ChipFind - документация

Электронный компонент: R2051Kxx

Скачать:  PDF   ZIP
'03.07.09
12345
I
2
C-Bus Real-Time Clock ICs
with Battery Backup switch-over Function
R2051 Series
12345
Rev.2.05 - 1 -
s
OUTLINE
The R2051 is a CMOS real-time clock IC connected to the CPU by two signal lines, SCL and SDA, and
configured to perform serial transmission of time and calendar data to the CPU. Further, battery backup
switchover circuit and a voltage detector. The periodic interrupt circuit is configured to generate interrupt signals
with six selectable interrupts ranging from 0.5 seconds to 1 month. The 2 alarm interrupt circuits generate
interrupt signals at preset times. As the oscillation circuit is driven under constant voltage, fluctuation of the
oscillator frequency due to supply voltage is small, and the time keeping current is small (TYP. 0.4
A at 3V). The
oscillation halt sensing circuit can be used to judge the validity of internal data in such events as power-on; The
supply voltage monitoring circuit is configured to record a drop in supply voltage below two selectable supply
voltage monitoring threshold settings. The 32.768kHz clock output function (CMOS output) is intended to output
sub-clock pulses for the external microcomputer. The oscillation adjustment circuit is intended to adjust time
counts with high precision by correcting deviations in the oscillation frequency of the crystal oscillator. Battery
backup switchover function is the automatic switchover circuit between a main power supply and a backup battery
of primary or secondary battery. Switchover is executed by monitoring the voltage of a main power supply,
therefore the voltage of a backup battery voltage is not relevant. Since the package for these ICs is SSOP16
(5.0x6.4x1.25: R2051Sxx) and FFP12 (2.0x2.0x1.0: R2051Kxx), high density mounting of ICs on boards is
possible.
s
FEATURES
q
Minimum Timekeeping supply voltage Typ. 0.75V (Max. 1.00V); VDD pin
q
Low power consumption
0.4
A TYP (1.0
A MAX.)
at VDD=3V
q
Built-in Backup switchover circuit (can be used for a primary battery, a secondary battery, or an electric double
layer capacitor)
q
Only two signal lines (SCL and SDA) required for connection to the CPU. ( I
2
C-Bus Interface, 400kHz)
q
Time counters (counting hours, minutes, and seconds) and calendar counters (counting years, months, days,
and weeks) (in BCD format)
q
Interrupt circuit configured to generate interrupt signals (with interrupts ranging from 0.5 seconds to 1 month) to
the CPU and provided with an interrupt flag and an interrupt halt
q
2 alarm interrupt circuits (Alarm_W for week, hour, and minute alarm settings and Alarm_D for hour and minute
alarm settings)
q
Built-in voltage detector with delay
q
With Power-on flag to prove that the power supply starts from 0V
q
32-kHz clock output pin (CMOS output. "H" level is always equal to VCC.)
q
Supply voltage monitoring circuit with two supply voltage monitoring threshold settings
q
Automatic identification of leap years up to the year 2099
q
Selectable 12-hour and 24-hour mode settings
q
High precision oscillation adjustment circuit
q
Built-in oscillation stabilization capacitors (CG and CD)
q
CMOS process
q
Package SSOP16 (5.0mm x 6.4mm x 1.25mm : R2051Sxx), FFP12 (2.0mm x 2.0mm x 1.0mm : R2051Kxx)
s
PIN CONFIGURATION
CLKOUT
SCL
VCC
NC
NC
1
2
3
4
5
6
7
9
TOP VIEW
R2051Sxx(SSOP16)
VSB
13
15
SDA
NC
/VDCC
NC
VDD
/INTR
10
11
12
14
OSCIN
CIN
8
16
VSS
OSCOUT
VDD
VCC
SD
A
VSS
10
11
12
1
2
3
4
TOP VIEW
R2051Kxx(FFP12)
7
VSB
/VDCC
SCL
CL
KOU
T
CIN
5
6
9
8
OSCI
N
OSCOUT
/INT
R
R2051 Series

12345
Rev.2.05 - 2 -
s
BLOCK DIAGRAM
OSCOUT
VSS
VDD
/INTR
CPU POWER
SUPLLY
OSCIN
VCC
VSB

CPU
REAL
TIME
CLOCK
SDA
SCL
C3
BATTERY
VOLTAGE
MONITOR
/VDCC
VOLTAGE
DETECTOR
SW1
SW2
CLKOUT
C2
R1
LE
V
E
L
SH
IF
TER
DELAY
CIN
VOLTAGE
REFERENCE
C1
s
SELECTION GUIDE
In the R2051xxx Series, output voltage and options can be designated.

Part Number is designated as follows:
R2051K01-E2
Part Number
R2051abb-cc
Code Description
a
Designation of the package.
K: FFP12
S: SSOP16
bb
Serial number of Voltage detector setting etc.
cc
Designation of the taping type. Only E2 is available.

*) I
2
C-Bus is a trademark of PHILIPS N.V.
Purchase of I
2
C-Bus components of Ricoh Company, LTD. conveys a license under the Philips I
2
C Patent
Rights to use these components in an I
2
C system, provided that the system conforms to the I
2
C standard
Specifications as defined by Philips.
Part Number
Package
-VDET1 (switch-over threshold)
DC Electrical Characteristics
R2051K01-E2 FFP12
2.40(Typ.)
P.5
R2051K02-E2 FFP12
2.80(Typ.)
P.6
R2051S01-E2 SSOP16
2.40(Typ.)
P.5
R2051S03-E2
(Preliminary)
SSOP16 4.00(Typ.)
P.7
R2051 Series
12345
Rev.2.05 - 3 -
s
PIN DESCRIPTION
Symbol Item
Description
SCL Serial
Clock Line
The SCL pin is used to input clock pulses synchronizing the input and output
of data to and from the SDA pin. Allows a maximum input voltage of 5.5
volts regardless of supply voltage.
SDA Serial
Data Line
The SDA pin is used to input or output data intended for writing or reading in
synchronization with the SCL pin. Up to 5.5v beyond VDD may be input.
This pin functions as an Nch open drain output.
/INTR Interrupt
Output
The /INTR pin is used to output alarm interrupt (Alarm_W) and alarm
interrupt (Alarm_D) and output periodic interrupt signals to the CPU signals.
Disabled at power-on from 0V. Nch. open drain output.
CLKOUT 32kHz
Clock
Output
The CLKOUT pin is used to output 32.768-kHz clock pulses. CMOS output.
"H" level is always equal to VCC.
VCC Main
Battery
input
Supply power to the IC.
VSB Power
Supply
Input for Backup
Battery
Connect a primary battery for backup. Normally, power is supplied from VCC
to the IC. If VCC level is equal or less than VDET1, power is supplied from
this pin.
OSCIN
OSCOUT
Oscillation
Circuit
Input / Output
The OSCIN and OSCOUT pins are used to connect the 32.768-kHz crystal
oscillator (with all other oscillation circuit components built into the R2051).
VDD
Positive Power
Supply Input
The VDD pin is connected to the power supply. Connect a capacitor as much
as 0.1
F between VDD and VSS. In the case of using a secondary battery,
connecting the secondary battery to this pin is possible.
/VDCC VCC
Power
Supply Monitoring
Result Output
While monitoring VCC Power supply, if the voltage is equal or lower than
VDET1, this output level is "L". When /VDCC becomes "L", SW1 turns off
and SW2 turns on. As a result, power is supplied from VSB pin to the
internal real time clock. When VCC is equal to +VDET1 or more, SW1 turns
on and SW2 turns off. After t DELAY passed, /VDCC output becomes off, or
"H".
Nch Open-drain output.
CIN
Noise Bypass Pin
To stabilize the internal reference, connect a capacitor as much as 0.1uF
between this pin and VSS.
VSS Negative
Power
Supply Input
The VSS pin is grounded.

R2051 Series

12345
Rev.2.05 - 4 -
s
ABSOLUTE MAXIMUM RATINGS
(VSS=0V)
Symbol Item
Pin
Name
Description
Unit
VCC
Supply Voltage 1
VCC
-0.3 to +6.5
V
VDD
Supply Voltage 2
VDD
-0.3 to +6.5
V
VSB
Supply Voltage 3
VSB
-0.3 to +6.5
V
Input Voltage 1
SCL, SDA
-0.3 to +6.5
V
VI
Input Voltage 2
CIN
-0.3 to VDD+0.3
V
Output Voltage 1
/INTR, /VDCC
-0.3 to +6.5
V
VO
Output Voltage 2
CLKOUT
-0.3 to VCC+0.3
V
IOUT
Maximum Output Current
VDD
10
mA
PD Power
Dissipation Topt = +25
C
300 mW
Topt
Operating Temperature
-40 to +85
C
Tstg
Storage Temperature
-55 to +125
C

s
RECOMMENDED OPERATING CONDITIONS
(VSS=0V,
Topt=-40
to
+85
C)
Symbol Item
Pin
Name
Min,
Typ. Max. Unit
Vaccess Supply
Voltage
VCC power supply
voltage for interfacing
with CPU
-VDET1
*1)
5.5
V
VCLK Minimum
Timekeeping
Voltage
CGout,CDout=0pF
*2), *3)
0.75
1.00
V
fXT Oscillation
Frequency
32.768
kHz
VPUP
Pull-up Voltage
/INTR, /VDCC
5.5
V
*1) -VDET1 in Vaccess specification is guaranteed by design.
*2) CGout is connected between OSCIN and VSS, CDout is connected between OSCOUT and VSS.
R2051 series incorporates the capacitors between OSCIN and VSS, between OSCOUT and VSS.
Then normally, CGout and CDout are not necessary.
*3) Crystal oscillator: CL=6-8pF, R1=30K

R2051 Series
12345
Rev.2.05 - 5 -
s
DC ELECTRICAL CHARACTERISTICS
q
R2051K01, R2051S01)
(Unless otherwise specified: VSS=0V,VCC=VSB=3.0V, 0.1uF between VDD and VSS, CIN and VSS,
Topt=-40 to +85
C)
Symbol Item
Pin
Name Conditions
Min. Typ. Max. Unit
VIH
"H" Input Voltage
0.8x
VCC
5.5
VIL
"L" Input Voltage
SCL,SDA
-0.3
0.2x
VCC

V
IOH "H"
Output
Current
CLKOUT
VOH=VCC-0.5V -0.5
mA
IOL1 CLKOUT
0.5
IOL2 /INTR 2.0
IOL4 SDA
VOL=0.4V
3.0
IOL3
"L" Output
Current
/VDCC VDD,VSB,VCC=2.0V
VOL=0.4V
0.5

mA
IIL Input
Leakage
Current
SCL
VI=5.5V or VSS
-1.0
1.0
A
IOZ1 Output
Off-state
Current 1
SDA
VO=5.5V or VSS
-1.0
1.0
A
IOZ2 Output
Off-state
Current 2
/INTR,
/VDCC
VO=5.5V or VSS
-1.0
1.0
A
ISB
Time Keeping Current
at Backup mode
VSB VCC=0V,
VSB=3.0V,
VDD, Output=OPEN
Time keeping
0.4
1.0
A
ISBL
Leakage Current of
Backup pin at
VCC_on
VSB VCC=3.0V,
VSB=5.5V or 0V,
VDD, Output=OPEN
-1.00
1.00
A
VDETH Supply
Voltage
Monitoring Voltage "H"
VSB
Topt=+25
C
1.90 2.10 2.30 V
VDETL Supply
Voltage
Monitoring Voltage "L"
VDD
Topt=+25
C
1.20 1.35 1.50 V
-VDET1 Detector
Threshold
Voltage
(falling edge of VCC)
VCC
Topt=+25
C
2.34 2.40 2.46 V
+VDET1 Detector
Released
Voltage (rising edge of
VCC)
VCC
Topt=+25
C
2.44 2.52 2.60 V
VDET
Topt
Detector Threshold
and Released Voltage
Temperature
coefficient
VCC,
VSB
Topt=-40 to +85
C
*1)
100
ppm
/
C
VDD
OUT1
VDD Output
Voltage 1
VDD
Topt=+25
C,
VCC=3.0V, Iout=1.0mA
VCC
-0.12
VCC
-0.04
V
VDD
OUT2
VDD Output
Voltage 2
VDD
Topt=+25
C,
VCC=2.0V, VSB=3.0V,
Iout=0.1mA
VSB
-0.08
VSB
-0.02
V
CG Internal
Oscillation
Capacitance 1
OSCIN
10
CD Internal
Oscillation
Capacitance 2
OSCOUT
10
pF
*1) Guaranteed by design.
R2051 Series

12345
Rev.2.05 - 6 -
q
R2051K02
(Unless otherwise specified: VSS=0V,VCC=3.3V, VSB=3.0V, 0.1uF between VDD and VSS, CIN and VSS,
Topt=-40 to +85
C)
Symbol Item
Pin
Name Conditions
Min. Typ. Max. Unit
VIH
"H" Input Voltage
0.8x
VCC
5.5
VIL
"L" Input Voltage
SCL,SDA
-0.3
0.2x
VCC

