ChipFind - документация

Электронный компонент: E5GN-Q1TCAC100-240

Скачать:  PDF   ZIP

Document Outline

R
67
Digital Temperature Controllers
E5GN
Compact, Intelligent Temperature Controllers
H
1/32 DIN sized controller saves panel
space, measures just 100 mm deep
H
Accepts thermocouple, platinum RTD,
non-contact temperature sensor, and
analog temperature inputs
H
Auto-tuning and self-tuning available;
functions can be used simultaneously
H
Heating or heating/cooling control
H
Water-resistant construction (NEMA 4X,
equivalent to IP66)
H
Conforms to UL, CSA, and IEC safety
standards as well as CE marking
H
3-year warranty
uC
Ordering Information
Optional communications and event input boards are shown on the following page.
J
STANDARD TEMPERATURE CONTROLLERS
Size
Power
Alarm points
Output
Part number
supply
voltage
Thermocouple input
Platinum RTD input
1/32 DIN
100 to
Relay
E5GN-RTC AC100-240
E5GN-RP AC100-240
48(W) x
240 VAC
Voltage (for driving SSR)
E5GN-QTC AC100-240
E5GN-QP AC100-240
24 (H) x
100(D) mm
1 (See Note 1)
Relay
E5GN-R1TC AC100-240
E5GN-R1P AC100-240
100(D) mm
Voltage (for driving SSR)
E5GN-Q1TC AC100-240
E5GN-Q1P AC100-240
24 V
Relay
E5GN-RTC AC/DC24
E5GN-RP AC/DC24
AC/DC
Voltage (for driving SSR)
E5GN-QTC AC/DC24
E5GN-QP AC/DC24
1 (See Note 1)
Relay
E5GN-R1TC AC/DC24
E5GN-R1P AC/DC24
Voltage (for driving SSR)
E5GN-Q1TC AC/DC24
E5GN-Q1P AC/DC24
Note: 1. If the heating/cooling function is used, ALM1 will be used for control output; the alarm output will not be available.
2. Control output 2 for heating/cooling control is a relay output
J
TEMPERATURE CONTROLLERS WITH COMMUNICATIONS
Size
Power
Communication
Output
Part number
supply
voltage
type
Thermocouple input
Platinum RTD input
1/32 DIN
100 to
RS-485
Relay
E5GN-R03TC-FLK AC100-240
E5GN-R03P-FLK AC100-240
48(W) x
240 VAC
Voltage (for driving SSR)
E5GN-Q03TC-FLK AC100-240
E5GN-Q03P-FLK AC100-240
24 (H) x
100(D) mm
24 V
Relay
E5GN-R03TC-FLK AC/DC24
E5GN-R03P-FLK AC/DC24
100(D) mm
AC/DC
Voltage (for driving SSR)
E5GN-Q03TC-FLK AC/DC24
E5GN-Q03P-FLK AC/DC24
E5GN
E5GN
68
J
INPUT RANGES
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100
200
Pt100
JPt100
Input type
Platinum resistance thermometer
Name
850
Applicable standards by input type are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C1604-1989, JIS C1606-1989
Pt100: JIS C1604-1997, IEC751
Set value
1
2
3
4
200
500.0
199.9
100.0
0.0
500.0
199.9
100.0
0.0
0
Thermocouple
ES1A Non-contact
Temperature Sensor
Analog input
Usable in the
following
ranges by
scaling:
1999 to 9999
or 199.9 to
999.9
0 to 50 mV
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100
200
Input type
Name
K
J
T
E
L
U
N
R
S
B
K10 to
70
C
K60 to
120
C
K115 to
165
C
K160 to
260
C
Set value
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
200
500.0
20.0
1300
850
100
400.0
20.0
400
200
600
0
850
100
400
200
1300
200
1700
0
1700
0
1800
100
70
0
120
0
165
0
260
0
0
17
400.0
199.9
18
400.0
199.9
Note: Lightly shaded ranges indicate default settings.
E5GN
E5GN
69
Specifications
J
RATINGS
Supply voltage
100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz/24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
7 VA
4 VA/2.5 W
Sensor input
Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: 10 to 70
_
C, 60 to 120
_
C, 115 to 165
_
C, 160 to 260
_
C
Voltage input: 0 to 50 mV
Control output
Relay output
SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations
Voltage output
12 VDC
+15%
/
20%
(PNP), max. load current: 21 mA, with short-circuit protection circuit
Alarm output
SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations
Control method
PID or ON/OFF control
Setting method
Digital setting using front panel keys
Indication method
7-segment digital display and single-lighting indicator
Character height: PV: 7.0 mm; SV: 3.5 mm
Ambient operating temperature
10
_
