g
NO
NC
Shielded
M8
1.5 mm
E2E-X1R5Y1-N
E2E-X1R5Y2-N
M12
2 mm
E2E-X2Y1-US-N
E2E-X2Y2-US-N
M18
5 mm
E2E-X5Y1-US-N*
E2E-X5Y2-US-N
M30
10 mm
E2E-X10Y1-US-N*
E2E-X10Y2-US-N
Unshielded
M8
2 mm
E2E-X2MY1-US-N*
E2E-X2MY2-US-N
M12
5 mm
E2E-X5MY1-US-N*
E2E-X5MY2-US-N*
M18
10 mm
E2E-X10MY1-US-N*
E2E-X10MY2-US-N*
M30
18 mm
E2E-X18MY1-US-N*
E2E-X18MY2-US-N
*Note: A different oscillating frequency is available to prevent mutual interference. Add a "5" to the part number (e.g., E2E-X5Y15-US-N).
E2E 2-WIRE AC
E2E 2-WIRE AC
3
J
PREWIRED SENSORS WITH SHORT-CIRCUIT PROTECTION
Type
Size
Sensing distance
Part number
yp
g
NO
NC
Shielded
M18
5 mm
E2E-X5Y1-53-US
E2E-X5Y2-53-US
M30
10 mm
E2E-X10Y1-53-US
E2E-X10Y2-53-US
Unshielded
M18
10 mm
E2E-X10MY1-53-US
E2E-X10MY2-53-US
M30
18 mm
E2E-X18MY1-53-US
E2E-X18MY2-53-US
J
SENSORS WITH BUILT-IN CONNECTORS
Connector
Type
Size
Sensing distance
Part number
yp
g
NO
NC
4-pin
connector
Shielded
M12
2 mm
E2E-X2Y1-M1-N
E2E-X2Y2-M1-N
(M12)
See Note 1.
M18
5 mm
E2E-X5Y1-M1-N
E2E-X5Y2-M1-N
M30
10 mm
E2E-X10Y1-M1-N
E2E-X10Y2-M1-N
Unshielded
M12
5 mm
E2E-X5MY1-M1-N
E2E-X5MY2-M1-N
M18
10 mm
E2E-X10MY1-M1-N
E2E-X10MY2-M1-N
M30
18 mm
E2E-X18MY1-M1-N
E2E-X18MY2-M1-N
3-pin
connector
(M12)
Shielded
M12
2 mm
E2E-X2Y1-M4
E2E-X2Y2-M4
(M12)
See Note 2.
M18
5 mm
E2E-X5Y1-M4
E2E-X5Y2-M4
M30
10 mm
E2E-X10Y1-M4
E2E-X10Y2-M4
Unshielded
M12
5 mm
E2E-X5MY1-M4
E2E-X5MY2-M4
M18
10 mm
E2E-X10MY1-M4
E2E-X10MY2-M4
M30
18 mm
E2E-X18MY1-M4
E2E-X18MY2-M4
Note: 1. Use Omron's Y96E-44jAj connector cordsets.
2. Use Omron's Y96E-33jAj connector cordsets.
J
ACCESSORIES
Description
Part number
Mounting brackets
Fits M8 size sensors
Fits M12 size sensors
Fits M18 size sensors
Fits M30 size sensors
Y92E-B8
Y92E-B12
Y92E-B18
Y92E-B30
Silicone rubber covers for shielded sensors
Fits M12 size sensors
Fits M18 size sensors
Fits M30 size sensors
Y92E-E12-2
Y92E-E18-2
Y92E-E30-2
Connector cordsets
See Y96E Connector Cordsets data sheet for details
E2E 2-WIRE AC
E2E 2-WIRE AC
4
J
REPLACEMENT PARTS
Description
Part number
Mounting hardware including one pair of
metal nuts and one washer
Fits M8 size sensors
Fits M12 size sensors
Fits M18 size sensors
Fits M30 size sensors
M8-MHWS
M12-MHWS
M18-MHWS
M30-MHWS
Specifications
J
SENSORS WITHOUT SHORT-CIRCUIT PROTECTION (E2E-X
j
j
j
j
Yj
j
j
j
)
Part number
E2E-X1R5Yj-N
E2E-X2MYj-N
E2E-X2Yj
-US-N
E2E-X5MY
j
-US-N
E2E-X5Y
j
-US-N
E2E-X10MY
j
-US-N
E2E-X10Y
j
-US-N
E2E-X18MY
j
-US-N
Size
M8
M12
M18
M30
Type
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
Sensing distance
1.5 mm
(0.06 in) 10%
2 mm
(0.08 in)
10%
2 mm
(0.08 in)
10%
5 mm
(0.20 in)
10%
5 mm
(0.20 in)
10%
10 mm
(0.39 in)
10%
10 mm
(0.39 in)
10%
18 mm
(0.71 in)
10%
Supply voltage
(operating voltage
range) (See note 1)
24 to 240 VAC, 50/60 Hz (20 to 264 VAC)
Current consumption
1.7 mA max.