V
IOH "H"
Output
Current
CLKOUT
VOH=VCC-0.5V -0.5
mA
IOL1 CLKOUT
0.5
IOL2 /INTR 2.0
IOL4 SDA
VOL=0.4V
3.0
IOL3
"L" Output
Current
/VDCC VDD,VSB,VCC=2.0V
VOL=0.4V
0.5

mA
IIL Input
Leakage
Current
SCL
VI=5.5V or VSS
-1.0
1.0
A
IOZ1 Output
Off-state
Current 1
SDA
VO=5.5V or VSS
-1.0
1.0
A
IOZ2 Output
Off-state
Current 2
/INTR,
/VDCC
VO=5.5V or VSS
-1.0
1.0
A
ISB
Time Keeping Current
at Backup mode
VSB VCC=0V,
VSB=3.0V,
VDD, Output=OPEN
Time keeping
0.4
1.0
A
ISBL
Leakage Current of
Backup pin at
VCC_on
VSB VCC=3.3V,
VSB=5.5V or 0V,
VDD, Output=OPEN
-1.00
1.00
A
VDETH Supply
Voltage
Monitoring Voltage "H"
VSB
Topt=+25
C
1.90 2.10 2.30 V
VDETL Supply
Voltage
Monitoring Voltage "L"
VDD
Topt=+25
C
1.20 1.35 1.50 V
-VDET1 Detector
Threshold
Voltage
(falling edge of VCC)
VCC
Topt=+25
C
2.73 2.80 2.87 V
+VDET1 Detector
Released
Voltage (rising edge of
VCC)
VCC
Topt=+25
C
2.85 2.94 3.03 V
VDET
Topt
Detector Threshold
and Released Voltage
Temperature
coefficient
VCC,
VSB
Topt=-40 to +85
C
*1)
100
ppm
/
C
VDD
OUT1
VDD Output
Voltage 1
VDD
Topt=+25
C,
VCC=3.3V, Iout=1.0mA
VCC
-0.12
VCC
-0.04
V
VDD
OUT2
VDD Output
Voltage 2
VDD
Topt=+25
C,
VCC=2.0V, VSB=3.3V,
Iout=0.1mA
VSB
-0.08
VSB
-0.02
V
CG Internal
Oscillation
Capacitance 1
OSCIN
10
CD Internal
Oscillation
Capacitance 2
OSCOUT
10
pF
*1) Guaranteed by design.
R2051 Series
12345
Rev.2.05 - 7 -
q
R2051S03 (Preliminary)
(Unless otherwise specified: VSS=0V, VCC=5.0V, VSB=3.0V, 0.1uF between VDD and VSS, CIN and VSS,
Topt=-40 to +85
C)
Symbol Item
Pin
Name Conditions
Min. Typ. Max. Unit
VIH
"H" Input Voltage
0.8x
VCC
5.5
VIL
"L" Input Voltage
SCL,SDA
-0.3
0.2x
VCC

V
IOH "H"
Output
Current
CLKOUT
VOH=VCC-0.5V -0.5
mA
IOL1 CLKOUT
0.5
IOL2 /INTR 2.0
IOL4 SDA
VOL=0.4V
3.0
IOL3
"L" Output
Current
/VDCC VDD,VSB,VCC=2.0V
VOL=0.4V
0.5

mA
IIL Input
Leakage
Current
SCL
VI=5.5V or VSS
-1.0
1.0
A
IOZ1 Output
Off-state
Current 1
SDA
VO=5.5V or VSS
-1.0
1.0
A
IOZ2 Output
Off-state
Current 2
/INTR,
/VDCC
VO=5.5V or VSS
-1.0
1.0
A
ISB
Time Keeping Current
at Backup mode
VSB VCC=0V,
VSB=3.0V,
VDD, Output=OPEN
Time keeping
0.4
1.0
A
ISBL
Leakage Current of
Backup pin at
VCC_on
VSB VCC=5.0V,
VSB=5.5V or 0V,
VDD, Output=OPEN
-1.00
1.00
A
VDETH Supply
Voltage
Monitoring Voltage "H"
VSB
Topt=+25
C
1.90 2.10 2.30 V
VDETL Supply
Voltage
Monitoring Voltage "L"
VDD
Topt=+25
C
1.20 1.35 1.50 V
-VDET1 Detector
Threshold
Voltage
(falling edge of VCC)
VCC
Topt=+25
C
3.90 4.00 4.10 V
+VDET1 Detector
Released
Voltage (rising edge of
VCC)
VCC
Topt=+25
C
4.07 4.20 4.33 V
VDET
Topt
Detector Threshold
and Released Voltage
Temperature
coefficient
VCC,
VSB
Topt=-40 to +85
C
*1)
100
ppm
/
C
VDD
OUT1
VDD Output
Voltage 1
VDD
Topt=+25
C,
VCC=5.0V, Iout=1.0mA
VCC
-0.12
VCC
-0.04
V
VDD
OUT2
VDD Output
Voltage 2
VDD
Topt=+25
C,
VCC=2.0V, VSB=3.0V,
Iout=0.1mA
VSB
-0.08
VSB
-0.02
V
CG Internal
Oscillation
Capacitance 1
OSCIN
10
CD Internal
Oscillation
Capacitance 2
OSCOUT
10
pF
*1) Guaranteed by design.
R2051 Series

12345
Rev.2.05 - 8 -
s
AC ELECTRICAL CHARACTERISTICS
Unless otherwise specified: VSS=0V,Topt=-40 to +85
C
Input and Output Conditions: VIH=0.8
VCC,VIL=0.2
VCC,VOH=0.8
VCC,VOL=0.2
VCC,CL=50pF
VCC
1.7V *1)
VCC
2.5V *1)
Sym
-bol
Item
Condi-
Tions
Min. Typ. Max. Min. Typ. Max.
Unit
f
SCL
SCL
Clock
Frequency
100
400
kHz
t
LOW
SCL
Clock
Low
Time
4.7
1.3
s
t
HIGH
SCL
Clock
High
Time
4.0
0.6
s
t
HD;STA
Start
Condition
Hold
Time
4.0
0.6
s
t
SU;STO
Stop Condition Set Up
Time
4.0
0.6
s
t
SU;STA
Start Condition Set Up
Time
4.7
0.6
s
t
SU;DAT
Data
Set
Up
Time 250
200
ns
t
HD;DAT
Data
Hold
Time
0 0 ns
t
PL;DAT
SDA "L" Stable Time
After Falling of SCL
2.0
0.9
s
t
PZ;DAT
SDA off Stable Time
After Falling of SCL
2.0
0.9
s
t
R
Rising Time of SCL and
SDA (input)
1000
300
ns
t
F
Falling Time of SCL
and SDA (input)
300
300
ns
t
SP
Spike Width that can
be removed with Input
Filter
50
50
ns
t
RCV
Recovery
Time
from
Stop Condition to Start
Condition
62
62
s
t
DELAY
Output Delay Time of
Voltage Detector
Time
Keeping
100 105 110 100 105 110 ms
*1) VCC voltage interfacing with CPU is defined by Vaccess (P.4
s
RECOMMENDED OPERATING CONDITIONS)
*) For reading/writing timing, see "P.31
s
Interfacing with the CPU
q
Data Transmission under Special Condition".
SDA(OUT)
SCL
S
Sr
P
t
PZ;DAT
t
HIGH
t
SU;DAT
t
HD;STA
t
SP
t
SU;STO
t
LOW
t
SU;STA
SDA(IN)
t
HD;STA
t
PL;DAT
Sr
P
Stop Condition
S
Start Condition
Repeated Start Condition
t
HD;DAT
R2051 Series
12345
Rev.2.05 - 9 -
/VDCC
VCC
t
DELAY
+VDET1
R2051 Series

12345
Rev.2.05 - 10 -
s
PACKAGE DIMENSIONS
q
R2051Kxx
9 7
6
4
3
1
10
12
1PIN INDEX
2.0
0.1
0.2
0.15
0.35
2.0
0.1
2PIN INDEX
0.5
0.3
0.15
0.103
0.25
0.35
1.0Max
0.27
0.15
(BOTTOM VIEW)
0.5
0.05
0.17
0.1
unit: mm
R2051 Series
12345
Rev.2.05 - 11 -
q
R2051Sxx

16
9
1
M
8
4.4
0.2
6.4
0.3
0.5
0.3
0.225typ
0.65
0 to 10
0.1
0.1
0.10
0.15
0.22
0.15
+0.1
-0.05
5.0
0.3
1.15
0.1
+0.1
-0.05
unit: mm
R2051 Series

12345
Rev.2.05 - 12 -
s
GENERAL DESCRIPTION
q
Battery Backup Switchover Function
The R2051 has two power supply input, or VCC and VSB. With monitoring input voltage of VCC pin by internal
Voltage Detector, it is selected which power supply of VCC or VSB is used for the internal power source.

Refer to the next table to see the state of the backup battery and internal power supply's state of the IC by each
condition.
VCC
VDET1 VCC
<
VDET1
VCC
RTC, VDD
/VDCC=OFF(H)
VSB
RTC, VDD
/VDCC=L

As a backup battery, not only a primary battery such as CR2025, LR44, or a secondary battery such as ML614,
TC616, but also an electric double layered capacitor or an aluminum capacitor can be used. Switchover point is
judged with the voltage of the main power (VCC), therefore, if the backup voltage is higher than main supply
voltage, switchover can be realized without extra load to the backup power supply.
VDD
VSB
VCC
VSS
0.1
F
CPU Power
Supply
The case of back-up by
primary battery
CR2025
etc.
VSB
VDD
VCC
VSS
0.1
F
CPU power
supply
ML614
etc.
The case of back-up by
capacitor or secondary battery
(Charging voltage is equal to CPU
power supply voltage)
VSB
VDD
VCC
VSS
0.1
F
CPU power
supply
(3V)
5V
Double layer
capacitor
etc.
The case of back-up by
capacitor or secondary battery
(Charging voltage is not equal to
CPU power supply voltage)
q
Interface with CPU
The R2051 is connected to the CPU by two signal lines SCL and SDA, through which it reads and writes data
from and to the CPU. Since the output of the I/O pin of SDA is open drain, data interfacing with a CPU different
supply voltage is possible by applying pull-up resistors on the circuit board. The maximum clock frequency of
400kHz (at VDD=3V) of SCL enables data transfer in I2C-Bus fast mode. VCC falls down under -VDET1, the
R2051 stops accessing with CPU.
q
Clock and Calendar Function
The R2051 reads and writes time data from and to the CPU in units ranging from seconds to the last two digits of
the calendar year. The calendar year will automatically be identified as a leap year when its last two digits are a
multiple of 4. Consequently, leap years up to the year 2099 can automatically be identified as such.
*) The year 2000 is a leap year while the year 2100 is not a leap year.
R2051 Series
12345
Rev.2.05 - 13 -
q
Alarm Function
The R2051 incorporates the alarm interrupt circuit configured to generate interrupt signals to the CPU at preset
times. The alarm interrupt circuit allows two types of alarm settings specified by the Alarm_W registers and the
Alarm_D registers. The Alarm_W registers allow week, hour, and minute alarm settings including combinations of
multiple day-of-week settings such as "Monday, Wednesday, and Friday" and "Saturday and Sunday". The
Alarm_D registers allow hour and minute alarm settings. The Alarm_W outputs from /INTR pin, and the Alarm_D
outputs also from /INTR pin. Each alarm function can be checked from the CPU by using a polling function.
q
High-precision Oscillation Adjustment Function
The R2051 has built-in oscillation stabilization capacitors (CG and CD), that can be connected to an external
crystal oscillator to configure an oscillation circuit. Two kinds of accuracy for this function are alternatives. To
correct deviations in the oscillator frequency of the crystal, the oscillation adjustment circuit is configured to allow
correction of a time count gain or loss (up to
1.5ppm or
0.5ppm at 25
C) from the CPU. The maximum range is
approximately
189ppm (or
63ppm) in increments of approximately 3ppm (or 1ppm). Such oscillation
frequency adjustment in each system has the following advantages:
* Allows timekeeping with much higher precision than conventional RTCs while using a crystal oscillator
with a wide range of precision variations.
* Corrects seasonal frequency deviations through seasonal oscillation adjustment.
* Allows timekeeping with higher precision particularly with a temperature sensing function out of RTC,
through oscillation adjustment in tune with temperature fluctuations.
q
Power-on Reset, Oscillation Halt Sensing Function and Supply Voltage Monitoring Function
The R2051 has 3 power supply pins (VCC, VSB, VDD), among them, VCC pin and VDD pin have
monitoring function of supply voltage. VCC power supply monitoring circuit makes /VDCC pin "L" when VCC
power supply pin becomes equal or lower than VDET1. At the power-on of VDD, this circuit makes /VDCC pin
turn off, or "H" after the delay time, tDELAY from when the VCC power supply pin becomes equal or more than
+VDET1.
The R2051 incorporates an oscillation halt sensing circuit equipped with internal registers configured to record
any past oscillation halt, the oscillation halt sensing circuit, VDD monitoring flag, and power-on reset flag are
useful for judging the validity of time data.

Power on reset function reset the control resisters when the system is powered on from 0V. At the same time, the
fact is memorized to the resister as a flag, thereby identifying whether they are powered on from 0V or battery
backed-up.