C to 55
_
C (14
F to 131
F) with no condensation or icing
Storage temperature
25
_
C to 65
_
C (13
F to 149
F) with no condensation or icing
Ambient humidity
25% to 85% RH
J
CHARACTERISTICS
Indication accuracy
Thermocouple:
0.5% of indicated value or
1
_
C, whichever greater,
1 digit max. (See Note)
Platinum resistance thermometer:
0.5% of indicated value or
1
_
C, whichever greater,
1 digit max.
Analog input:
0.5% FS
1 digit max.
CT input:
5% FS
1 digit max.
Hysteresis
0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band (P)
0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I)
0 to 3999 s (in units of 1 s)
Derivative time (D)
0 to 3999 s (in units of 1 s)
Control period
1 to 99 s (in units of 1 s)
Manual reset value
0.0% to 100.0% (in units of 0.1%)
Alarm setting range
-1999 to 9999 (decimal point position depends on input type)
Sampling period
500 ms
Insulation resistance
20 M
min. at 500 VDC
Dielectric strength
2000 VAC, 50 or 60 Hz for 1 min between different charging terminals
Vibration resistance
10 to 55 Hz, 10 m/s
2
for 2 hours each in X, Y and Z directions
Shock resistance
300 m/s
2
, 3 times each in 3 axes, 6 directions (relay: 100 m/s
2
)
Weight
Approx. 90 g; mounting bracket: Approx. 10 g
Protective structure
Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
Memory protection
EEPROM non-volatile memory (number of writes: 100,000)
Note:
The indication of K thermocouples in the -200 to 1300
C range, and T and N thermocouples at a temperature of -100
C or less, and U
and L thermocouples at any temperature is
2
C
1 digit maximum. The indication of B thermocouples at a temperature of 400
C or
less is unrestricted.
The indication of R and S thermocouples at a temperature of 200
C or less is
3
C
1 digit maximum.
(This table continues on the next page.)
E5GN
E5GN
70
Specifications Table
continued from previous page
EMC
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance:
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards
UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1)
J
COMMUNICATIONS SPECIFICATIONS
Transmission path connection
Multiple points
Communications method (See Note)
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Baud rate
1,200/2,400/4,800/9,600/19,200 bps
Transmission code
ASCII
Data bit length (See Note)
7 or 8 bits
Stop bit length (See Note)
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSMAC WAY
Block check character (BCC): with CompoWay/F
Flow control
Not available
Interface (See Note)
RS-485
Retry function
Not available
Communications buffer
40 bytes
Note: The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
Nomenclature
CMW
STP
OUT
Temperature unit
No.1 display
Level key
Operation in-
dicators
No.2 display
Up key
Mode key
Down key
E5GN
E5GN
71
Dimensions
Unit: mm (inch)
Panel Cutout
* When carrying out maintenance on the E5GN, only the
terminal plate can be drawn out with the terminal leads still
attached.
48 (1.89)
36.8
(1.45)
3
(0.12)
100 (3.94)
44.8 (1.76)
48
number of units 2.5
(1.89
number of units 0.10)
60 (2.36) min.
60
(2.36)
min.
+1.0
+0.3
0
0
+0.3
0
Mounted Separately
Insert the Controller through the hole in the panel from the front and
push the adapter on from the rear. Push the adapter up to the back
of the panel ensuring that the controller is pushed all the way in,
removing any gap between the Controller, panel, and adapter.
Finally, use the two screws on the adapter to secure the unit in
place.
To mount the E5GN so that it is waterproof, insert the waterproof
packing onto the E5GN.
When two or more E5GN Controllers are mounted, make sure that
the surrounding temperature does not exceed the allowable
operating temperature ranges in the specifications.
Group Mounted
Mounting separately does not allow waterproofing.
22
(0.87)
22
(0.87)
45
(1.77)
22
(0.87)
0
24
(0.94)
35
(1.38)
22
(0.87)
+0.6