Sensing object
Magnetic metals (refer to Engineering Data for non-magnetic metals)
Setting distance
0 to 1.2 mm
(0 to 0.05 in)
0 to 1.6 mm
(0 to 0.06 in)
0 to 1.6
mm (0 to
0.06 in)
0 to 4.0
mm (0 to
0.16 in)
0 to 4.0
mm (0 to
0.16 in)
0 to 8.0
mm (0 to
0.31 in)
0 to 8.0
mm (0 to
0.31 in)
0 to 14.0
mm (0 to
0.55 in)
Standard object
(mild steel)
8 x 8 x 1 mm
(0.31 x 0.31 x
0.04 in)
12 x 12 x
1 mm (0.47 x
0.47 x 0.04
in)
12 x 12 x
1 mm
(0.47 x
0.47 x
0.04 in)
15 x 15 x
1 mm
(0.59 x
0.59 x
0.04 in)
18 x 18 x
1 mm
(0.71 x
0.71 x
0.04 in)
30 x 30 x
1 mm
(1.18 x
1.18 x
0.04 in)
30 x 30 x
1 mm (1.18
x 1.18 x
0.04 in)
54 x 54 x
1 mm (2.13
x 2.13 x
0.04 in)
Differential travel
10% max. of sensing distance
Response frequency
25 Hz
Operation (with
sensing object
approaching)
Y1 models: Load ON
Y2 models: Load OFF
Control output
(switching capacity)
5 to 100 mA max.
5 to 200 mA max.
5 to 300 mA max.
Indicator
Operation indicator (red LED)
Ambient temperature
(See note 2)
Operating: --25C to 70C
(--13F to 158F)
with no icing
Operating: --40C to 85C (--40F to 185F) with no icing
Ambient humidity
Operating: 35% to 95%
Temperature
influence
15% max. of sensing distance at 23C in temperature range of --40C to 85C (--40F to 185F)
10% max. of sensing distance at 23C in temperature range of --25C to 70C (--13F to 158F)
Voltage influence
1% max. of sensing distance in rated voltage range 15%
Residual voltage
Refer to Engineering Data
Insulation resistance
50 M min. (at 500 VDC) between current carry parts and case
Dielectric strength
4,000 VAC for 1 min between current carry parts and case (2,000 VAC for M8 types)
Vibration resistance
10 to 55 Hz, 1.5-mm double amplitude for 2 hrs each in X, Y, and Z directions
Shock resistance
500 m/s
2
(approx. 50G) for 10
times each in X, Y, and Z axes
1,000 m/s
2
(approx. 50G) for 10 times each in X, Y, and Z axes
500 m/s
2
(approx. 50G) for E2E-X5M
Enclosure IEC
IP67
rating
NEMA
1, 4, 6, 12, 13
Note: 1. When using an M18 or M30 size E2E at an ambient temperature between 70C and 85C (158F and 185F), make sure that
the E2E has a control output of 200 mA maximum.
2. When supplying 24 VAC to any of the above models, make sure that the operating ambient temperature range is --25C to 85C
(--13F to 185F).
(This table continues on the next page.)
E2E 2-WIRE AC
E2E 2-WIRE AC
5
Specifications Table
-- continued from previous page
Part number
E2E-X1R5Y
j
-N
E2E-X2MY
j
-N
E2E-X2Yj-
US-N
E2E-X5MYj
-US-N
E2E-X5Yj-
US-N
E2E-X10MY
j
-US-N
E2E-X10Y
j
-US-N
E2E-X18MY
j
-US-N
Approvals UL
--
Recognized, File Number E76675
pp
CSA
--
Certified, File Number LR45951
Weight
Prewired
Approx. 45 g
Approx. 120 g
Approx. 160 g
Approx. 270 g
g
Connector
---
Approx. 25 g
Approx. 45 g
Approx.