The R2051 also incorporates a supply voltage monitoring circuit equipped with internal registers configured to
record any drop in supply voltage below a certain threshold value. Supply voltage monitoring threshold settings
can be selected between 2.1V and 1.35V through internal register settings. The sampling rate is normally 1s. The
oscillation halt sensing circuit is configured to confirm the established invalidation of time data in contrast to the
supply voltage monitoring circuit intended to confirm the potential invalidation of time data. Further, the supply
voltage monitoring circuit can be applied to battery supply voltage monitoring.
q
Periodic Interrupt Function
The R2051 incorporates the periodic interrupt circuit configured to generate periodic interrupt signals aside from
interrupt signals generated by the periodic interrupt circuit for output from the /INTR pin. Periodic interrupt signals
have five selectable frequency settings of 2 Hz (once per 0.5 seconds), 1 Hz (once per 1 second), 1/60 Hz (once
per 1 minute), 1/3600 Hz (once per 1 hour), and monthly (the first day of every month). Further, periodic
interrupt signals also have two selectable waveforms, a normal pulse form (with a frequency of 2 Hz or 1 Hz) and
special form adapted to interruption from the CPU in the level mode (with second, minute, hour, and month
interrupts). The condition of periodic interrupt signals can be monitored with using a polling function.
q
32kHz Clock Output
The R2051 incorporates a 32-kHz clock circuit configured to generate clock pulses with the oscillation frequency
of a 32.768kHz crystal oscillator for output from the CLKOUT pin (CMOS push-pull output). The 32-kHz clock
output is always enabled and the "H" level of the CLKOUT pin is same as VCC power supply.
R2051 Series

12345
Rev.2.05 - 14 -
s
Address Mapping

Address
Register Name
D a t a
A3A2A1A0
D7 D6 D5 D4 D3 D2
D1 D0
0 0
0
0
0 Second
Counter
-
*2)
S40 S20 S10 S8 S4 S2 S1
1 0
0
0
1 Minute
Counter
-
M40 M20 M10 M8 M4 M2 M1
2 0
0
1
0
Hour
Counter
- - H20
P
/A
H10 H8 H4
H2 H1
3 0
0
1
1
Day-of-week
Counter
- - - - - W4
W2
W1
4 0
1
0
0
Day-of-month
Counter
- - D20
D10
D8
D4
D2
D1
5 0
1
0
1
Month Counter and
Century Bit
/19
20
- - MO10
MO8
MO4
MO2
MO1
6 0
1
1
0 Year
Counter
Y80 Y40 Y20 Y10 Y8 Y4 Y2 Y1
7 0
1
1
1 Oscillation
Adjustment
Register *3)
DEV
*4)
F6 F5 F4 F3 F2
F1 F0
8 1
0
0
0 Alarm_W
(Minute Register)
-
WM40 WM20 WM10 WM8 WM4 WM2 WM1
9 1
0
0
1 Alarm_W
(Hour Register)
- -
WH20
WP
/ A
WH10
WH8 WH4 WH2 WH1
A 1
0
1
0 Alarm_W
(Day-of-week
Register)
-
WW6 WW5 WW4 WW3 WW2 WW1 WW0
B 1
0
1
1 Alarm_D
(Minute Register)
-
DM40
DM20
DM10
DM8 DM4
DM2 DM1
C 1
1
0
0 Alarm_D
(Hour Register)
- - DH20
DP
/A
DH10 DH8 DH4
DH2 DH1
D 1
1
0
1
- - - - - -
- -
E 1
1
1
0
Control Register 1 *3) WALE
DALE
/12
24
SCRA
TCH2
TEST CT2 CT1 CT0
F 1
1
1
1
Control Register 2 *3)
VDSL
VDET
/XST
PON
*5)
SCRA
TCH1
CTFG WAFG DAFG

Notes:
* 1) All the data listed above accept both reading and writing.
* 2) The data marked with "-" is invalid for writing and reset to 0 for reading.
* 3) When the PON bit is set to 1 in Control Register 2, all the bits are reset to 0 in Oscillation Adjustment
Register, Control Register 1 and Control Register 2 excluding the /XST bit.
* 4) When DEV=0, the oscillation adjustment circuit is configured to allow correction of a time count gain or
loss up to
1.5ppm.
When DEV=1, the oscillation adjustment circuit is configured to allow correction of a time count gain or
loss up to or
0.5ppm.
* 5) PON is a power-on-reset flag.
R2051 Series
12345
Rev.2.05 - 15 -
s
Register Settings
q
Control Register 1 (ADDRESS Eh)
D7 D6 D5 D4 D3 D2 D1 D0
WALE DALE /12
24
SCRA
TCH2
TEST
CT2 CT1 CT0 (For
Writing)
WALE DALE /12
24
SCRA
TCH2
TEST
CT2 CT1 CT0 (For
Reading)
0 0 0 0 0 0 0 0 Default
Settings
*)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.
(1) WALE, DALE Alarm_W Enable Bit, Alarm_D Enable Bit
WALE,DALE Description
0
Disabling the alarm interrupt circuit (under the control of the settings
of the Alarm_W registers and the Alarm_D registers).
(Default)
1
Enabling the alarm interrupt circuit (under the control of the settings
of the Alarm_W registers and the Alarm_D registers)
(2) /12
24
/12-24-hour Mode Selection Bit
/12
24
Description
0
Selecting the 12-hour mode with a.m. and p.m. indications.
(Default)
1
Selecting the 24-hour mode
Setting the /12
24 bit to 0 and 1 specifies the 12-hour mode and the 24-hour mode, respectively.
24-hour mode
12-hour mode
24-hour mode
12-hour mode
00 12
(AM12)
12 32
(PM12)
01
01 (AM 1)
13
21 (PM 1)
02
02 (AM 2)
14
22 (PM 2)
03
03 (AM 3)
15
23 (PM 3)
04
04 (AM 4)
16
24 (PM 4)
05
05 (AM 5)
17
25 (PM 5)
06
06 (AM 6)
18
26 (PM 6)
07
07 (AM 7)
19
27 (PM 7)
08
08 (AM 8)
20
28 (PM 8)
09
09 (AM 9)
21
29 (PM 9)
10 10
(AM10)
22 30
(PM10)
11
11 (AM11)
23
31 (PM11)
Setting the /12
24 bit should precede writing time data
(3) SCRATCH2
Scratch Bit 2
SCRATCH2 Description
0
(Default)
1
The SCRATCH2 bit is intended for scratching and accepts the reading and writing of 0 and 1.
The SCRATCH2 bit will be set to 0 when the PON bit is set to 1 in the Control Register 1.
(4) TEST
Test Bit
TEST Description
0 Normal
operation
mode.
(Default)
1 Test
mode.
The TEST bit is used only for testing in the factory and should normally be set to 0.
R2051 Series

12345
Rev.2.05 - 16 -
(5) CT2, CT1, and CT0
Periodic Interrupt Selection Bits
Description
CT2 CT1 CT0
Wave form
mode
Interrupt Cycle and Falling Timing
0 0 0 -
OFF(H)
(Default)
0 0 1 -
Fixed
at
"L"
0 1 0 Pulse
Mode
*1)
2Hz (Duty50%)
0 1 1 Pulse
Mode
*1)
1Hz (Duty50%)
1 0 0 Level
Mode
*2)
Once per 1 second (Synchronized with
second counter increment)
1 0 1 Level
Mode
*2)
Once per 1 minute (at 00 seconds of
every minute)
1 1 0 Level
Mode
*2)
Once per hour (at 00 minutes and 00
seconds of every hour)
1 1 1 Level
Mode
*2)
Once per month (at 00 hours, 00
minutes,
and 00 seconds of first day of every
month)

* 1) Pulse Mode: 2-Hz and 1-Hz clock pulses are output in synchronization with the increment of the second
counter as illustrated in the timing chart below.
/INTR Pin
Rewriting of the second counter
CTFG Bit
Approx. 92
s
(Increment of second counter)

In the pulse mode, the increment of the second counter is delayed by approximately 92
s from the
falling edge of clock pulses. Consequently, time readings immediately after the falling edge of clock
pulses may appear to lag behind the time counts of the real-time clocks by approximately 1 second.
Rewriting the second counter will reset the other time counters of less than 1 second, driving the
/INTR pin low.

* 2) Level Mode: Periodic interrupt signals are output with selectable interrupt cycle settings of 1 second, 1
minute, 1 hour, and 1 month. The increment of the second counter is synchronized with the falling
edge of periodic interrupt signals. For example, periodic interrupt signals with an interrupt cycle
setting of 1 second are output in synchronization with the increment of the second counter as
illustrated in the timing chart below.
(Increment of
second counter)
Setting CTFG bit to 0
Setting CTFG bit to 0
(Increment of
second counter)
(Increment of
second counter)
CTFG Bit
/INTR Pin

*1), *2) When the oscillation adjustment circuit is used, the interrupt cycle will fluctuate once per 20sec. or
60sec. as follows:
Pulse Mode: The "L" period of output pulses will increment or decrement by a maximum of
3.784 ms. For
example, 1-Hz clock pulses will have a duty cycle of 50
0.3784%.
Level Mode: A periodic interrupt cycle of 1 second will increment or decrement by a maximum of
3.784 ms.
R2051 Series
12345
Rev.2.05 - 17 -
q
Control Register 2 (Address Fh)
D7 D6 D5 D4 D3 D2 D1 D0
VDSL VDET /XST PON SCRA
TCH1
CTFG WAFG DAFG (For
Writing)
VDSL VDET /XST PON SCRA
TCH1
CTFG WAFG DAFG (For
Reading)
0 0
Indefinite
1 0 0 0 0 Default
Settings
*)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.

(1) VDSL
VDD Supply Voltage Monitoring Threshold Selection Bit
VDSL Description
0
Selecting the VDD supply voltage monitoring threshold setting of 2.1v.
(Default)
1
Selecting the VDD supply voltage monitoring threshold setting of
1.35v.
The VDSL bit is intended to select the VDD supply voltage monitoring threshold settings.
(2) VDET
Supply Voltage Monitoring Result Indication Bit
VDET Description
0
Indicating supply voltage above the supply voltage monitoring
threshold settings.
(Default)
1
Indicating supply voltage below the supply voltage monitoring
threshold settings.
Once the VDET bit is set to 1, the supply voltage monitoring circuit will be disabled while the VDET bit will
hold
the setting of 1. The VDET bit accepts only the writing of 0, which restarts the supply voltage monitoring
circuit. Conversely, setting the VDET bit to 1 causes no event.
(3) /XST
Oscillation Halt Sensing Monitor Bit
/XST Description
0
Sensing a halt of oscillation
1
Sensing a normal condition of oscillation
The /XST accepts the reading and writing of 0 and 1. The /XST bit will be set to 0 when the oscillation halt
sensing. The /XST bit will hold 0 even after the restart of oscillation.
(4) PON
Power-on-reset Flag Bit
PON Description
0 Normal
condition
1
Detecting VDD power-on -reset
(Default)
The PON bit is for sensing power-on reset condition.

*
The PON bit will be set to 1 when VDD power-on from 0 volts. The PON bit will hold the setting of 1
even after power-on.
*
When the PON bit is set to 1, all bits will be reset to 0, in the Oscillation Adjustment Register, Control
Register 1, and Control Register 2, except /XST and PON. As a result, /INTR pin stops outputting.
*
The PON bit accepts only the writing of 0. Conversely, setting the PON bit to 1 causes no event.
(5) SCRATCH1
Scratch Bit 1
SCRATCH1 Description
0
(Default)
1
The SCRATCH1 bit is intended for scratching and accepts the reading and writing of 0 and 1. The
SCRATCH1 bit
will be set to 0 when the PON bit is set to 1 in the Control Register 2.
R2051 Series

12345
Rev.2.05 - 18 -
(6) CTFG
Periodic Interrupt Flag Bit
CTFG Description
0
Periodic interrupt output = "H"
(Default)
1
Periodic interrupt output = "L"
The CTFG bit is set to 1 when the periodic interrupt signals are output from the /INTR pin ("L"). The CTFG
bit
accepts only the writing of 0 in the level mode, which disables ("H") the /INTR pin until it is enabled ("L") again
in the next interrupt cycle. Conversely, setting the CTFG bit to 1 causes no event.
(7) WAFG,DAFG
Alarm_W Flag Bit and Alarm_D Flag Bit
WAFG,DAFG Description
0
Indicating a mismatch between current time and preset alarm time
(Default)
1
Indicating a match between current time and preset alarm time
The WAFG and DAFG bits are valid only when the WALE and DALE have the setting of 1, which is caused
approximately 61
s after any match between current time and preset alarm time specified by the Alarm_W
registers and the Alarm_D registers. The WAFG (DAFG) bit accepts only the writing of 0. /INTR pin
outputs off ("H") when this bit is set to 0. And /INTR pin outputs "L" again at the next preset alarm time.
Conversely, setting the WAFG and DAFG bits to 1 causes no event. The WAFG and DAFG bits will have
the reading of 0 when the alarm interrupt circuit is disabled with the WALE and DALE bits set to 0.
The settings of the WAFG and DAFG bits are synchronized with the output of the /INTR pin as shown in the
timing chart below.
/INTR Pin
Writing of 0 to
WAFG(DAFG) bit
WAFG(DAFG) Bit
(Match between
current time and
preset alarm time)
Approx. 61
s
Approx. 61
s
Writing of 0 to
WAFG(DAFG) bit
(Match between
current time and
preset alarm time)
(Match between
current time and
preset alarm time)
R2051 Series
12345
Rev.2.05 - 19 -
q
Time Counter (Address 0-2h)
Second Counter (Address 0h)
D7 D6 D5 D4 D3 D2 D1 D0
-
S40 S20 S10 S8 S4 S2 S1 (For
Writing)
0
S40 S20 S10 S8 S4 S2 S1 (For
Reading)
0
Indefinite Indefinite Indefinite Indefinite Indefinite Indefinite Indefinite
Default Settings *)

Minute Counter (Address 1h)
D7 D6 D5 D4 D3 D2 D1 D0
-
M40 M20 M10 M8 M4 M2 M1 (For
Writing)
0
M40 M20 M10 M8 M4 M2 M1 (For
Reading)
0
Indefinite Indefinite Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)

Hour Counter (Address 2h)
D7 D6 D5 D4 D3 D2 D1 D0
- - P
/A
or H20
H10
H8 H4 H2 H1 (For
Writing)
0 0 P
/A
or H20
H10
H8 H4 H2 H1 (For
Reading)
0 0
Indefinite Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.

*
Time digit display (BCD format) as follows:
The second digits range from 00 to 59 and are carried to the minute digit in transition from 59 to 00.
The minute digits range from 00 to 59 and are carried to the hour digits in transition from 59 to 00.
The hour digits range as shown in "P15
q
Control Register 1 (ADDRESS Eh) (2) /12
24: /12-24-hour
Mode Selection Bit" and are carried to the day-of-month and day-of-week digits in transition from
PM11 to AM12 or from 23 to 00.
*
Any writing to the second counter resets divider units of less than 1 second.
*
Any carry from lower digits with the writing of non-existent time may cause the time counters to
malfunction. Therefore, such incorrect writing should be replaced with the writing of existent time
data.
q
Day-of-week Counter (Address 3h)
D7 D6 D5 D4 D3 D2 D1 D0
- - - - - W4
W2
W1
(For
Writing)
0 0 0 0 0 W4
W2
W1
(For
Reading)
0 0 0 0 0
Indefinite
Indefinite
Indefinite
Default Settings *)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.

*
The day-of-week counter is incremented by 1 when the day-of-week digits are carried to the
day-of-month digits.
*
Day-of-week display (incremented in septimal notation):
(W4, W2, W1) = (0, 0, 0)
(0, 0, 1)
...
(1, 1, 0)
(0, 0, 0)
*
Correspondences between days of the week and the day-of-week digits are user-definable
(e.g. Sunday = 0, 0, 0)
*
The writing of (1, 1, 1) to (W4, W2, W1) is prohibited except when days of the week are unused.
R2051 Series

12345
Rev.2.05 - 20 -
q
Calendar Counter (Address 4-6h)

Day-of-month Counter (Address 4h)
D7 D6 D5 D4 D3 D2 D1 D0
- - D20 D10 D8 D4 D2 D1 (For
Writing)
0 0 D20 D10 D8 D4 D2 D1 (For
Reading)
0 0
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)

Month Counter + Century Bit (Address 5h)
D7 D6 D5 D4 D3 D2 D1 D0
/19
20
-
-
MO10 MO8 MO4 MO2 MO1 (For
Writing)
/19
20
0
0
MO10 MO8 MO4 MO2 MO1 (For
Reading)
Indefinite
0 0
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)
Year Counter (Address 6h)
D7 D6 D5 D4 D3 D2 D1 D0
Y80 Y40 Y20 Y10 Y8 Y4 Y2 Y1 (For
Writing)
Y80 Y40 Y20 Y10 Y8 Y4 Y2 Y1 (For
Reading)
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.

*
The calendar counters are configured to display the calendar digits in BCD format by using the
automatic calendar function as follows:
The day-of-month digits (D20 to D1) range from 1 to 31 for January, March, May, July, August, October,
and December; from 1 to 30 for April, June, September, and November; from 1 to 29 for February in
leap years; from 1 to 28 for February in ordinary years. The day-of-month digits are carried to the
month digits in reversion from the last day of the month to 1. The month digits (MO10 to MO1) range
from 1 to 12 and are carried to the year digits in reversion from 12 to 1.
The year digits (Y80 to Y1) range from 00 to 99 (00, 04, 08,
...
, 92, and 96 in leap years) and are
carried to the /19
20 digits in reversion from 99 to 00.
The /19
20 digits cycle between 0 and 1 in reversion from 99 to 00 in the year digits.
*
Any carry from lower digits with the writing of non-existent calendar data may cause the calendar
counters to malfunction. Therefore, such incorrect writing should be replaced with the writing of
existent calendar data.
q
Oscillation Adjustment Register (Address 7h)
D7 D6 D5 D4 D3 D2 D1 D0
DEV
F6 F5 F4 F3 F2 F1 F0 (For
Writing)
DEV
F6 F5 F4 F3 F2 F1 F0 (For
Reading)
0 0 0 0 0 0 0 0 Default
Settings
*)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.
DEV bit
When DEV is set to 0, the Oscillation Adjustment Circuit operates 00, 20, 40 seconds.
When DEV is set to 1, the Oscillation Adjustment Circuit operates 00 seconds.
F6 to F0 bits
The Oscillation Adjustment Circuit is configured to change time counts of 1 second on the basis of the
settings of the Oscillation Adjustment Register at the timing set by DEV.
R2051 Series
12345
Rev.2.05 - 21 -
* The Oscillation Adjustment Circuit will not operate with the same timing (00, 20, or 40 seconds)
as the timing of writing to the Oscillation Adjustment Register.
* The F6 bit setting of 0 causes an increment of time counts by ((F5, F4, F3, F2, F1, F0) - 1) x 2.
The F6 bit setting of 1 causes a decrement of time counts by ((/F5, /F4, /F3, /F2, /F1, /F0) + 1) x 2.
The settings of "*, 0, 0, 0, 0, 0, *" ("*" representing either "0" or "1") in the F6, F5, F4, F3, F2, F1, and F0
bits cause neither an increment nor decrement of time counts.

Example:
If (DEV, F6, F5, F4, F3, F2, F1, F0) is set to (0, 0, 0, 0, 0, 1, 1, 1), when the second digits read 00, 20,
or 40, an increment of the current time counts of 32768 + (7 - 1) x 2 to 32780 (a current time count
loss).
If (DEV, F6, F5, F4, F3, F2, F1, F0) is set to (0, 0, 0, 0, 0, 0, 0, 1), when the second digits read 00, 20,
40, neither an increment nor a decrement of the current time counts of 32768.
If (DEV, F6, F5, F4, F3, F2, F1, F0) is set to (1, 1, 1, 1, 1, 1, 1, 0), when the second digits read 00, a
decrement of the current time counts of 32768 + (- 2) x 2 to 32764 (a current time count gain).

An increase of two clock pulses once per 20 seconds causes a time count loss of approximately 3
ppm (2 / (32768 x 20 = 3.051 ppm). Conversely, a decrease of two clock pulses once per 20
seconds causes a time count gain of 3 ppm. Consequently, when DEV is set to "0", deviations in
time counts can be corrected with a precision of
1.5 ppm. In the same way, when DEV is set to "1",
deviations in time counts can be corrected with a precision of
0.5 ppm. Note that the oscillation
adjustment circuit is configured to correct deviations in time counts and not the oscillation frequency of
the 32.768-kHz clock pulses. For further details, see "P35
s
Configuration of Oscillation Circuit and
Correction of Time Count Deviations
q
Oscillation Adjustment Circuit".
R2051 Series

12345
Rev.2.05 - 22 -
q
Alarm_W Registers (Address 8-Ah)

Alarm_W Minute Register (Address 8h)
D7 D6 D5 D4 D3 D2 D1 D0
-
WM40
WM20 WM10 WM8 WM4 WM2 WM1 (For
Writing)
0
WM40
WM20 WM10 WM8 WM4 WM2 WM1 (For
Reading)
0
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)

Alarm_W Hour Register (Address 9h)
D7 D6 D5 D4 D3 D2 D1 D0
- -
WH20
WP
/A
WH10
WH8 WH4 WH2 WH1 (For
Writing)
0 0
WH20
WP
/A
WH10
WH8 WH4 WH2 WH1 (For
Reading)
0 0
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)

Alarm_W Day-of-week Register (Address Ah)
D7 D6 D5 D4 D3 D2 D1 D0
-
WW6 WW5 WW4 WW3 WW2 WW1 WW0 (For
Writing)
0
WW6 WW5 WW4 WW3 WW2 WW1 WW0 (For
Reading)
0
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.

*
The D5 bit of the Alarm_W Hour Register represents WP/A when the 12-hour mode is selected (0 for
a.m. and 1 for p.m.) and WH20 when the 24-hour mode is selected (tens in the hour digits).
*
The Alarm_W Registers should not have any non-existent alarm time settings.
(Note that any mismatch between current time and preset alarm time specified by the Alarm_W
registers may disable the alarm interrupt circuit.)
*
When the 12-hour mode is selected, the hour digits read 12 and 32 for 0 a.m. and 0 p.m., respectively.
(See "P15
q
Control Register 1 (ADDRESS Eh) (2) /12
24: 12-/24-hour Mode Selection Bit")
*
WW0 to WW6 correspond to W4, W2, and W1 of the day-of-week counter with settings ranging from
(0, 0, 0) to (1, 1, 0).
*
WW0 to WW6 with respective settings of 0 disable the outputs of the Alarm_W Registers.
R2051 Series
12345
Rev.2.05 - 23 -
Example of Alarm Time Setting
Alarm
Day-of-week
12-hour mode
24-hour mode
Preset alarm time
Sun.
Mon. Tue.
Wed. Th.
Fri.
Sat.
10
hr.
1
hr.
10
min.
1
min.
10
hr.
1
hr.
10
min.
1
min.
WW0 WW1 WW2
WW3
WW4
WW5
WW6
00:00
a.m.
on
all
days 1 1 1 1 1 1 1 1
2
0
0
0
0
0
0
01:30
a.m.
on
all
days 1 1 1 1 1 1 1 0
1
3
0
0
1
3
0
11:59
a.m.
on
all
days 1 1 1 1 1 1 1 1
1
5
9
1
1
5
9
00:00
p.m.
on
Mon.
to
Fri.
0 1 1 1 1 1 0 3
2
0
0
1
2
0
0
01:30
p.m.
on
Sun.
1 0 0 0 0 0 0 2
1
3
0
1
3
3
0
11:59 p.m.
on Mon. ,Wed., and Fri.
0 1 0 1 0 1 0 3
1
5
9
2
3
5
9
Note that the correspondence between WW0 to WW6 and the days of the week shown in the above table is
only an example and not mandatory.
q
Alarm_D Register (Address B-Ch)

Alarm_D Minute Register (Address Bh)
D7 D6 D5 D4 D3 D2 D1 D0
-
DM40 DM20 DM10 DM8 DM4 DM2 DM1 (For
Writing)
0
DM40 DM20 DM10 DM8 DM4 DM2 DM1 (For
Reading)
0
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)
Alarm_D Hour Register (Address Ch)
D7 D6 D5 D4 D3 D2 D1 D0
- - DH20
DP
/A
DH10 DH8 DH4 DH2 DH1 (For
Writing)
0 0 DH20
DP
/A
DH10 DH8 DH4 DH2 DH1 (For
Reading)
0 0
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Indefinite
Default Settings *)
*) Default settings: Default value means read / written values when the PON bit is set to "1" due to VDD
power-on from 0 volts.

*
The D5 bit represents DP/A when the 12-hour mode is selected (0 for a.m. and 1 for p.m.) and DH20
when the 24-hour mode is selected (tens in the hour digits).
*
The Alarm_D registers should not have any non-existent alarm time settings.
(Note that any mismatch between current time and preset alarm time specified by the Alarm_D
registers may disable the alarm interrupt circuit.)
*
When the 12-hour mode is selected, the hour digits read 12 and 32 for 0a.m. and 0p.m., respectively.
(See "P15
q
Control Register 1 (ADDRESS Eh) (2) /12
24: 12-/24-hour Mode Selection Bit")
R2051 Series

12345
Rev.2.05 - 24 -
s
Interfacing with the CPU
The R2051 employs the I
2
C-Bus system to be connected to the CPU via 2-wires. Connection and system of
I
2
C-Bus are described in the following sections.
q
Connection of I
2
C-Bus
2-wires, SCL and SDA pins that are connected to I
2
C-Bus are used for transmit clock pulses and data respectively.
All ICs that are connected to these lines are designed that will not be clamped when a voltage beyond supply
voltage is applied to input or output pins. Open drain pins are used for output. This construction allows
communication of signals between ICs with different supply voltages by adding a pull-up resistor to each signal
line as shown in the figure below. Each IC is designed not to affect SCL and SDA signal lines when power to
each of these is turned off separately.
Micro-
Controller
R2051
Other
Peripheral
Device
VDD1
VDD2
VDD3
VDD4
SCL
SDA
* For data interface, the following
conditions must be met:
VCC4
VCC1
VCC4
VCC2
VCC4
VCC3

* When the master is one, the
micro-controller is ready for driving
SCL to "H" and Rp of SCL may not be
required.
Rp
Rp

Cautions on determining Rp resistance,
(1) Dropping voltage at Rp due to sum of input current or output current at off conditions on each IC pin
connected to the I
2
C-Bus shall be adequately small.
(2) Rising time of each signal be kept short even when all capacity of the bus is driven.
(3) Current consumed in I
2
C-Bus is small compared to the consumption current permitted for the entire system.