125 g
Approx.
124 g
Material
Body
Stainless steel
Brass
Sensing
face
PBT
J
SENSORS WITH SHORT-CIRCUIT PROTECTION (E2E-Xj
j
j
j
Yj
j
j
j
-53-US)
Part number
E2E-X5Yj-53-US
E2E-X10MYj-53-US
E2E-X10Yj-53-US
E2E-X18MYj-53-US
Body
Size
M18
M30
y
Type
Shielded
Unshielded
Shielded
Unshielded
Supply voltage
90 to 140 VAC, 50/60 Hz
Effective maximum detecting distance
(with standard target)
5 mm (0.20 in) 10%
10 mm (0.40 in) 10%
18 mm
(0.71 in) 10%
Usable detecting range (with standard
target)
0 to 4 mm
(0 to 0.16 in)
0 to 8 mm (0 to 0.31 in)
0 to 14 mm
(0 to 0.55 in)
Standard target size
(mild steel, L x W x H)
18 x 18 x 1 mm
(0.71 x 0.71 x
0.04 in)
30 x 30 x 1 mm
(1.18 x 1.18 x 0.04 in)
54 x 54 x 1 mm
(2.13 x 2.13 x
0.04 in)
Differential travel
10% max. of effective detecting distance
Control
output
AC
solid
Type
SCR-NO (E2E-XjjjY1-jj-jj)
SCR-NC (E2E-XjjjY2-jj-jj)
p
state
Max. load
300 mA
Min. load
5 mA
Max. offstate
leakage current
1.5 mA (See "Leakage Current Characteristics" graph in Engineering Data.)
Max. on-state
voltage drop
(See "Leakage Current Characteristics" graph in Engineering Data.)
Response frequency
25 Hz
Circuit
Output short-circuit
Provided
protection
Weld field
immunity
Not provided
RFI immunity
Not provided
Indicators
Target present (red LED)
Materials
Housing
Nickel-plated brass
Sensing face
Plastic
Cable sheath
Plastic
Mounting
Two lock washers and M18 nuts included.
Bracket Y92E-B18 optional.
Two lock washers and M30 nuts included.
Bracket Y92E-B30 optional.
Connections
Prewired
2-conductor cable, 2 m (6.56 ft) length
Weight with cable
Approx. 160 g (5.6 oz.)
Approx. 270 g (9.5 oz.)
Enclosure
UL
1
ratings
NEMA
1, 4, 6, 12, 13
IEC 144
IP67
Approvals
UL
Recognized, File Number E76675
pp
CSA
Certified, File Number LR45951
Ambient operating temperature
-25 to 70C (-13 to 158F)
Vibration
10 to 55 Hz, 1.5 mm (0.06 in) double amplitude
Shock
Approx. 100 G's
E2E 2-WIRE AC
E2E 2-WIRE AC
6
Operation
J
OUTPUT CIRCUITS
Sensors without Short-Circuit Protection (E2E-XjYj)
E2E-XjYj-N AC 2-wire Models
Main
circuit
Load
Brown 1 (or 3)
Blue 2 (or 4)
Sensing
object
Control
output
Yes
No
Lit
Not lit
Red
indicator
ON
OFF
AC 2-wire Models
E2E-XjYj-N
Sensors with Short-Circuit Protection (E2E-XjYj-US-53)
Prox.
switch
main
circuit
White (Brown)
Load
Black (Blue)
Note: IEC colors are shown in parenthesis
With Short-Circuit Protection
E2E-X
jY1-53
NO
Load
Target
Output
Output
operation
indicator
Shorted
Normal
Present
Absent
ON
OFF
ON
OFF
Shorted
Normal
Present
Absent
ON
OFF
ON
OFF
E2E-XjY2-53
NC
Short-Circuit Indication
The LED dims when the load is shorted and the load output immediately turns off and remains off until the short-circuit protection is reset.
Resetting Short-Circuit Protection
Before the short-circuit protection can be reset, the short must be repaired. We recommend turning the power off before repairing the
short. If this approach is taken, no further action is required to reset the short-circuit protection.
If the short must be repaired with power on, the following resetting steps are required:
For NO sensors, the target must be removed to reset the short-circuit protection.
For NC sensors, the target must be presented then removed to reset the short-circuit protection.