When all ICs connected to I
2
C-Bus are CMOS type, condition (1) may usually be ignored since input current and
off-state output current is extremely small for the many CMOS type ICs. Thus the maximum resistance of Rp
may be determined based on (2), while the minimum on (3) in most cases.
In actual cases a resistor may be place between the bus and input/output pins of each IC to improve noise
margins in which case the Rp minimum value may be determined by the resistance.
Consumption current in the bus to review (3) above may be expressed by the formula below:

Bus consumption current

(Sum of input current and off state output current of all devices in standby mode )
Bus standby duration
Bus stand-by duration + the Bus operation duration

+ Supply voltage
Bus operation duration
2
Rp resistance
2
(Bus stand-by duration + bus operation duration)

+ Supply voltage
Bus capacity
Charging/Discharging times per unit time

Operation of "
2" in the second member denominator in the above formula is derived from assumption that "L"
duration of SDA and SCL pins are the half of bus operation duration. "
2" in the numerator of the same member
is because there are two pins of SDA and SCL. The third member, (charging/discharging times per unit time)
means number of transition from "H" to "L" of the signal line.


Calculation example is shown below:
Pull-up resistor (Rp) = 10k
, Bus capacity = 50pF(both for SCL, SDA), VCC=3v,
In a system with sum of input current and off-state output current of each pin = 0.1
A,
R2051 Series
12345
Rev.2.05 - 25 -
I
2
C-Bus is used for 10ms every second while the rest of 990ms in the stand-by mode,
In this mode, number of transitions of the SCL pin from "H" to "L" state is 100 while SDA 50, every second.

Bus consumption current
0.1
A
990msec
990msec + 10msec

+ 3V
10msec
2
10K
2
(990msec + 10msec)

+ 3V
50pF
(100 + 50)

0.099
A + 3.0
A + 0.0225
A
3.12
A

Generally, the second member of the above formula is larger enough than the first and the third members bus
consumption current may be determined by the second member is many cases.

q
Transmission System of I
2
C-Bus
(1) Start Condition and Stop Condition
In I
2
C-Bus, SDA must be kept at a certain state while SCL is at the "H" state during data transmission as shown
below.
SCL
SDA
tSU;DAT
tHD;DAT

The SCL and SDA pins are at the "H" level when no data transmission is made. Changing the SDA from "H" to "L"
when the SCL and the SDA are "H" activates the Start Condition and access is started. Changing the SDA from
"L" to "H" when the SCL is "H" activates Stop Condition and accessing stopped. Generation of Start and Stop
Conditions are always made by the master (see the figure below).
SCL
SDA
tHD;STA
tSU;STO
Start Condition
Stop Condition


(2) Data transmission and its acknowledge
After Start condition is entered, data is transmitted by 1byte (8bits). Any bytes of data may be serially transmitted.
The receiving side will send an acknowledge signal to the transmission side each time 8bit data is transmitted.
The acknowledge signal is sent immediately after falling to "L" of SCL 8bit clock pulses of data is transmitted, by
releasing the SDA by the transmission side that has asserted the bus at that time and by turning SDA to "L" by
receiving side. When transmission of 1byte data next to preceding 1byte of data is received the receiving side
releases the SDA pin at falling edge of the SCL 9bit of clock pulses or when the receiving side switches to the
transmission side it starts data transmission. When the master is receiving side, it generates no acknowledge
signal after last 1byte of data from the slave to tell the transmitter that data transmission has completed. The
R2051 Series

12345
Rev.2.05 - 26 -
slave side (transmission side) continues to release the SDA pin so that the master will be able to generate Stop
Condition, after falling edge of the SCL 9bit of clock pulses.
SCL
from the master
SDA from
the transmission side
SDA from
the receiving side
1
2
8
9
Acknowledge
signal
Start
Condition


(3) Data Transmission Format in I
2
C-Bus
I
2
C-Bus has no chip enable signal line. In place of it, each device has a 7bit Slave Address allocated. The first
1byte is allocated to this 7bit address and to the command (R/W) for which data transmission direction is
designated by the data transmission thereafter. 7bit address is sequentially transmitted from the MSB and 2 and
after bytes are read, when 8bit is "H" and when write "L".
The Slave Address of the R2051 is specified at (0110010).
At the end of data transmission / receiving, Stop Condition is generated to complete transmission. However, if
start condition is generated without generating Stop Condition, Repeated Start Condition is met and transmission /
receiving data may be continue by setting the Slave Address again. Use this procedure when the transmission
direction needs to be change during one transmission.
S
A
A
Data
/A P
Data is written to the slave
from the master
S
0
A
Slave Address
Data
A
A P
When data is read from the
slave immediately after 7bit
addressing from the master
Master to slave
Slave to master
Sr
Repeated Start Condition
P
Stop Condition
A
A
/A Acknowledge Signal
R/W=1(Read)
(0110010)
Inform read has been completed by not generate
an acknowledge signal to the slave side.
Data
R/W=0(Write)
(0110010)
When the transmission
direction is to be changed
during transmission.
Sr
1
0
A
A
R/W=0(Write)
A
Data
R/W=1(Read)
(0110010)
S
1
A
/A P
Inform read has been completed by not generate
an acknowledge signal to the slave side.
Data
S
Start Condition
(0110010)
Slave Address
Salve Address
Slave Address
Data
Data
R2051 Series
12345
Rev.2.05 - 27 -
(4) Data Transmission Write Format in the R2051
Although the I
2
C-Bus standard defines a transmission format for the slave allocated for each IC, transmission
method of address information in IC is not defined. The R2051 transmits data the internal address pointer (4bit)
and the Transmission Format Register (4bit) at the 1byte next to one which transmitted a Slave Address and a
write command. For write operation only one transmission format is available and (0000) is set to the
Transmission Format Register. The 3byte transmits data to the address specified by the internal address pointer
written to the 2byte. Internal address pointer setting are automatically incremented for 4byte and after. Note
that when the internal address pointer is Fh, it will change to 0h on transmitting the next byte.
1
A
S
0
A
Data
A
Data
A P
Example of data writing (When writing to internal address Eh to Fh)
Master to slave
Slave to master
S
Start Condition
P
Stop Condition
A
A
/A
Acknowledge signal
Address
Pointer
Eh
R/W=0(Write)
Slave Address
(0110010)
1
1
0
0
0
0
0
0 0 0
0
1 1
1
Transmission
Format
Register
0h
Writing of data to the
internal address Fh
Writing of data to the
internal address Eh
R2051 Series

12345
Rev.2.05 - 28 -
(5) Data transmission read format of the R2051
The R2051 allows the following three read out method of data an internal register.

The first method to reading data from the internal register is to specify an internal address by setting the internal
address pointer and the transmission format register described P27 (4), generate the Repeated Start Condition
(See P26 (3)) to change the data transmission direction to perform reading. The internal address pointer is set
to Fh when the Stop Condition is met. Therefore, this method of reading allows no insertion of Stop Condition
before the Repeated Start Condition. Set 0h to the Transmission Format Register when this method used.
1
S
0
A
A
Data
/A P
Example 1 of Data Read (when data is read from 2h to 4h)
Master to slave
Slave to master
S
Start Condition
Sr
Repeated Start
Condition
A
A
/A
Acknowledge signal
Address
Pointer
2h
Repeated Start Condition
0
1
0
0
0
1
1
0 0 0
0
0
0
1
Transmission
Format
Register
0h
Sr
1
0
A
Slave Address
(0110010)
1
0
0 0
0
1
A
Data
A
Data
Reading of data from
the internal address 3h
R/W=1(Read)
R/W=0(Write)
P
Stop Condition
Slave Address
(0110010)
Reading of data from
the internal address 4h
Reading of data from
the internal address 2h
R2051 Series
12345
Rev.2.05 - 29 -

The second method to reading data from the internal register is to start reading immediately after writing to the
Internal Address Pointer and the Transmission Format Register. Although this method is not based on I
2
C-Bus
standard in a strict sense it still effective to shorten read time to ease load to the master. Set 4h to the
transmission format register when this method used.
1
S
A
A
Data
/A P
Example 2 of data read (when data is read from internal addresses Eh to 1h)
Master to slave
Slave to Master
S
Start Condition
A
A
/A
Acknowledge Signal
Address
Pointer
Eh
0 1
1
0 0
0
1
Transmission
Format
Register
4h
1
0
A
Slave Address
(0110010)
1
0
0 0
0
1
A
Data
A
Data
Reading of data from
the internal address Eh
R/W=0(Write)
P Stop Condition
Data
Reading of data from
the internal address Fh
Reading of data from
the internal address 0h
Reading of data from
the internal address 1h

R2051 Series

12345
Rev.2.05 - 30 -

The third method to reading data from the internal register is to start reading immediately after writing to the Slave
Address and R/W bit. Since the Internal Address Pointer is set to Fh by default as described in the first method,
this method is only effective when reading is started from the Internal Address Fh.
S
A
A
Data
/A P
Example 3 of data read (when data is read from internal addresses Fh to 3h)
Master to slave
Slave to master
S
Start Condition
A
A
/A
Acknowledge Signal
1
0
A
Slave Address
(0110010)
1
0
0 1
0
1
A
Data
A
Data
R/W=1(Read)
P Stop Condition
Data
Data
Reading of data from
the Internal Address Fh
Reading of data from
the Internal Address 0h
Reading of data from
the Internal Address 1h
Reading of data from
the Internal Address 2h
Reading of data from
the Internal Address 3h
R2051 Series
12345
Rev.2.05 - 31 -
q
Data Transmission under Special Condition
The R2051 holds the clock tentatively for duration from Start Condition to avoid invalid read or write clock on
carrying clock. When clock carried during this period, which will be adjusted within approx. 61
s from Stop
Condition. To prevent invalid read or write, clock and calendar data shall be made during one transmission
operation (from Start Condition to Stop Condition). When 0.5 to 1.0 second elapses after Start Condition, any
access to the R2051 is automatically released to release tentative hold of the clock, and access from the CPU is
forced to be terminated (The same action as made Stop Condition is received: automatic resume function from
I
2
C-Bus interface). Therefore, one access must be complete within 0.5 seconds. The automatic resume
function prevents delay in clock even if SCL is stopped from sudden failure of the system during clock read
operation.
Also a second Start Condition after the first Start Condition and before the Stop Condition is regarded "Repeated
Start Condition". Therefore, when 0.5 to 1.0 seconds passed after the first Start Condition, an access to the
R2051 is automatically released.
If access is tried after automatic resume function is activated, no acknowledge signal will be output for writing
while FFh will be output for reading.

The user shall always be able to access the real-time clock as long as three conditions are met.
No Stop Condition shall be generated until clock and calendar data read/write is started and completed.
One cycle read/write operation shall be complete within 0.5 seconds.
Do not make Start Condition within 61
s from Stop Condition. When clock is carried during the access, which
will be adjusted within approx. 61
s from Stop Condition.

Bad example of reading from seconds to hours (invalid read)
(Start Condition)
(Read of seconds)
(Read of minutes)
(Stop Condition)
(Start Condition)
(Read of
hour)
(Stop Condition)

Assuming read was started at 05:59:59 P.M. and while reading seconds and minutes the time advanced to
06:00:00 P.M. At this time second digit is hold so read the read as 05:59:59. Then the R2051 confirms (Stop
Condition) and carries second digit being hold and the time change to 06:00:00 P.M. Then, when the hour digit is
read, it changes to 6. The wrong results of 06:59:59 will be read.
R2051 Series

12345
Rev.2.05 - 32 -
s
Configuration of Oscillation Circuit and Correction of Time Count Deviations
q
Configuration of Oscillation Circuit
32kHz
CG
CD
A
OSCIN
OSCOUT
Oscillator
Circuit

The oscillation circuit is driven at a constant voltage of approximately 1.2 volts relative to the level of the VSS pin
input. As such, it is configured to generate an oscillating waveform with a peak-to-peak voltage on the order of
1.1 volts on the positive side of the VSS pin input.

< Considerations in Handling Crystal Oscillators >
Generally, crystal oscillators have basic characteristics including an equivalent series resistance (R1) indicating
the ease of their oscillation and a load capacitance (CL) indicating the degree of their center frequency.
Particularly, crystal oscillators intended for use in the R2051 are recommended to have a typical R1 value of 30k
and a typical CL value of 6 to 8pF. To confirm these recommended values, contact the manufacturers of crystal
oscillators intended for use in these particular models.

< Considerations in Installing Components around the Oscillation Circuit >
1)
Install the crystal oscillator in the closest possible vicinity to the real-time clock ICs.
2)
Avoid laying any signal lines or power lines in the vicinity of the oscillation circuit (particularly in the area
marked "A" in the above figure).
3)
Apply the highest possible insulation resistance between the OSCIN and OSCOUT pins and the printed
circuit board.
4)
Avoid using any long parallel lines to wire the OSCIN and OSCOUT pins.
5)
Take extreme care not to cause condensation, which leads to various problems such as oscillation halt.

< Other Relevant Considerations >
1)
For external input of 32.768-kHz clock pulses to the OSCIN pin:
DC coupling: Prohibited due to an input level mismatch.
AC coupling: Permissible except that the oscillation halt sensing circuit does not guarantee perfect
operation because it may cause sensing errors due to such factors as noise.
2)
To maintain stable characteristics of the crystal oscillator, avoid driving any other IC through 32.768-kHz
clock pulses output from the OSCOUT pin.
Typical externally-equipped element
X'tal
:
32.768kHz
(R1=30k
typ)
(CL=6pF
to
8pF)
Standard values of internal elements
CG,CD 10pF typ
R2051 Series
12345
Rev.2.05 - 33 -
q
Measurement of Oscillation Frequency
Frequency
Counter
32768Hz
VCC
OSCIN
OSCOUT
VDD
CLKOUT
VSS
* 1)
The R2051 is configured to generate 32.768-kHz clock pulses for output from the CLKOUT pin.
* 2) A frequency counter with 6 (more preferably 7) or more digits on the order of 1ppm is recommended
for use in the measurement of the oscillation frequency of the oscillation circuit.
q
Adjustment of Oscillation frequency
The oscillation frequency of the oscillation circuit can be adjusted by varying procedures depending on the usage
of Model R2051 in the system into which they are to be built and on the allowable degree of time count errors.
The flow chart below serves as a guide to selecting an optimum oscillation frequency adjustment procedure for
the relevant system.
Start
Course (B)
Use 32-kHz clock output without regard
to its frequency precision
NO
YES
Use 32-kHz
clock output?
YES
NO
Course (C)
Course (A)
Course (D)
YES
YES
NO
NO
Allowable time count precision on order of oscillation
frequency variations of crystal oscillator (*1) plus
frequency variations of RTC (*2)? (*3)
Allowable time count precision on order of oscillation
frequency variations of crystal oscillator (*1) plus
frequency variations of RTC (*2)? (*3)
* 1) Generally, crystal oscillators for commercial use are classified in terms of their center frequency
depending on their load capacitance (CL) and further divided into ranks on the order of
10,
20, and
50ppm depending on the degree of their oscillation frequency variations.
* 2) Basically, Model R2051 is configured to cause frequency variations on the order of
5 to
10ppm at
25
C.
* 3) Time count precision as referred to in the above flow chart is applicable to normal temperature and
actually affected by the temperature characteristics and other properties of crystal oscillators.
R2051 Series

12345
Rev.2.05 - 34 -
Course (A)
When the time count precision of each RTC is not to be adjusted, the crystal oscillator intended for use in that
RTC may have any CL value requiring no presetting. The crystal oscillator may be subject to frequency
variations which are selectable within the allowable range of time count precision. Several crystal oscillators and
RTCs should be used to find the center frequency of the crystal oscillators by the method described in "P33
q
Measurement of Oscillation Frequency" and then calculate an appropriate oscillation adjustment value by the
method described in "P35
q
Oscillation Adjustment Circuit" for writing this value to the R2051.

Course (B)
When the time count precision of each RTC is to be adjusted within the oscillation frequency variations of the
crystal oscillator plus the frequency variations of the real-time clock ICs, it becomes necessary to correct
deviations in the time count of each RTC by the method described in " P35
q
Oscillation Adjustment Circuit".
Such oscillation adjustment provides crystal oscillators with a wider range of allowable settings of their oscillation
frequency variations and their CL values. The real-time clock IC and the crystal oscillator intended for use in that
real-time clock IC should be used to find the center frequency of the crystal oscillator by the method described in "
P33
q
Measurement of Oscillation Frequency" and then confirm the center frequency thus found to fall within
the range adjustable by the oscillation adjustment circuit before adjusting the oscillation frequency of the
oscillation circuit. At normal temperature, the oscillation frequency of the oscillator circuit can be adjusted by up
to approximately
0.5ppm.

Course (C)
Course (C) together with Course (D) requires adjusting the time count precision of each RTC as well as the
frequency of 32.768-kHz clock pulses output from the CLKOUT pin. Normally, the oscillation frequency of the
crystal oscillator intended for use in the RTCs should be adjusted by adjusting the oscillation stabilizing capacitors
CG and CD connected to both ends of the crystal oscillator. The R2051, which incorporate the CG and the CD,
require adjusting the oscillation frequency of the crystal oscillator through its CL value.
Generally, the relationship between the CL value and the CG and CD values can be represented by the following
equation:
CL = (CG
CD)/(CG + CD) + CS where "CS" represents the floating capacity of the printed circuit board.
The crystal oscillator intended for use in the R2051 is recommended to have the CL value on the order of 6 to 8pF.
Its oscillation frequency should be measured by the method described in " P33
q
Measurement of Oscillation
Frequency". Any crystal oscillator found to have an excessively high or low oscillation frequency (causing a time
count gain or loss, respectively) should be replaced with another one having a smaller and greater CL value,
respectively until another one having an optimum CL value is selected. In this case, the bit settings disabling the
oscillation adjustment circuit (see " P35
q
Oscillation Adjustment Circuit ") should be written to the oscillation
adjustment register.
Incidentally, the high oscillation frequency of the crystal oscillator can also be adjusted by adding an external
oscillation stabilization capacitor CGOUT as illustrated in the diagram below.
32kHz
RD
CG
CD
OSCIN
OSCOUT
CGOUT
*1)
Oscillator
Circuit

Course (D)
It is necessary to select the crystal oscillator in the same manner as in Course (C) as well as correct errors in the
time count of each RTC in the same manner as in Course (B) by the method described in " P35
q
Oscillation
Adjustment Circuit ".
*1) The CGOUT should have a capacitance ranging
from 0 to 15 pF.
R2051 Series
12345
Rev.2.05 - 35 -
q
Oscillation Adjustment Circuit
The oscillation adjustment circuit can be used to correct a time count gain or loss with high precision by varying
the number of 1-second clock pulses once per 20 seconds or 60 seconds. When DEV bit in the Oscillation
Adjustment Register is set to 0, R2051 varies number of 1-second clock pulses once per 20 seconds. When
DEV bit is set to 1, R2051 varies number of 1-second clock pulses once per 60 seconds. The oscillation
adjustment circuit can be disabled by writing the settings of "*, 0, 0, 0, 0, 0, *" ("*" representing "0" or "1") to the F6,
F5, F4, F3, F2, F1, and F0 bits in the oscillation adjustment circuit. Conversely, when such oscillation
adjustment is to be made, an appropriate oscillation adjustment value can be calculated by the equation below for
writing to the oscillation adjustment circuit.


(1) When Oscillation Frequency (* 1) Is Higher Than Target Frequency (* 2) (Causing Time Count Gain)
When DEV=0:
Oscillation adjustment value (*3) = (Oscillation frequency - Target Frequency + 0.1)
Oscillation frequency
3.051
10
-6
(Oscillation Frequency Target Frequency)
10 + 1
When DEV=1:
Oscillation adjustment value (*3) = (Oscillation frequency - Target Frequency + 0.0333)
Oscillation frequency
1.017
10
-6
(Oscillation Frequency Target Frequency)
30 + 1

* 1)
Oscillation frequency:
Frequency of clock pulse output from the CLKOUT pin at normal temperature in the manner described
in " P33
q
Measurement of Oscillation Frequency".
* 2)
Target frequency:
Desired frequency to be set. Generally, a 32.768-kHz crystal oscillator has such temperature
characteristics as to have the highest oscillation frequency at normal temperature. Consequently, the
crystal oscillator is recommended to have target frequency settings on the order of 32.768 to 32.76810
kHz (+3.05ppm relative to 32.768 kHz). Note that the target frequency differs depending on the
environment or location where the equipment incorporating the RTC is expected to be operated.
* 3)
Oscillation adjustment value:
Value that is to be finally written to the F0 to F6 bits in the Oscillation Adjustment Register and is
represented in 7-bit coded decimal notation.
(2) When Oscillation Frequency Is Equal To Target Frequency (Causing Time Count neither Gain nor Loss)
Oscillation adjustment value = 0, +1, -64, or 63

(3) When Oscillation Frequency Is Lower Than Target Frequency (Causing Time Count Loss)
When DEV=0:
Oscillation adjustment value = (Oscillation frequency - Target Frequency)
Oscillation frequency
3.051
10
-6
(Oscillation Frequency Target Frequency)
10
When DEV=1:
Oscillation adjustment value = (Oscillation frequency - Target Frequency)
Oscillation frequency
1.017
10
-6
(Oscillation Frequency Target Frequency)
30

Oscillation adjustment value calculations are exemplified below

(A) For an oscillation frequency = 32768.85Hz and a target frequency = 32768.05Hz
When setting DEV bit to 0:
Oscillation adjustment value = (32768.85 - 32768.05 + 0.1) / (32768.85
3.051
10
-6
)
(32768.85 - 32768.05)
10 + 1
= 9.001
9
In this instance, write the settings (DEV,F6,F5,F4,F3,F2,F1,F0)=(0,0,0,0,1,0,0,1) in the oscillation adjustment
register. Thus, an appropriate oscillation adjustment value in the presence of any time count gain represents a
distance from 01h.

When setting DEV bit to 1:
R2051 Series

12345
Rev.2.05 - 36 -
Oscillation adjustment value = (32768.85 - 32768.05 + 0.0333) / (32768.85
1.017
10
-6
)
(32768.85 - 32768.05)
30 + 1
= 23.51
24
In this instance, write the settings (DEV,F6,F5,F4,F3,F2,F1,F0)=(1,0,0,1,1,0,0,0) in the oscillation adjustment
register.

(B) For an oscillation frequency = 32762.22Hz and a target frequency = 32768.05Hz

When setting DEV bit to 0:
Oscillation adjustment value = (32762.22 - 32768.05) / (32762.22
3.051
10
-6
)
(32762.22 - 32768.05)
10
= -58.325
-58
To represent an oscillation adjustment value of - 58 in 7-bit coded decimal notation, subtract 58 (3Ah) from 128
(80h) to obtain 46h. In this instance, write the settings of (DEV,F6,F5,F4,F3,F2,F1,F0) = (0,1,0,0,0,1,1,0) in the
oscillation adjustment register. Thus, an appropriate oscillation adjustment value in the presence of any time
count loss represents a distance from 80h.

When setting DEV bit to 1:
Oscillation adjustment value = (32762.22 - 32768.05) / (32762.22
1.017
10
-6
)
(32762.22 - 32768.05)
30
= -174.97
-175

Oscillation adjustment value can be set from -62 to 63. Then, in this case, Oscillation adjustment value is out of
range.


(4) Difference between DEV=0 and DEV=1
Difference between DEV=0 and DEV=1 is following,
DEV=0 DEV=1
Maximum value range
-189.2ppm to 189.2ppm
--62ppm to 63ppm
Minimum resolution
3ppm
1ppm

Notes:
1)
Oscillation adjustment circuit does not affect the frequency of 32.768-kHz clock pulses output from the
CLKOUT pin.
2)
If following 3 conditions are completed, actual clock adjustment value could be different from target
adjustment value that set by oscillator adjustment function.
1. Using oscillator adjustment function
2. Access to R2051 at random, or synchronized with external clock that has no relation to R2051, or
synchronized with periodic interrupt in pulse mode.
3. Access to R2051 more than 2 times per each second on average.
For more details, please contact to Ricoh.
q
How to evaluate the clock gain or loss
The oscillator adjustment circuit is configured to change time counts of 1 second on the basis of the settings of
the oscillation adjustment register once in 20 seconds or 60 seconds. The oscillation adjustment circuit does not
effect the frequency of 32768Hz-clock pulse output from the CLKOUT pin. Therefore, after writing the oscillation
adjustment register, we cannot measure the clock error with probing CLKOUT clock pulses. The way to measure
the clock error as follows:

(1) Output a 1Hz clock pulse of Pulse Mode with interrupt pin
Set (0,0,x,x,0,0,1,1) to Control Register 1 at address Eh.

(2) After setting the oscillation adjustment register, 1Hz clock period changes every 20seconds ( or every 60
seconds) like next page figure.
R2051 Series
12345
Rev.2.05 - 37 -
1Hz clock pulse
T0
T0
T0
T1
1 time
19 times

Measure the interval of T0 and T1 with frequency counter. A frequency counter with 7 or more digits is
recommended for the measurement.

(3) Calculate the typical period from T0 and T1
T = (19
T0+1
T1)/20
Calculate the time error from T.
R2051 Series

12345
Rev.2.05 - 38 -
s
Power-on Reset, Oscillation Halt Sensing, and Supply Voltage Monitoring
q
PON, /XST, and VDET
The power-on reset circuit is configured to reset control register1, 2, and clock adjustment register when VDD
power up from 0v. The oscillation halt sensing circuit is configured to record a halt on oscillation by 32.768-kHz
clock pulses. The supply voltage monitoring circuit is configured to record a drop in supply voltage below a
threshold voltage of 2.1 or 1.35v.
Each function has a monitor bit. I.e. the PON bit is for the power-on reset circuit, and /XST bit is for the
oscillation halt sensing circuit, and VDET is for the supply voltage monitoring circuit. PON and VDET bits are
activated to "H". However, /XST bit is activated to "L". The PON and VDET accept only the writing of 0, but /XST
accepts the writing of 0 and 1. The PON bit is set to 1, when VDD power-up from 0V, but VDET is set to 0, and
/XST is indefinite.
The functions of these three monitor bits are shown in the table below.
PON
/XST
VDET
Function Monitoring
for
the
power-on reset function
Monitoring for the
oscillation halt sensing
function
a drop in supply voltage
below a threshold voltage
of 2.1 or 1.35v
Address
D4 in Address Fh
D5 in Address Fh
D6 in Address Fh
Activated High
Low
High
When VDD power
up from 0v
1 indefinite
0
accept the writing
0 only
Both 0 and 1
0 only

The relationship between the PON, /XST, and VDET is shown in the table below.
PON
/XST VDET
Conditions of supply voltage and
oscillation
Condition of oscillator, and back-up
status
0
0
0
Halt on oscillation, but no drop in
VDD supply voltage below threshold
voltage
Halt on oscillation cause of
condensation etc.
0
0
1
Halt on oscillation and drop in VDD
supply voltage below threshold
voltage, but no drop to 0V
Halt on oscillation cause of drop in
back-up battery voltage
0
1
0
No drop in VDD supply voltage below
threshold voltage and no halt in
oscillation
Normal condition
0
1
1
Drop in VDD supply voltage below
threshold voltage and no halt on
oscillation
No halt on oscillation, but drop in
back-up battery voltage
1
*
*
Drop in supply voltage to 0v
Power-up from 0v,
32768Hz Oscillation
Power-on reset flag
(PON)
Oscillation halt
sensing flag (/XST)
Threshold voltage (2.1V or 1.35V)
VDD
VDD supply voltage
monitor flag (VDET)
Internal initialization
period (1 to 2 sec.)
VDET
0
/XST
1
PON
0
VDET
0
/XST
1
PON
1
VDET
0
/XST
1
PON
0
Internal initialization
period (1 to 2 sec.)
When the PON bit is set to 1 in the control register 2, the DEV, F6 to F0, WALE, DALE, /12
24, SCRATCH2,
R2051 Series
12345
Rev.2.05 - 39 -
TEST, CT2, CT1, CT0, VDSL, VDET, SCRATCH1, CTFG, WAFG, and DAFG bits are reset to 0 in the oscillation
adjustment register, the control register 1, and the control register 2. The PON bit is also set to 1 at power-on
from 0 volts.

< Considerations in Using Oscillation Halt Sensing Circuit >
Be sure to prevent the oscillation halt sensing circuit from malfunctioning by preventing the following:

1) Instantaneous power-down on the VDD
2) Condensation on the crystal oscillator
3) On-board noise to the crystal oscillator
4) Applying to individual pins voltage exceeding their respective maximum ratings

In particular, note that the /XST bit may fail to be set to 0 in the presence of any applied supply voltage as
illustrated below in such events as backup battery installation. Further, give special considerations to prevent
excessive chattering in the oscillation halt sensing circuit.
VDD
R2051 Series

12345
Rev.2.05 - 40 -
q
Voltage Monitoring Circuit
R2051 incorporates two kinds of voltage monitoring function. These are shown in the table below.
VCC Voltage Monitoring Circuit
VDD Voltage Monitoring Circuit
(VDET)
Purpose
CPU reset output
Back-up battery checker
Monitoring supply voltage
VCC pin
VDD pin (supply voltage for the
internal RTC circuit)
Output for result
/VDCC pin
Store in the Control Register 2
(D6 in Address Fh)
Function
After falling VCC, /VDCC outputs
"L". tDEALY after rising VCC,
/VDCC outputs "H" (OFF)
Below the threshold voltage, SW1
turns off and SW2 turns on. Over
the threshold voltage, SW1 turns
on and SW2 turns off.
Detector Threshold (falling edge
of power supply voltage)
-VDET1
Selecting from VDETH or VDETL
by writing to the register
(D7 in Address Fh)
Detector Released
Voltage (rising edge of power
supply voltage)
+VDET1
Same as falling edge
( No hysteresis)
The way to monitor
Always
One time every second

The VDD supply voltage monitoring circuit is configured to conduct a sampling operation during an interval of
7.8ms per second to check for a drop in supply voltage below a threshold voltage of 2.1 or 1.35v for the VDSL bit
setting of 0 (the default setting) or 1, respectively, in the Control Register 2, thus minimizing supply current
requirements as illustrated in the timing chart below. This circuit suspends a sampling operation once the VDET
bit is set to 1 in the Control Register 2. The VDD supply voltage monitor is useful for back-up battery checking.
VDET
(D6 in Address Fh)
PON
VDD
2.1v or 1.35v
1s
VDET
0
7.8ms
Sampling timing for VDD
supply voltage monitor
Internal nitiali-
zation period
(1 to 2sec.)
PON
0
VDET
0
R2051 Series
12345
Rev.2.05 - 41 -
The VCC supply voltage monitor circuit operates always. When VCC rising over +VDET1, SW1 turns on, and
SW2 turns off. And tDELAY after rising VCC, /VDCC outputs OFF(H). But when oscillation is halt, VCC outputs
OFF(H) tDELAY after oscillation starting. When VCC falling beyond -VDET1, SW1 turns off, and SW2 turns on.
And /VDCC outputs "L".

VDD
32768Hz Oscillation
/VDCC
+VDET1
VCC
SW1
SW2
tDELAY
tDELAY
tDELAY
ON
ON
ON
ON
ON
Same voltage level as VSB
Oscillation starting
-VDET1
s
Battery Switch Over Circuit
R2051 incorporates three power supply pins, VDD, VCC, and VSB. VDD pin is the power supply pin for internal
real time clock circuit. When VCC voltage is lower than
VDET1, VSB supplies the power to VDD, and when
higher than
VDET1, VCC supplies the power to VDD. The timing chart for VCC, VDD, and VSB is shown
following.

VDD
+VDET1
VCC
VSB
(1)
(2)
(3)
(3)
(2)
-VDET1

(1) When VSB is 0v and VCC is rising from 0v, VDD follows half of VCC voltage level. After VCC rising over
+VDET1, VDD follows VCC voltage level.
(2) When VCC is higher than +VDET1, VDD level is equal to VCC.
(3) After VCC falling beyond -VDET1, VDD level is equal to VSB.

R2051 Series

12345
Rev.2.05 - 42 -
s
Alarm and Periodic Interrupt
The R2051 incorporates the alarm interrupt circuit and the periodic interrupt circuit that are configured to generate
alarm signals and periodic interrupt signals for output from the /INTR pin as described below.

(1) Alarm Interrupt Circuit
The alarm interrupt circuit is configured to generate alarm signals for output from the /INTR, which is driven low
(enabled) upon the occurrence of a match between current time read by the time counters (the day-of-week, hour,
and minute counters) and alarm time preset by the alarm registers (the Alarm_W registers intended for the
day-of-week, hour, and minute digit settings and the Alarm_D registers intended for the hour and minute digit
settings).

(2) Periodic Interrupt Circuit
The periodic interrupt circuit is configured to generate either clock pulses in the pulse mode or interrupt signals in
the level mode for output from the /INTR pin depending on the CT2, CT1, and CT0 bit settings in the control
register 1.

The above two types of interrupt signals are monitored by the flag bits (i.e. the WAFG, DAFG, and CTFG bits in
the Control Register 2) and enabled or disabled by the enable bits (i.e. the WALE, DALE, CT2, CT1, and CT0 bits
in the Control Register 1) as listed in the table below.
Flag bits
Enable bits
Alarm_W WAFG
(D1 at Address Fh)
WALE
(D7 at Address Eh)
Alarm_D DAFG
(D0 at Address Fh)
DALE
(D6 at Address Eh)
Peridic interrupt
CTFG
(D2 at Address Fh)
CT2=CT1=CT0=0
(These bit setting of "0" disable the Periodic Interrupt)
(D2 to D0 at Address Eh)

* At power-on, when the WALE, DALE, CT2, CT1, and CT0 bits are set to 0 in the Control Register 1,
the /INTR pin is driven high (disabled).
* When two types of interrupt signals are output simultaneously from the /INTR pin, the output from the
/INTR pin becomes an OR waveform of their negative logic.
Example: Combined Output to /INTR Pin Under Control of
/ALARM_D and Periodic Interrupt
Periodic Interrupt
/INTR
/Alarm_D

In this event, which type of interrupt signal is output from the /INTR pin can be confirmed by reading the
DAFG,
and CTFG bit settings in the Control Register 2.
q
Alarm Interrupt
The alarm interrupt circuit is controlled by the enable bits (i.e. the WALE and DALE bits in the Control Register 1)
and the flag bits (i.e. the WAFG and DAFG bits in the Control Register 2). The enable bits can be used to
enable this circuit when set to 1 and to disable it when set to 0. When intended for reading, the flag bits can be
used to monitor alarm interrupt signals. When intended for writing, the flag bits will cause no event when set to 1
and will drive high (disable) the alarm interrupt circuit when set to 0.
The enable bits will not be affected even when the flag bits are set to 0. In this event, therefore, the alarm
interrupt circuit will continue to function until it is driven low (enabled) upon the next occurrence of a match
between current time and preset alarm time.
R2051 Series
12345
Rev.2.05 - 43 -
The alarm function can be set by presetting desired alarm time in the alarm registers (the Alarm_W Registers for
the day-of-week digit settings and both the Alarm_W Registers and the Alarm_D Registers for the hour and
minute digit settings) with the WALE and DALE bits once set to 0 and then to 1 in the Control Register 1. Note
that the WALE and DALE bits should be once set to 0 in order to disable the alarm interrupt circuit upon the
coincidental occurrence of a match between current time and preset alarm time in the process of setting the
alarm function.
current time =
preset alarm time
WALE
1
(DALE)
Interval (1min.) during which a match
between current time and preset alarm time
occurs
current time =
preset alarm time
WAFG
0
(DAFG)
/INTR
WALE
1
(DALE)
WALE
1
(DALE)
current time =
preset alarm time
WALE
0
(DALE)
current time =
preset alarm time
/INTR

After setting WALE(DALW) to 0, Alarm registers is set to current time, and WALE(DALE) is set to 1, /INTR will be
not driven to "L" immediately, /INTR will be driven to "L" at next alarm setting time.
q
Periodic Interrupt
Setting of the periodic selection bits (CT2 to CT0) enables periodic interrupt to the CPU. There are two waveform
modes: pulse mode and level mode. In the pulse mode, the output has a waveform duty cycle of around 50%. In
the level mode, the output is cyclically driven low and, when the CTFG bit is set to 0, the output is return to High
(OFF).
Description
CT2 CT1 CT0
Wave form mode
Interrupt Cycle and Falling Timing
0 0 0 -
OFF(H)
(Default)
0 0 1 -
Fixed
at
"L"
0 1 0 Pulse
Mode
*1) 2Hz(Duty50%)
0 1 1 Pulse
Mode
*1) 1Hz(Duty50%)
1
0
0
Level Mode *2)
Once per 1 second (Synchronized with
Second counter increment)
1
0
1
Level Mode *2)
Once per 1 minute (at 00 seconds of every
Minute)
1
1
0
Level Mode *2)
Once per hour (at 00 minutes and 00
Seconds of every hour)
1
1
1
Level Mode *2)
Once per month (at 00 hours, 00 minutes,
and 00 seconds of first day of every month)

*1) Pulse Mode:
2-Hz and 1-Hz clock pulses are output in synchronization with the increment of the second counter as
illustrated in the timing chart below.
/INTR Pin
Rewriting of the second counter
CTFG Bit
Approx. 92
s
(Increment of second counter)
R2051 Series

12345
Rev.2.05 - 44 -
In the pulse mode, the increment of the second counter is delayed by approximately 92
s from the
falling edge of clock pulses. Consequently, time readings immediately after the falling edge of clock
pulses may appear to lag behind the time counts of the real-time clocks by approximately 1 second.
Rewriting the second counter will reset the other time counters of less than 1 second, driving the
/INTR pin low.

*2) Level Mode:
Periodic interrupt signals are output with selectable interrupt cycle settings of 1 second, 1 minute, 1
hour, and 1 month. The increment of the second counter is synchronized with the falling edge of
periodic interrupt signals. For example, periodic interrupt signals with an interrupt cycle setting of 1
second are output in synchronization with the increment of the second counter as illustrated in the
timing chart below.
/INTR Pin
(Increment of
second counter)
CTFG Bit
Setting CTFG bit to 0
Setting CTFG bit to 0
(Increment of
second counter)
(Increment of
second counter)

*1), *2) When the oscillation adjustment circuit is used, the interrupt cycle will fluctuate once per 20sec. as
follows:
Pulse Mode: The "L" period of output pulses will increment or decrement by a maximum of
3.784ms. For
example, 1-Hz clock pulses will have a duty cycle of 50
0.3784%.
Level Mode: A periodic interrupt cycle of 1 second will increment or decrement by a maximum of
3.784 ms.
R2051 Series
12345
Rev.2.05 - 45 -
s
Typical Applications
q
Typical Power Circuit Configurations
VDD
VSB
VCC
VSS
0.1
F
CPU Power
Supply
The case of back-up by
primary battery
CR2025
etc.
VSB
VDD
VCC
VSS
0.1
F
CPU power
supply
ML614
etc.
The case of back-up by
capacitor or secondary battery
(Charging voltage is equal to CPU
power supply voltage)
VSB
VDD
VCC
VSS
0.1
F
CPU power
supply
(3V)
5V
Double layer
capacitor
etc.
The case of back-up by
capacitor or secondary battery
(Charging voltage is not equal to
CPU power supply voltage)

VDD pin cannot be connect to any additional heavy load components such as SRAM. And VDD pin must be
connected C2, and C2 should be over 0.1
F.
VDD
CPU power supply
VCC
VSB


C3
VOLTAGE
DETECTOR
SW1
SW2
C2
R1
CPU
Vbat
-VDET1
Rcpu
R2051 Series

When secondary battery or double layer capacitor connects to VDD pin, after CPU power supply turning off,
secondray battery discharges through the root above figure. If R1 is much smaller than CPU impedance (Rcpu),
VCC voltage keeps higher than -VDET1, and SW1 keeps on. Therefore R1 must be specified by following
formula.

R1 > Rcpu x (Vbat - (-VDET1)) / (-VDET1)

R1 is specified by back-up battery or double layer capacitor, too. Please check the data sheet for back-up
devices.
q
Connection of CIN pin
Please connect capacitor over 0.1
F between CIN and VSS pin.
R2051 Series

12345
Rev.2.05 - 46 -
q
Connection of /INTR and /VDCC Pin
The /INTR and /VDCC pins follow the N-channel open drain output logic and contains no protective diode on the
power supply side. As such, it can be connected to a pull-up resistor of up to 5.5 volts regardless of supply
voltage.
VSB
OSCIN
OSCOUT
/INTR or /VDCC
*1)
32768Hz
B
A
Backup power supply
System power supply
VSS
*1) Depending on whether the /INTR and /VDCC
pins are to be used during battery backup, it
should be connected to a pull-up resistor at
the following different positions:
(1) Position A in the left diagram when it is not to
be used during battery backup.
(2) Position B in the left diagram when it is to be
used during battery backup.
R2051 Series
12345
Rev.2.05 - 47 -
s
Typical Characteristics
q
Time keeping current (ISB) vs. Supply voltage (VSB)
(Topt=25
C) Test Circuit
0
0.1
0.2
0.3
0.4
0.5
0
1
2
3
4
5
6
VSB(v)
Time keeping current (uA
)
0.1
F
0.1
F
A
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
q
Stand-by current (ICC) vs. Supply voltage (VCC)
(Topt=25
C) Test circuit
0
1
2
3
4
2
3
4
5
6
VCC(v)
S
t
and-
by
c
u
r
r
ent (
u
A
)
0.1
F
0.1
F
A
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
q
Time keeping current (ISB) vs. Operating Temperature (Topt)
(VSB=3V) Test circuit
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
-50
-25
0
25
50
75
100
Operating Temperature (Celsius)
Ti
m
e
k
eepi
ng c
u
rrent
(uA
)
0.1
F
0.1
F
A
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
R2051x01
R2051S03
R2051 Series

12345
Rev.2.05 - 48 -
q
Stand-by current (ICC) vs. Operating Temperature (Topt)
Test circuit
0
1
2
3
4
5
6
-50
-25
0
25
50
75
100
Operating temperature (Celsius)
S
t
and-by current
(uA
)
0.1
F
0.1
F
A
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
q
CPU access current vs. SCL clock frequency (kHz)
(Topt=25
C)
0
10
20
30
40
0
100
200
300
400
500
SCL clock frequency (KHz)
C
P
U
access current (uA
)
q
Oscillation frequency deviation (
f/f0) vs. Operating temperature (Topt)
(VCC=3V) Topt=25
C as standard Test circuit
-160
-140
-120
-100
-80
-60
-40
-20
0
20
-50 -25
0
25
50
75 100
Operating temperature Topt(Celsius)
Os
c
illat
i
on f
r
equenc
y
dev
iat
i
on
d
f/f0
(
p
p
m
)
0.1
F
0.1
F
Frequency
counter
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
VCC=5v
VCC=3v
VCC=5v
VCC=3v(R2051x01/02)
R2051 Series
12345
Rev.2.05 - 49 -
q
Frequency deviation (
f/f0) vs. Supply voltage (VSB/VCC)
(Topt=25
C) VCC/VSB=3V as standard Test circuit
-4
-3
-2
-1
0
1
2
0
1
2
3
4
5
6
VCC/VSB(v)
Frequenc
y
dev
iation d
f/f0(ppm)
Frequency
counter
0.1
F
0.1
F
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
q
Frequency deviation (
f/f0) vs. CGOUT
(Topt=25
C, VCC=3V)CGOUT=0pF as standard Test circuit
-40
-30
-20
-10
0
10
0
5
10
15
20
CGOUT(pF)
F
r
equency devi
a
t
i
on d
f/f0
(p
p
m
)
0.1
F
0.1
F
Frequency
counter
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
q
Detector threshold voltage (+VDET1/-VDET1) vs. Operating temperature (Topt) (VSB=3V)
(R2051S/K01) (R2051K02)
2.3
2.4
2.5
2.6
-50
-25
0
25
50
75
100
perating temperature Topt(Celsius)
D
e
tector threshold voltage
VDET1
(V)
2.7
2.8
2.9
3
-50
-25
0
25
50
75
100
perating temperature Topt(Celsius)
D
e
tector threshold voltage
VDET1
(V)
+VDET1
-VDET1
+VDET1
-VDET1
R2051 Series

12345
Rev.2.05 - 50 -
(R2051S03) Test circuit
3.8
3.9
4
4.1
4.2
4.3
4.4
-50
-25
0
25
50
75
100
perating temperature Topt(Celsius)
D
e
tector
thr
e
shold voltage
VDET1
(V)
0.1
F
0.1
F
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
q
VCC-VDD(VDDOUT1) vs. Output load current (IOUT1)
(Topt=25
C) Test circuit
-0.5
-0.4
-0.3
-0.2
-0.1
0
0
2
4
6
8
10
Output load current IOUT1(mA)
VCC-
VDD(
V)
A
0.1
F
0.1
F
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
q
VSB-VDD(VDDOUT2) vs. Output load current (IOUT2)
(Topt=25
C) Test circuit
-0.8
-0.7
-0.6
-0.5
-0.4
-0.3
-0.2
-0.1
0
0
0.5
1
1.5
2
2.5
3
Output load current IOUT2(mA)
VSB-
VDD(
V)
A
0.1
F
0.1
F
VCC
VSB
VDD
CIN
VSS
OSCIN
OSCOUT
/INTR
/VDCC
CLKOUT
SCL
SDA
VSB=3V
VSB=2V
VSB=1V
VCC=5V
VCC=3V
VCC=2.5V
+VDET1
-VDET1
R2051 Series
12345
Rev.2.05 - 51 -
q
VOL vs. IOL (/VDCC pin)
q
VOL vs. IOL (/INTR pin)
(Topt=25
C, VSB=VCC=2v) (Topt=25
C)
0
0.2
0.4
0.6
0.8
0
2
4
6
8
10
IOL(mA)
VOL(
v)
0
0.1
0.2
0.3
0.4
0
2
4
6
8
10
IOL(mA)
VOL(
v)


VCC=3V
VCC=5V
R2051 Series

12345
Rev.2.05 - 52 -
s
Typical Software-based Operations
q
Initialization at Power-on
Start
*1)
Yes
No
VDET=0?
Warning Back-up
Battery Run-down
Set Oscillation Adjustment
Register and Control
Register 1 and 2, etc.
Power-on
*2)
*4)
*3)
PON=1?
Yes
No

*1)
After power-on from 0 volt, the process of internal initialization require a time span on 1sec, so that
access should be done after /VDCC turning to OFF(H).
*2)
The PON bit setting of 0 in the Control Register 1 indicates power-on from backup battery and not
from 0v. For further details, see "P.38
s
Power-on Reset, Oscillation Halt Sensing, and Supply
Voltage Monitoring
q
PON, /XST, and VDET ".
*3)
This step is not required when the supply voltage monitoring circuit is not used.
*4)
This step involves ordinary initialization including the Oscillation Adjustment Register and interrupt
cycle settings, etc.
q
Writing of Time and Calendar Data
Write to Time Counter and
Calendar Counter
*2)
Stop Condition
*3)
Start Condition
*1)

*1) When writing to clock and calendar counters, do not insert Stop
Condition until all times from second to year have been written to
prevent error in writing time. (Detailed in "P.28 Data Transmission
under Special Condition".
*2) Any writing to the second counter will reset divider units lower than
the second digits.

*3) Take care so that process from Start Condition to Stop Condition
will be complete within 0.5sec. (Detailed in "P.28 Data
Transmission under Special Condition".

The R2051 may also be initialized not at power-on but in the
process of writing time and calendar data.
R2051 Series
12345
Rev.2.05 - 53 -
q
Reading Time and Calendar Data
(1) Ordinary Process of Reading Time and Calendar Data
Read from Time Counter
and Calendar Counter
*2)
Start Condition
Start Condition
*1)


(2) Basic Process of Reading Time and Calendar Data with Periodic Interrupt Function
*2)
Other Interrupt
Processes
Set Periodic Interrupt
Cycle Selection Bits
CTFG=1?
Read from Time Counter
and Calendar Counter
Yes
No
Control Register 2
(X1X1X011)
Generate Interrupt in CPU
*1)
*3)
*1) When reading to clock and calendar counters, do not insert Stop
Condition until all times from second to year have been written to prevent
error in writing time. (Detailed in "P.28 Data Transmission under Special
Condition".
*2) Take care so that process from Start Condition to Stop Condition will be
complete within 0.5sec. (Detailed in "P.28 Data Transmission under
Special Condition".
*1) This step is intended to select the level mode as a
waveform mode for the periodic interrupt function.
*2) This step must be completed within 0.5 second.
*3) This step is intended to set the CTFG bit to 0 in the
Control Register 2 to cancel an interrupt to the CPU.
R2051 Series

12345
Rev.2.05 - 54 -

(3) Applied Process of Reading Time and Calendar Data with Periodic Interrupt Function
Time data need not be read from all the time counters when used for such ordinary purposes as time count
indication. This applied process can be used to read time and calendar data with substantial reductions in the
load involved in such reading.

For Time Indication in "Day-of-Month, Day-of-week, Hour, Minute, and Second" Format:

*2)
Other interrupts
Processes
Sec.=00?
Yes
No
Generate interrupt to CPU
*1)
*3)
CTFG=1?
Control Register 2
(X1X1X011)
Yes
Read Min.,Hr.,Day,
and Day-of-week
*4)
No
Control Register 1
(XXXX0100)
Control Register 2
(X1X1X011)
Use previous Min.,Hr.,
Day, and Day-of-week data
*1) This step is intended to select the level
mode as a waveform mode for the
periodic interrupt function.
*2) This step must be completed within 0.5
sec.
*3) This step is intended to read time data
from all the time counters only in the
first session of reading time data after
writing time data.
*4) This step is intended to set the CTFG
bit to 0 in the Control Register 2 to
cancel an interrupt to the CPU.
R2051 Series
12345
Rev.2.05 - 55 -
q
Interrupt Process
(1) Periodic Interrupt
*2)
Other Interrupt
Processes
Set Periodic Interrupt
Cycle Selection Bits
CTFG=1?
Conduct
Periodic Interrupt
Yes
No
Control Register 2
(X1X1X011)
Generate Interrupt to CPU
*1)

(2) Alarm Interrupt
*3)
Other Interrupt
Processes
Set Alarm Min., Hr., and
Day-of-week Registers
WAFG or DAFG=1?
Conduct Alarm Interrupt
Yes
No
Control Register 2
(X1X1X101)
Generate Interrupt to CPU
*1)
WALE or DALE
0
*2)
WALE or DALE
1
*1) This step is intended to once disable the alarm
interrupt circuit by setting the WALE or DALE bits to 0
in anticipation of the coincidental occurrence of a
match between current time and preset alarm time in
the process of setting the alarm interrupt function.
*2) This step is intended to enable the alarm interrupt
function after completion of all alarm interrupt settings.
*3) This step is intended to once cancel the alarm
interrupt function by writing the settings of "X,1,X,
1,X,1,0,1" and "X,1,X,1,X,1,1,0" to the Alarm_W
Registers and the Alarm_D Registers, respectively.
*1) This step is intended to select the level mode as a
waveform mode for the periodic interrupt function.
*2) This step is intended to set the CTFG bit to 0 in
the Control Register 2 to cancel an interrupt to the
CPU.